Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop P
Sequence Number 2
Notes
Date Text
2007-08-27 18:55:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT
 NUMBERS TO REMAIN THE SAME.
  
 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE
 FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN
 THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES
 NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE
 DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN
 REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE
 NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL
 SHEETS WITH ARCHITECTURAL TITLE BLOCK.
  
 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO
 HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES
 WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO
 INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION
 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT
 SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER
 CLOSETS. PLEASE CLARIFY.
 ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS
 REQUIRED FOR SEALANT OF CONCRETE TO VERIFY
 NONABSORBENCY. ALSO THE FINISH SCHEDULE CALLS FOR
 CERAMIC TILE FOR THE FLOOR. PLEASE CLARIFY. SECTION
 106.1.1.
  
 3. OK
  
 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE
 SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET
 ROOMS)
  
 __FOR W/C'S:
 A. OK
 B. OK
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED
 E. OK
  
 __FOR URINALS:
 A. 11-4.18.2 OK
 B. 11-4.18.3 OK
 C. 11-4.18.4 OK
  
 __FOR LAVS:
 A. 11-4.19.2 OK
 B. 11-4.19.3 OK
 C. 11-4.19.4 OK
 D. 11-4.19.5 FAUCETS ****NOT ADDRESSED
 E. 11-4.19.6 OK
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT NOT ALL CUT SECTIONS INDICATE
 THE LENGTH. SEE THE SECTIONS DOWNSTREAM OF THE DROP,
 (7'0")THRU THE RISE SECTION AFTER THE SOLENOID VALVE
 AND THE 3 SECTIONS AFTER THE 13'6" LENGTH OF PIPE
 DOWNSTREAM OF THE SOLENOID VALVE. PLEASE CHECK THAT
 ---ALL--- CUT SECTIONS INDICATE THE LENGTH. SCALING THE
 RISER ON SHEET P1.03 DOES NOT CORRELATE WITH
 MEASURMENTS ON THE RISER ISOMETRIC. PLEASE CHECK ALL
 MEASUREMENTS FOR THE LENGHTS OF PIPE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
 ****RESPONSE NOTED, BUT NOT INDICATED ON THE PLANS.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN
 COMMENT (A) IS ADDRESSED.
 ****RESPONSE NOTED, BUT WILL BE VERIFIED AFTER ALL CUT
 SECTION LENGTHS ARE INDICATED IN COMMENT A.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT FLORIDA PUBLIC UTILITIES ONLY
 DELIVERS 2PSI OR .5PSI. PLEASE INDICATE THE DELIVERY
 PRESSURE.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT
 FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE
 WITH ARCHITECT.
  
 F. N/A
 G. N/A
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND
 UNION ARE NOT INDICATED ON THE RISER DIAGRAM AS
 REQUIRED.
  
 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER
 DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A
 FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT
 WASTE.
 ****RESPONSE NOTED, BUT RISER INDICATES A MOP SINK, NOT
 HUB DRAIN AS INDICATED IN COMMENT RESPONSE.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV
 BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE
 FLOOR FOR SERVICING & TESTING.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED
 AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN
 INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED.
  
 12. OK
 13. OK
 14. OK
  
 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS
 K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE
 TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED
 TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY
 DBPR.
 ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE
 THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT
 APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS
 OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN
 ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR
 EACH SET OF PLANS.
  
 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON
 THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED.
 PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS
 SUBMITTED.SECTION 106.1.
 ****RESPONSE NOTED, BUT SEE COMMENT 15 AND MAKE SURE
 THE SHEET INDEX REFLECT SHEETS SUBMITTED.
  
 ***********NEW COMMENTS**********
  
 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT
 CONNECT TO THE SANITARY DIRECTLY. SECTION 108.1.2.
 INDIRECT CONNECTION REQUIRED.
  
 2B. SHT P102 THE FLOOR SINK AT FIXTURES 49 & 50 SHALL
 CONNECT TO THE VENTED LINE SEPARATELY. AS SHOWN IT
 CONNECTS TO THE LINE TO THE FLOOR SINK FOR FIXTURES
 41.1 & 44. SECTION 912.2.4.
  
 3B. SHT P2.01 THE SANITARY ISOMETRIC RISER DIAGRAM, THE
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE
 TOILET ROOM NEXT TO THE OFFICE. THE RISER DIAGRAM SHOWS
 A FLOOR DRAIN NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1.
  
 4B. SHT P2.01 THE GREASE ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE VENT DOWNSTREAM OF THE
 FLOOR SINK FOR FIXTURE 55SHOWN ON THE FLOOR PLAN IS
 NOT INDICATED ON THE RISER DIAGRAM. PLEASE CORRELATE.
 --THE FLOOR SINK FOR FIXTURES 49 & 50 SHALL CONNECTED
 TO THE VENTED MAIN LINE SEPARATELY. SECTION 106.1.1 &
 SECTION 912.2.4. (SEE COMMENT 2B).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved