| Date |
Text |
| 2007-08-27 18:55:24 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT |
| | NUMBERS TO REMAIN THE SAME. |
| | |
| | 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE |
| | FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN |
| | THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219, |
| | 481.2055. |
| | ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES |
| | NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE |
| | DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE |
| | TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN |
| | REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE |
| | NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL |
| | SHEETS WITH ARCHITECTURAL TITLE BLOCK. |
| | |
| | 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO |
| | HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES |
| | WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT |
| | SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO |
| | INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION |
| | 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT |
| | SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER |
| | CLOSETS. PLEASE CLARIFY. |
| | ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS |
| | REQUIRED FOR SEALANT OF CONCRETE TO VERIFY |
| | NONABSORBENCY. ALSO THE FINISH SCHEDULE CALLS FOR |
| | CERAMIC TILE FOR THE FLOOR. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 3. OK |
| | |
| | 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE |
| | SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET |
| | ROOMS) |
| | |
| | __FOR W/C'S: |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED |
| | E. OK |
| | |
| | __FOR URINALS: |
| | A. 11-4.18.2 OK |
| | B. 11-4.18.3 OK |
| | C. 11-4.18.4 OK |
| | |
| | __FOR LAVS: |
| | A. 11-4.19.2 OK |
| | B. 11-4.19.3 OK |
| | C. 11-4.19.4 OK |
| | D. 11-4.19.5 FAUCETS ****NOT ADDRESSED |
| | E. 11-4.19.6 OK |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO |
| | ISSUING THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT NOT ALL CUT SECTIONS INDICATE |
| | THE LENGTH. SEE THE SECTIONS DOWNSTREAM OF THE DROP, |
| | (7'0")THRU THE RISE SECTION AFTER THE SOLENOID VALVE |
| | AND THE 3 SECTIONS AFTER THE 13'6" LENGTH OF PIPE |
| | DOWNSTREAM OF THE SOLENOID VALVE. PLEASE CHECK THAT |
| | ---ALL--- CUT SECTIONS INDICATE THE LENGTH. SCALING THE |
| | RISER ON SHEET P1.03 DOES NOT CORRELATE WITH |
| | MEASURMENTS ON THE RISER ISOMETRIC. PLEASE CHECK ALL |
| | MEASUREMENTS FOR THE LENGHTS OF PIPE. |
| | |
| | B. TYPE OF GAS, (LP OR NATURAL). |
| | ****RESPONSE NOTED, BUT NOT INDICATED ON THE PLANS. |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN |
| | COMMENT (A) IS ADDRESSED. |
| | ****RESPONSE NOTED, BUT WILL BE VERIFIED AFTER ALL CUT |
| | SECTION LENGTHS ARE INDICATED IN COMMENT A. |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, BUT FLORIDA PUBLIC UTILITIES ONLY |
| | DELIVERS 2PSI OR .5PSI. PLEASE INDICATE THE DELIVERY |
| | PRESSURE. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT |
| | FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE |
| | WITH ARCHITECT. |
| | |
| | F. N/A |
| | G. N/A |
| | |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND |
| | UNION ARE NOT INDICATED ON THE RISER DIAGRAM AS |
| | REQUIRED. |
| | |
| | 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER |
| | DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A |
| | FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT |
| | WASTE. |
| | ****RESPONSE NOTED, BUT RISER INDICATES A MOP SINK, NOT |
| | HUB DRAIN AS INDICATED IN COMMENT RESPONSE. |
| | |
| | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV |
| | BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE |
| | FLOOR FOR SERVICING & TESTING. |
| | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED |
| | AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN |
| | INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED. |
| | |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS |
| | K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE |
| | TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS |
| | REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED |
| | TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY |
| | DBPR. |
| | ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE |
| | THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT |
| | APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS |
| | OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN |
| | ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR |
| | EACH SET OF PLANS. |
| | |
| | 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON |
| | THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED. |
| | PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS |
| | SUBMITTED.SECTION 106.1. |
| | ****RESPONSE NOTED, BUT SEE COMMENT 15 AND MAKE SURE |
| | THE SHEET INDEX REFLECT SHEETS SUBMITTED. |
| | |
| | ***********NEW COMMENTS********** |
| | |
| | 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT |
| | CONNECT TO THE SANITARY DIRECTLY. SECTION 108.1.2. |
| | INDIRECT CONNECTION REQUIRED. |
| | |
| | 2B. SHT P102 THE FLOOR SINK AT FIXTURES 49 & 50 SHALL |
| | CONNECT TO THE VENTED LINE SEPARATELY. AS SHOWN IT |
| | CONNECTS TO THE LINE TO THE FLOOR SINK FOR FIXTURES |
| | 41.1 & 44. SECTION 912.2.4. |
| | |
| | 3B. SHT P2.01 THE SANITARY ISOMETRIC RISER DIAGRAM, THE |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE |
| | TOILET ROOM NEXT TO THE OFFICE. THE RISER DIAGRAM SHOWS |
| | A FLOOR DRAIN NOT SHOWN ON THE FLOOR PLAN. PLEASE |
| | CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 4B. SHT P2.01 THE GREASE ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. THE VENT DOWNSTREAM OF THE |
| | FLOOR SINK FOR FIXTURE 55SHOWN ON THE FLOOR PLAN IS |
| | NOT INDICATED ON THE RISER DIAGRAM. PLEASE CORRELATE. |
| | --THE FLOOR SINK FOR FIXTURES 49 & 50 SHALL CONNECTED |
| | TO THE VENTED MAIN LINE SEPARATELY. SECTION 106.1.1 & |
| | SECTION 912.2.4. (SEE COMMENT 2B). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |