| Date |
Text |
| 2007-08-25 09:50:47 | |
| | 2007-08-25 09:50:47 |
| | |
| | *** DENIED2ND REVIEW *** |
| | |
| | *** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON SOME INFORMATION ON REVISED PLANS. |
| | SOME INFORMATION IS ONLY NOW BEING SUBMITTED FOR |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE DESIGN |
| | TEAM QUOTES THIS REVIEWER'S COMMENTS AND THEN CONTAINS |
| | A RESPONSE BELOW. PLEASE SEE THERE ARE NUMEROUS |
| | INSTANCES WHERE THE TYPEWRITTEN NOTES OF THIS |
| | REVIEWER'S COMMENTS ARE NOT WHAT WERE TYPED IN THE |
| | PREVIOUS REVIEW. |
| | SOME ARE TYPED AS STATING THE REVIEWER HAS REQUIRED |
| | CERTAIN ITEMS WHICH ARE NOT THE CASE. PLEASE SEE THE |
| | FOLLOWING FOR EXAMPLE. |
| | **RESPONSE TO COMMENT #2 FROM PREVIOUS REVIEW IN |
| | LETTER. |
| | PART OF THE REVIEW COMMENT MENTIONS: *PLANS ONLY SHOW |
| | STANDARD SWITCHES* AND THE RESPONSE LETTER TYPES |
| | *PLEASE ONLY SHOW STANDARD SWITCHES*. |
| | THIS WOULD COMPLETELY CHANGE THE CODE REQUIRED ITEM. IF |
| | THE RESPONSE LETTER IS GOING TO *QUOTE* REVIEWER'S |
| | COMMENTS PLEASE BE SURE TO ACCURATELY PLACE ACTUAL |
| | NOTES. |
| | |
| | 2) NOTE: PLEASE SEE COMMENT #2 FROM PREVIOUS REVIEW |
| | WHICH REQUESTED COMPLIANCE WITH THE FBC CHAPTER 13. |
| | THIS IS THE FIRST REVIEW FOR SOME INFORMATION SUBMITTED |
| | FOR CHAPTER 13. |
| | PLEASE SEE THERE ARE MANY ITEMS WHICH STILL NEED TO BE |
| | ADDRESSED: |
| | PLEASE SEE NOTE #3 BELOW WITH RESPECT TO THE ENERGY |
| | CALCULATIONS. |
| | |
| | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | DO NOT REFLECT THE SAME INFORMATION AS SHOWN ON PLANS. |
| | THE INPUT DATA REPORT CONTAINS INPUT OF LIGHTING |
| | LUMINARIES WHICH ARE NOT ON PLANS AND ALSO THE PLANS |
| | CONTAIN LIGHTING FIXTURES WHICH ARE NOT INPUTTED INTO |
| | THE REPORT. |
| | PLEASE SEE SHEET 2 OF THE IDR WHICH CONTAINS ONLY SEVEN |
| | LUMINARIES, HOW IS THIS POSSIBLE WHEN THE PLANS |
| | INDICATE A SUBSTANTIALLY HIGHER AMOUNT OF FIXTURES? |
| | PLEASE SEE THE WATTAGE OF THESE DO NOT CORRELATE WITH |
| | THE FIXTURE LEGEND AND FIXTURES ON PLANS. |
| | PLEASE SEE THE LIGHTING POWER DENSITIES CALCULATIONS |
| | INDICATE DIFFERENT WATTAGES THAN ON PLANS AND WHAT IS |
| | SHOWN ON CALCULATIONS. 13-415.1.A, 13-415.2 |
| | PLEASE SEE NO EXTERIOR LIGHTING WAS ENTERED YET PLANS |
| | CONTAIN THESE LIGHTING FIXTURES 13-415.2.ABC.1.3. THE |
| | CALCULATIONS AS SUBMITTED ARE UNDER METHOD A. THE PLANS |
| | ARE INDICATING THE TABLE 13-415.2.C.1 |
| | PLEASE EXPLAIN AND COORDINATE. |
| | |
| | 4) NOTE:PLEASE SEE NO INFORMATION IS SHOWN FOR THE |
| | MINIMUM LOADS FOR TRACK LIGHTING AS REQUIRED AND STATED |
| | IN THE PREVIOUS REVIEW. THIS SECTION OF THE CODE WAS |
| | SPECIFICALLY QUOTED ON THE PREVIOUS REVIEW AS TRACK |
| | LIGHTING INPUT IS OFTEN NOT CORRECT IN |
| | DESIGNS.13-415.2.ABC.1.2. |
| | |
| | 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED |
| | INFORMATION AND DESIGNS FOR 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE SEE ONLY SOME INFORMATION WAS SUBMITTED AND |
| | SHOWN ON PLANS. |
| | PLEASE SEE THE PLANS STATE THERE IS GOING TO THE A |
| | LIGHTING CONTROL PANEL HOWEVER NO INFORMATION WAS SHOWN |
| | FOR SCHEDULING , ALL OVER RIDE LOCATIONS, AND MAXIMUM |
| | TIMES ON OVER RIDES AND DEVICES FOR LIGHTING CONTROLS. |
| | PLANS INDICATE SEVERAL OS TYPE DEVICES, HOWEVER NO |
| | MAXIMUM TIMES ON THESE DEVICES. |
| | PLEASE SEE THE LOCATIONS REQUIRED FOR OVER RIDES WERE |
| | NOT CLEAR AT ALL OF THE LOCATIONS REQUIRED. |
| | COULD NOT LOCATE CONTROLS FOR DISPLAY OR ACCENT |
| | LIGHTING WHICH IS SHOWN ON PLANS. |
| | PLEASE SEE THERE ARE SEVERAL LOCATIONS ON PLANS WHICH |
| | STILL ONLY CONTAIN STANDARD CONTROL SWITCHES. (SOME OF |
| | THESE LOCATIONS ARE REDLINED) |
| | PLEASE INCLUDE INFORMATION FOR ZONES AND SQ FT AS |
| | REQUIRED PER 13-415.1.ABC.1.2 |
| | PLEASE SEE THE LIGHTING PLANS INDICATE A NOTE #2 ON THE |
| | COOLER LIGHTS WHICH MENTIONS TO WIRE THROUGH LIGHTING |
| | CONTROL PANEL. HOW IS THIS POSSIBLE WHEN THE LIGHTING |
| | CONTROL PANEL IS 120/208V AND THE CIRCUIT NOTED IS |
| | 277/480V? PLEASE COORDINATE ALL.(KITCHEN LIGHTING NOTED |
| | ON THIS SAME CIRCUIT ON PANEL SCHEDULE) |
| | PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION |
| | AT THIS TIME. SOME ARE NOTED TO BE *SELECTED BY OWNER* |
| | HOWEVER THE MINIMUM ARE REQUIRED AT THIS TIME. THESE |
| | CAN ALWAYS BE REVISED AT A LATER DATE IF NEEDED.( |
| | PREVIOUS NOTE #18) |
| | PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS |
| | WHICH CAN NOT BE REVIEWED AT THIS TIME. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | IN FACT CONTAIN A PHOTO-COPIED SIGNATURE ON THE |
| | CERTIFICATION SHEETS WHEN THESE ARE REQUIRED TO BE |
| | SIGNED, SEALED AND DATED PER FLORIDA STATUTES 471.025, |
| | 481.221. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND |
| | FBC 13-103.1.1.1 |
| | PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON |
| | SHEETS. |
| | |
| | 7) NOTE:PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS |
| | FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC |
| | 11.4-28.1, .2 AND .3(4). |
| | ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE |
| | SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING |
| | PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM. |
| | FBC 106.3.5.1.1 |
| | THIS NOTE WAS NOTE #9 ON THE PREVIOUS REVIEW AND |
| | REMAINS. THE RESPONSE FROM THE ENGINEERING FIRM STATES |
| | *NOT PROVIDED* BY FIRM. |
| | THE RESPONSE FROM THE ARCHITECT MENTIONS TO SEE A3.2 |
| | HOWEVER PLEASE SEE THE DEVICES AS SHOWN ON THIS SHEET |
| | DO NOT MEET THE LOCATIONS AS REQUIRED. PLEASE ALSO SEE |
| | THE SYMBOL BEING USED FOR HORNS, STROBES OR |
| | HORN/STROBES IS NOT THAT OF THE STANDARD USE IN THE |
| | INDUSTRY AND ON PLANS. |
| | PLEASE SUBMIT COMPLETED INFORMATION FOR MINIMUM DESIGN |
| | FOR BASE FIRE ALARM DEVICES ON BASE BUILD OUT PLANS AS |
| | REQUIRED PER FS 633 AND 106.3.5.1.2 OF THE FBC |
| | ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST |
| | PALM BEACH. |
| | |
| | 8) NOTE:PLEASE SEE THE PREVIOUS NOTE #13 IS STILL IN |
| | NEED OF ADDRESSING. THE ELECTRICAL PLANS AS REQUIRED DO |
| | NOT CONTAIN THE REQUIRED AND NEEDED INFORMATION FOR THE |
| | TRANSFORMER INSTALLATION AS PREVIOUSLY REQUESTED. A |
| | NOTE ON THE ELECTRICAL SHEET MENTIONS TO SEE THE |
| | ARCHITECTURAL AND/OR STRUCTURAL SHEETS HOWEVER NO |
| | COMPLETED INFORMATION WAS LOCATED ON THESE SHEETS. THIS |
| | IS A LIFE SAFETY, FIRE, AND PROPERTY HAZARD ISSUE. |
| | SERIOUS INJURY OR DEATH COULD RESULT IN AN INSTALLATION |
| | OF EQUIPMENT OF THIS NATURE WHICH IS IMPROPERLY |
| | INSTALLED. THIS INFORMATION IS NEEDED ON PLANS FOR THE |
| | CODE REQUIRED INSTALLATION AT THIS TIME. PLANS MAY NOT |
| | SIMPLY STATE TO SEE OTHER SHEETS. PLEASE KNOW THAT |
| | THESE UNITS CREATE A SUBSTANTIAL AMOUNT OF HEAT AND |
| | BEING LOCATED NEAR EASILY IGNITABLE MATERIALS AND |
| | COMBUSTIBLES IS STRICTLY PROHIBITED. PLEASE SEE 110.26, |
| | 240.24A, C AND D, 450.9, 450.13, 450.21-450.27. AS NO |
| | INFORMATION SPECIFICALLY IS SHOWN ON THE TRANSFORMER |
| | SECTIONS .21-.27 ARE BEING NOTED. PLEASE KNOW THIS |
| | PROPOSED LOCATION ABOVE THE AREA AS STATED IS NOT |
| | PERMITTED. |
| | PLEASE SEE NO STRUCTURAL INFORMATION WAS SUBMITTED FOR |
| | SUPPORT AS THE PLANS STATE THIS WILL BE LOCATED OFF THE |
| | FLOOR. |
| | ** CAREFUL CONSIDERATION IS TO BE GIVEN ON THE |
| | LOCATION. |
| | |
| | *** PREVIOUS REVIEW NOTE**** |
| | PLEASE SEE THE PLANS ARE MISSING THE LOCATION FOR THE |
| | REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE 110.26 |
| | AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT THIS |
| | TIME. |
| | PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT |
| | BE ABOVE CEILING. |
| | PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS |
| | TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE |
| | INSTALLED. |
| | ** PLANS CURRENTLY MENTION THE LOCATION OF THE |
| | TRANSFORMER IS TO BE DETERMINED BY THE BUILDING |
| | ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON |
| | WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT |
| | WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL |
| | SUPPORT ETC. |
| | ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME** |
| | |
| | |
| | 9) NOTE: THIS NOTE REMAINS FROM THE PREVIOUS REVIEW. |
| | PLEASE SEE THE RESPONSE MENTIONS THERE ARE NO OTHER |
| | LOADS ON THIS MAIN. THIS NOTED EXISTING MAIN IS NOT |
| | KNOWN BY THIS OFFICE BEING DIRECTLY FROM FPL WITH ITS |
| | OWN SERVICE AS BEING SHOWN ON THE REVISED RISER. PLEASE |
| | KNOW THAT A FIELD INSPECTION WILL NEED TO BE PERFORMED |
| | TO GO OVER THE SERVICES AND EQUIPMENT AT THIS LOCATION. |
| | THIS OFFICE WILL NEED TO BE IN CONTACT WITH THE |
| | LANDLORDS OFFICE TO OBTAIN ACCESS TO LOCATION. |
| | AS REQUESTED FROM PREVIOUS REVIEW: |
| | **PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS ON |
| | SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN SERVICE |
| | WITH NEW LOAD ADDED. |
| | THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON |
| | *L*. |
| | 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42 |
| | ETC |
| | NEC 220 WAS GIVEN IN GENERAL AS THERE ARE TOO MANY |
| | SPECIFIC CODE SECTIONS WHICH APPLY FROM 220. (TRACK |
| | LTS, LIGHTING, RECEPTACLES) ETC. |
| | FBC 106.3.5.1.2, 106.1.2. |
| | ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER |
| | POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT |
| | THE LOAD CALCULATIONS ON MAIN SERVICE. |
| | |
| | 10) NOTE:THE PREVIOUS REVIEW NOTE #20 REQUESTED |
| | COORDINATION OF SHUNT TRIP BREAKERS FOR EQUIPMENT. MOST |
| | OF THIS SEEMS TO BE DONE HOWEVER PLEASE SEE THE |
| | EQUIPMENT SCHEDULES ON E1.02 AND BE SURE ALL |
| | COORDINATE. |
| | PLEASE KNOW MANY OF THESE ITEMS SEEM TO BE MISPRINTS |
| | FOR ACTUAL LOADS ETC. |
| | REDLINED SHEETS ON ONE SET. FBC 106.1.2 FOR |
| | COORDINATION. |
| | MAY CALL TO GO OVER. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL |
| | ELECTRICAL UNDER HOODS PER NFPA-96. |
| | PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS |
| | HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL. |
| | |
| | 11) NOTE: THIS NOTE REMAINS FROM PREVIOUS REVIEW NOTE # |
| | 22. THE ENGINEER'S FIRM RESPONSE MENTIONS *NOT |
| | PROVIDED* PER FIRM. |
| | THE ARCHITECT'S RESPONSE MENTIONS THIS WAS COMPLETED IN |
| | TITLE BLOCKS HOWEVER UPON REVIEW OF SEVERAL SHEETS |
| | INCLUDING CHECKING THE TITLE BLOCKS OF OTHER TRADES, |
| | THIS WAS NOT COMPLETED AS NEEDED AND AS REQUESTED. |
| | PLEASE BE SURE THE TITLE BLOCKS REFLECT THE ADDRESS AND |
| | SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC 61G15-23.002, |
| | 61G1-16.004 |
| | |
| | 12) NOTE: PLEASE CLARIFY HOW IT IS DIMMERS ARE BEING |
| | SHOWN ON LIGHTING WHICH IS LOCATED IN THE EGRESS |
| | PATHS. |
| | PLEASE SEE LS 101 7.8 AND 7.9. |
| | PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THESE |
| | PATHS. |
| | PLEASE SEE FAC 61G15-33.004. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE ATTACHED COPY OF FS 553.80(2)(B) |
| | WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND |
| | ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE |
| | AT THIS TIME. |
| | |
| | AS STATED ON THE PREVIOUS REVIEW: |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-08-25 07:55:04 | 2007-08-25 07:55:04 |
| | |
| | REVIEW CONTINUED |
| 2007-08-24 21:04:56 | 2007-08-24 21:04:56 |
| | |
| | PLANS ARE IN ELEC FOR REVIEW. |
| | REVIEW TO CONTINUE ON 8/25, NOTES WILL FOLLOW ONCE |
| | REVIEW IS COMPLETE. |
| | PLANS WILL BE GOING INTO A *F* STATUS. |