Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-25 09:50:47 
 2007-08-25 09:50:47
  
 *** DENIED2ND REVIEW ***
  
 *** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON SOME INFORMATION ON REVISED PLANS.
 SOME INFORMATION IS ONLY NOW BEING SUBMITTED FOR
 REVIEW.
  
 1) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE DESIGN
 TEAM QUOTES THIS REVIEWER'S COMMENTS AND THEN CONTAINS
 A RESPONSE BELOW. PLEASE SEE THERE ARE NUMEROUS
 INSTANCES WHERE THE TYPEWRITTEN NOTES OF THIS
 REVIEWER'S COMMENTS ARE NOT WHAT WERE TYPED IN THE
 PREVIOUS REVIEW.
 SOME ARE TYPED AS STATING THE REVIEWER HAS REQUIRED
 CERTAIN ITEMS WHICH ARE NOT THE CASE. PLEASE SEE THE
 FOLLOWING FOR EXAMPLE.
 **RESPONSE TO COMMENT #2 FROM PREVIOUS REVIEW IN
 LETTER.
 PART OF THE REVIEW COMMENT MENTIONS: *PLANS ONLY SHOW
 STANDARD SWITCHES* AND THE RESPONSE LETTER TYPES
 *PLEASE ONLY SHOW STANDARD SWITCHES*.
 THIS WOULD COMPLETELY CHANGE THE CODE REQUIRED ITEM. IF
 THE RESPONSE LETTER IS GOING TO *QUOTE* REVIEWER'S
 COMMENTS PLEASE BE SURE TO ACCURATELY PLACE ACTUAL
 NOTES.
  
 2) NOTE: PLEASE SEE COMMENT #2 FROM PREVIOUS REVIEW
 WHICH REQUESTED COMPLIANCE WITH THE FBC CHAPTER 13.
 THIS IS THE FIRST REVIEW FOR SOME INFORMATION SUBMITTED
 FOR CHAPTER 13.
 PLEASE SEE THERE ARE MANY ITEMS WHICH STILL NEED TO BE
 ADDRESSED:
 PLEASE SEE NOTE #3 BELOW WITH RESPECT TO THE ENERGY
 CALCULATIONS.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT REFLECT THE SAME INFORMATION AS SHOWN ON PLANS.
 THE INPUT DATA REPORT CONTAINS INPUT OF LIGHTING
 LUMINARIES WHICH ARE NOT ON PLANS AND ALSO THE PLANS
 CONTAIN LIGHTING FIXTURES WHICH ARE NOT INPUTTED INTO
 THE REPORT.
 PLEASE SEE SHEET 2 OF THE IDR WHICH CONTAINS ONLY SEVEN
 LUMINARIES, HOW IS THIS POSSIBLE WHEN THE PLANS
 INDICATE A SUBSTANTIALLY HIGHER AMOUNT OF FIXTURES?
 PLEASE SEE THE WATTAGE OF THESE DO NOT CORRELATE WITH
 THE FIXTURE LEGEND AND FIXTURES ON PLANS.
 PLEASE SEE THE LIGHTING POWER DENSITIES CALCULATIONS
 INDICATE DIFFERENT WATTAGES THAN ON PLANS AND WHAT IS
 SHOWN ON CALCULATIONS. 13-415.1.A, 13-415.2
 PLEASE SEE NO EXTERIOR LIGHTING WAS ENTERED YET PLANS
 CONTAIN THESE LIGHTING FIXTURES 13-415.2.ABC.1.3. THE
 CALCULATIONS AS SUBMITTED ARE UNDER METHOD A. THE PLANS
 ARE INDICATING THE TABLE 13-415.2.C.1
 PLEASE EXPLAIN AND COORDINATE.
  
 4) NOTE:PLEASE SEE NO INFORMATION IS SHOWN FOR THE
 MINIMUM LOADS FOR TRACK LIGHTING AS REQUIRED AND STATED
 IN THE PREVIOUS REVIEW. THIS SECTION OF THE CODE WAS
 SPECIFICALLY QUOTED ON THE PREVIOUS REVIEW AS TRACK
 LIGHTING INPUT IS OFTEN NOT CORRECT IN
 DESIGNS.13-415.2.ABC.1.2.
  
 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED
 INFORMATION AND DESIGNS FOR 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE ONLY SOME INFORMATION WAS SUBMITTED AND
 SHOWN ON PLANS.
 PLEASE SEE THE PLANS STATE THERE IS GOING TO THE A
 LIGHTING CONTROL PANEL HOWEVER NO INFORMATION WAS SHOWN
 FOR SCHEDULING , ALL OVER RIDE LOCATIONS, AND MAXIMUM
 TIMES ON OVER RIDES AND DEVICES FOR LIGHTING CONTROLS.
 PLANS INDICATE SEVERAL OS TYPE DEVICES, HOWEVER NO
 MAXIMUM TIMES ON THESE DEVICES.
 PLEASE SEE THE LOCATIONS REQUIRED FOR OVER RIDES WERE
 NOT CLEAR AT ALL OF THE LOCATIONS REQUIRED.
 COULD NOT LOCATE CONTROLS FOR DISPLAY OR ACCENT
 LIGHTING WHICH IS SHOWN ON PLANS.
 PLEASE SEE THERE ARE SEVERAL LOCATIONS ON PLANS WHICH
 STILL ONLY CONTAIN STANDARD CONTROL SWITCHES. (SOME OF
 THESE LOCATIONS ARE REDLINED)
 PLEASE INCLUDE INFORMATION FOR ZONES AND SQ FT AS
 REQUIRED PER 13-415.1.ABC.1.2
 PLEASE SEE THE LIGHTING PLANS INDICATE A NOTE #2 ON THE
 COOLER LIGHTS WHICH MENTIONS TO WIRE THROUGH LIGHTING
 CONTROL PANEL. HOW IS THIS POSSIBLE WHEN THE LIGHTING
 CONTROL PANEL IS 120/208V AND THE CIRCUIT NOTED IS
 277/480V? PLEASE COORDINATE ALL.(KITCHEN LIGHTING NOTED
 ON THIS SAME CIRCUIT ON PANEL SCHEDULE)
 PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION
 AT THIS TIME. SOME ARE NOTED TO BE *SELECTED BY OWNER*
 HOWEVER THE MINIMUM ARE REQUIRED AT THIS TIME. THESE
 CAN ALWAYS BE REVISED AT A LATER DATE IF NEEDED.(
 PREVIOUS NOTE #18)
 PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS
 WHICH CAN NOT BE REVIEWED AT THIS TIME.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 IN FACT CONTAIN A PHOTO-COPIED SIGNATURE ON THE
 CERTIFICATION SHEETS WHEN THESE ARE REQUIRED TO BE
 SIGNED, SEALED AND DATED PER FLORIDA STATUTES 471.025,
 481.221.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FBC 13-103.1.1.1
 PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON
 SHEETS.
  
 7) NOTE:PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS
 FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC
 11.4-28.1, .2 AND .3(4).
 ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE
 SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING
 PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM.
 FBC 106.3.5.1.1
 THIS NOTE WAS NOTE #9 ON THE PREVIOUS REVIEW AND
 REMAINS. THE RESPONSE FROM THE ENGINEERING FIRM STATES
 *NOT PROVIDED* BY FIRM.
 THE RESPONSE FROM THE ARCHITECT MENTIONS TO SEE A3.2
 HOWEVER PLEASE SEE THE DEVICES AS SHOWN ON THIS SHEET
 DO NOT MEET THE LOCATIONS AS REQUIRED. PLEASE ALSO SEE
 THE SYMBOL BEING USED FOR HORNS, STROBES OR
 HORN/STROBES IS NOT THAT OF THE STANDARD USE IN THE
 INDUSTRY AND ON PLANS.
 PLEASE SUBMIT COMPLETED INFORMATION FOR MINIMUM DESIGN
 FOR BASE FIRE ALARM DEVICES ON BASE BUILD OUT PLANS AS
 REQUIRED PER FS 633 AND 106.3.5.1.2 OF THE FBC
 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 8) NOTE:PLEASE SEE THE PREVIOUS NOTE #13 IS STILL IN
 NEED OF ADDRESSING. THE ELECTRICAL PLANS AS REQUIRED DO
 NOT CONTAIN THE REQUIRED AND NEEDED INFORMATION FOR THE
 TRANSFORMER INSTALLATION AS PREVIOUSLY REQUESTED. A
 NOTE ON THE ELECTRICAL SHEET MENTIONS TO SEE THE
 ARCHITECTURAL AND/OR STRUCTURAL SHEETS HOWEVER NO
 COMPLETED INFORMATION WAS LOCATED ON THESE SHEETS. THIS
 IS A LIFE SAFETY, FIRE, AND PROPERTY HAZARD ISSUE.
 SERIOUS INJURY OR DEATH COULD RESULT IN AN INSTALLATION
 OF EQUIPMENT OF THIS NATURE WHICH IS IMPROPERLY
 INSTALLED. THIS INFORMATION IS NEEDED ON PLANS FOR THE
 CODE REQUIRED INSTALLATION AT THIS TIME. PLANS MAY NOT
 SIMPLY STATE TO SEE OTHER SHEETS. PLEASE KNOW THAT
 THESE UNITS CREATE A SUBSTANTIAL AMOUNT OF HEAT AND
 BEING LOCATED NEAR EASILY IGNITABLE MATERIALS AND
 COMBUSTIBLES IS STRICTLY PROHIBITED. PLEASE SEE 110.26,
 240.24A, C AND D, 450.9, 450.13, 450.21-450.27. AS NO
 INFORMATION SPECIFICALLY IS SHOWN ON THE TRANSFORMER
 SECTIONS .21-.27 ARE BEING NOTED. PLEASE KNOW THIS
 PROPOSED LOCATION ABOVE THE AREA AS STATED IS NOT
 PERMITTED.
 PLEASE SEE NO STRUCTURAL INFORMATION WAS SUBMITTED FOR
 SUPPORT AS THE PLANS STATE THIS WILL BE LOCATED OFF THE
 FLOOR.
 ** CAREFUL CONSIDERATION IS TO BE GIVEN ON THE
 LOCATION.
  
 *** PREVIOUS REVIEW NOTE****
 PLEASE SEE THE PLANS ARE MISSING THE LOCATION FOR THE
 REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE 110.26
 AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT THIS
 TIME.
 PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT
 BE ABOVE CEILING.
 PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS
 TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE
 INSTALLED.
 ** PLANS CURRENTLY MENTION THE LOCATION OF THE
 TRANSFORMER IS TO BE DETERMINED BY THE BUILDING
 ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON
 WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT
 WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL
 SUPPORT ETC.
 ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME**
  
  
 9) NOTE: THIS NOTE REMAINS FROM THE PREVIOUS REVIEW.
 PLEASE SEE THE RESPONSE MENTIONS THERE ARE NO OTHER
 LOADS ON THIS MAIN. THIS NOTED EXISTING MAIN IS NOT
 KNOWN BY THIS OFFICE BEING DIRECTLY FROM FPL WITH ITS
 OWN SERVICE AS BEING SHOWN ON THE REVISED RISER. PLEASE
 KNOW THAT A FIELD INSPECTION WILL NEED TO BE PERFORMED
 TO GO OVER THE SERVICES AND EQUIPMENT AT THIS LOCATION.
 THIS OFFICE WILL NEED TO BE IN CONTACT WITH THE
 LANDLORDS OFFICE TO OBTAIN ACCESS TO LOCATION.
 AS REQUESTED FROM PREVIOUS REVIEW:
 **PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS ON
 SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN SERVICE
 WITH NEW LOAD ADDED.
 THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON
 *L*.
 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42
 ETC
 NEC 220 WAS GIVEN IN GENERAL AS THERE ARE TOO MANY
 SPECIFIC CODE SECTIONS WHICH APPLY FROM 220. (TRACK
 LTS, LIGHTING, RECEPTACLES) ETC.
 FBC 106.3.5.1.2, 106.1.2.
 ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER
 POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT
 THE LOAD CALCULATIONS ON MAIN SERVICE.
  
 10) NOTE:THE PREVIOUS REVIEW NOTE #20 REQUESTED
 COORDINATION OF SHUNT TRIP BREAKERS FOR EQUIPMENT. MOST
 OF THIS SEEMS TO BE DONE HOWEVER PLEASE SEE THE
 EQUIPMENT SCHEDULES ON E1.02 AND BE SURE ALL
 COORDINATE.
 PLEASE KNOW MANY OF THESE ITEMS SEEM TO BE MISPRINTS
 FOR ACTUAL LOADS ETC.
 REDLINED SHEETS ON ONE SET. FBC 106.1.2 FOR
 COORDINATION.
 MAY CALL TO GO OVER.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL
 ELECTRICAL UNDER HOODS PER NFPA-96.
 PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS
 HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL.
  
 11) NOTE: THIS NOTE REMAINS FROM PREVIOUS REVIEW NOTE #
 22. THE ENGINEER'S FIRM RESPONSE MENTIONS *NOT
 PROVIDED* PER FIRM.
 THE ARCHITECT'S RESPONSE MENTIONS THIS WAS COMPLETED IN
 TITLE BLOCKS HOWEVER UPON REVIEW OF SEVERAL SHEETS
 INCLUDING CHECKING THE TITLE BLOCKS OF OTHER TRADES,
 THIS WAS NOT COMPLETED AS NEEDED AND AS REQUESTED.
 PLEASE BE SURE THE TITLE BLOCKS REFLECT THE ADDRESS AND
 SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC 61G15-23.002,
 61G1-16.004
  
 12) NOTE: PLEASE CLARIFY HOW IT IS DIMMERS ARE BEING
 SHOWN ON LIGHTING WHICH IS LOCATED IN THE EGRESS
 PATHS.
 PLEASE SEE LS 101 7.8 AND 7.9.
 PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THESE
 PATHS.
 PLEASE SEE FAC 61G15-33.004.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE ATTACHED COPY OF FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE
 AT THIS TIME.
  
 AS STATED ON THE PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-25 07:55:042007-08-25 07:55:04
  
 REVIEW CONTINUED
2007-08-24 21:04:562007-08-24 21:04:56
  
 PLANS ARE IN ELEC FOR REVIEW.
 REVIEW TO CONTINUE ON 8/25, NOTES WILL FOLLOW ONCE
 REVIEW IS COMPLETE.
 PLANS WILL BE GOING INTO A *F* STATUS.