| 2008-10-10 17:06:06 | |
| | ** DENIED REVIEW** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS |
| | COORDINATE. |
| | SOME EXAMPLES: |
| | L-76, L-51, L2-39, 37,ETC |
| | |
| | THERE ARE OTHERS. ALL PANEL SCHEDULE ON RECORD PLANS |
| | NEED TO COORDINATE. SPOKE WITH DESIGNER AND IS AWARE OF |
| | THE ITEMS. WILL NEED TO GET REVISED PANEL SCHEDULES |
| | FROM ELECTRICAL CONTRACTOR FOR WHAT WAS ACTUALLY DONE |
| | ON-SITE SO REVISED PLANS AND PANEL SCHEDULES CAN BE |
| | ACCURATE FOR RECORD PLANS. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |