Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-07 11:02:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE
 FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN
 THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219,
 481.2055.
  
 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO
 HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES
 WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO
 INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION
 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT
 SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER
 CLOSETS. PLEASE CLARIFY.
  
 3. SHT A-9 ACCESSIBLE STALL DETAIL. LAVS SHALL BE A
 MINIMUM 15" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE TO BE CENTERED ON THE 30" OF THE 30"X48" CLEAR
 FLOOR SPACE. SECTION 11-4.19.3.
  
 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE
 SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET
 ROOMS)
  
 __FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE (PER FIG 30E)
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 __FOR URINALS:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 5. ALL STRUCTURAL SHEETS. PROFESSIONAL ENGINEER FIRM'S
 CERTIFICATE OF AUTHORIZATION IS SHOWN AS DELINQUENT ON
 THE STATE DBPR WEBSITE AND THE ADDRESS IN THE TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS INDICATED ON THE
 DBPR WEBSITE. PLEASE UPDATE THE STATUS OF THE C.A.
 NUMBER AND UPDATE EITHER THE DBPR WEBSITE OR THE TITLE
 BLOCK ADDRESS. FAC 61G15-23.002(2) & FS 471.025. (SEE
 ATTACHED SHEETS).
  
 6. ALL E, M, & P SHEETS. THE ADDRESS OF FORMICA &
 ASSOCIATES IN THE TITLE BLOCK DOES NOT REFLECT THE
 ADDRESS INDICATED ON THE STATE DBPR WEBSITE. EITHER
 UPDATE THE WEBSITE OR THE TITLE BLOCKS. FAC
 61G15-23.002(2) & FS 471.025. (SEE ATTACHED SHEET)
  
 7. SHTS P1.01 & P2.01 SAFE WASTE IS NOT APPROVED.
 SECTION 1002.1. (SEE FIXTURE 44.1). ALSO THE FLOOR SINK
 SHALL NOT BE LOCATED IN THE MIDDLE OF THE FLOOR AS IT
 CAN BE A TRIPPING HAZARD BECAUSE FLOOR SINKS ARE TO BE
 USED FOR INDIRECT WASTE ONLY. SECTION 802.3.
  
 8. SHTS P1.01 & P2.01 THE DISHWASHER SHALL CONNECT TO
 THE SANITARY SYSTEM, NOT THE GREASE WASTE SYSTEM PER
 ARTICLE III SECTION 90-124(7)(B).
  
 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN
 COMMENT (A) IS ADDRESSED.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER
 DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A
 FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT
 WASTE.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV
 BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE
 FLOOR FOR SERVICING & TESTING.
  
 12. SHT P2.02 WATER HEATER DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. INDICATE
 METHOD.
  
 13. SHT P2.02 DETAIL NO. 2 SAFE WASTE IS NOT APPROVED.
 SECTION 1002.1.
  
 14. SHT P2.02 DETAIL NO. 3 THE AIR GAP SHALL BE PER
 SECTION 802.2.1.PLEASE INDICATE ON DETAIL.
  
 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS
 K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE
 TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED
 TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY
 DBPR.
  
 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON
 THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED.
 PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS
 SUBMITTED.SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved