| Date |
Text |
| 2007-06-07 11:02:16 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE |
| | FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN |
| | THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219, |
| | 481.2055. |
| | |
| | 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO |
| | HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES |
| | WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT |
| | SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO |
| | INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION |
| | 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT |
| | SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER |
| | CLOSETS. PLEASE CLARIFY. |
| | |
| | 3. SHT A-9 ACCESSIBLE STALL DETAIL. LAVS SHALL BE A |
| | MINIMUM 15" OFF THE WALL TO THE CENTERLINE OF THE |
| | FIXTURE TO BE CENTERED ON THE 30" OF THE 30"X48" CLEAR |
| | FLOOR SPACE. SECTION 11-4.19.3. |
| | |
| | 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE |
| | SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET |
| | ROOMS) |
| | |
| | __FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE (PER FIG 30E) |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | |
| | __FOR URINALS: |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | |
| | __FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | |
| | 5. ALL STRUCTURAL SHEETS. PROFESSIONAL ENGINEER FIRM'S |
| | CERTIFICATE OF AUTHORIZATION IS SHOWN AS DELINQUENT ON |
| | THE STATE DBPR WEBSITE AND THE ADDRESS IN THE TITLE |
| | BLOCK DOES NOT REFLECT THE ADDRESS INDICATED ON THE |
| | DBPR WEBSITE. PLEASE UPDATE THE STATUS OF THE C.A. |
| | NUMBER AND UPDATE EITHER THE DBPR WEBSITE OR THE TITLE |
| | BLOCK ADDRESS. FAC 61G15-23.002(2) & FS 471.025. (SEE |
| | ATTACHED SHEETS). |
| | |
| | 6. ALL E, M, & P SHEETS. THE ADDRESS OF FORMICA & |
| | ASSOCIATES IN THE TITLE BLOCK DOES NOT REFLECT THE |
| | ADDRESS INDICATED ON THE STATE DBPR WEBSITE. EITHER |
| | UPDATE THE WEBSITE OR THE TITLE BLOCKS. FAC |
| | 61G15-23.002(2) & FS 471.025. (SEE ATTACHED SHEET) |
| | |
| | 7. SHTS P1.01 & P2.01 SAFE WASTE IS NOT APPROVED. |
| | SECTION 1002.1. (SEE FIXTURE 44.1). ALSO THE FLOOR SINK |
| | SHALL NOT BE LOCATED IN THE MIDDLE OF THE FLOOR AS IT |
| | CAN BE A TRIPPING HAZARD BECAUSE FLOOR SINKS ARE TO BE |
| | USED FOR INDIRECT WASTE ONLY. SECTION 802.3. |
| | |
| | 8. SHTS P1.01 & P2.01 THE DISHWASHER SHALL CONNECT TO |
| | THE SANITARY SYSTEM, NOT THE GREASE WASTE SYSTEM PER |
| | ARTICLE III SECTION 90-124(7)(B). |
| | |
| | 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO |
| | ISSUING THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN |
| | COMMENT (A) IS ADDRESSED. |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | F. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | G. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER |
| | DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A |
| | FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT |
| | WASTE. |
| | |
| | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV |
| | BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE |
| | FLOOR FOR SERVICING & TESTING. |
| | |
| | 12. SHT P2.02 WATER HEATER DETAIL THERMAL EXPANSION |
| | CONTROL IS REQUIRED PER SECTION 607.3.2. INDICATE |
| | METHOD. |
| | |
| | 13. SHT P2.02 DETAIL NO. 2 SAFE WASTE IS NOT APPROVED. |
| | SECTION 1002.1. |
| | |
| | 14. SHT P2.02 DETAIL NO. 3 THE AIR GAP SHALL BE PER |
| | SECTION 802.2.1.PLEASE INDICATE ON DETAIL. |
| | |
| | 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS |
| | K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE |
| | TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS |
| | REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED |
| | TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY |
| | DBPR. |
| | |
| | 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON |
| | THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED. |
| | PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS |
| | SUBMITTED.SECTION 106.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |