Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop M
Sequence Number 1
Notes
Date Text
2007-05-10 10:10:43*** DENIED ***
 A COMPLETE MECHANICAL REVIEW CAN NOT BE DONE DUE TO A
 LACK OF INFORMATION.
  
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-400.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S SPECIFICATION
 SHEETS FOR A/C SYSTEMS AND INDICATE WHICH UNITS ARE
 BEING INSTALLED.
  
 4) PLEASE SUBMIT INFORMATION ON EXISTING A/C SYSTEMS
 FOR THIS SPACE BEING REMOVED.
  
 5) PLEASE PROVIDE INFORMATION REGARDING THE KITCHEN
 EXHAUST HOODS (ENGINEERING ON HOODS NOT REQUIRED AT
 THIS TIME) NEED SPEC'S. ON HOODS TO KNOW CORRECT
 EXHAUST AIR AND MAKE-UP AIR IF BEING PROVIDE BY HOODS.
 IF NOT PLEASE STATE WERE MAKE-UP AIR IS COMING FROM.
  
 6) PLEASE CHECK AIR BALANCE SCHEDULE ON PAGE M2.01 TO
 BE CERTAIN THE BUILDING NEEDS TO BE AT A +6450 TOTAL
 PRESSURE.
  
 7) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 ALL PAGES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved