| 2007-06-08 11:16:34 | *****DENIED***** |
| | |
| | |
| | 01.THE SITE LOCATION INDICATED ON THE COVER SHEET |
| | SHOWS THIS STRUCTURE AT THE SOUTHEAST CORNER OF |
| | HIBISCUS STREET AND SOUTH ROSEMARY AVENUE.THE |
| | NUMERICAL ADDRESS FOR THIS SITE WOULD BE 700 INSTEAD OF |
| | 701.PLEASE VERIFY |
| | |
| | 02.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK |
| | OF EACH SUBMITTED PLAN SHEET.BE ADVISED THAT THE ZIP |
| | CODE FOR THIS AREA IS 33401 NOT 33305(SEE S SHEETS) |
| | |
| | 03.PLEASE INDICATE IF THIS ASSEMBLY OCCUPANCY IS |
| | EXISTING OR NEW. |
| | |
| | 04.THE REMOVAL AND/OR REPLACEMENT OF BUILDING |
| | MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH |
| | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ROADS, FIRE LANES). |
| | |
| | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 06.SHOW/DISPLAY THE SUITE NUMBER ON THE THE |
| | APPROPIATE EXTERIOR ELEVATION AS TO BE DISTINGUISHABLE |
| | FROM OTHER SUITESOF THIS BUILDING. |
| | |
| | 07.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PERMITTED TO BE PROVIDED WITH PANIC HARDWARE |
| | OR FIRE EXIT HARDWARE. |
| | |
| | 08.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL |
| | BE CLASS A, CLASS B, OR CLASS C.BE SPECIFIC |
| | |
| | 09.WILL THE SCOPE OF WORK HAVE CAUSE FOR FIRE |
| | SPRINKLERS TO BE MODIFIED?IF SO SEPARATE PLANS WILL |
| | BE REQUIRED. |
| | |
| | 10.SHOW THE LOCATION OF THE 2A:10BC FIRE EXTINGUISHER |
| | WHICH SATISFY 75' TRAVEL DISTANCE. |
| | |
| | |
| | TO EXPIDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW / WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | CAPT. MICHAEL WILLIAMS |
| | FIRE PLAN REVIEW |