Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-10 15:45:23** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT CODE ADOPTED AS OF DECEMBER
 8TH, 2006 IS LISTED AS FOLLOWS.
 PLEASE SEE THERE ARE PARTS OF THE PLANS WHICH REFLECT A
 2004 NEC AND A 2002 NEC.
 PLEASE KNOW THAT THERE WAS NOT ANY 2004 NEC. PLEASE
 LIST THE FOLLOWING CODES AT A MINIMUM ON THE ELECTRICAL
 PAGES AND ARCHITECTURAL SHEETS. SOME CODES ARE ALREADY
 REFLECTED ON PLANS, HOWEVER WILL BE AS FOLLOWS FOR
 INFORMATION AS SOME NEED TO BE CHANGED. 2005 NFPA-70
 (NEC).
 2003 NFPA- 101
 2002 NFPA-72
 2004 FBC W/2006 REVISIONS.
 AS STATED, SOME OF THESE ARE DONE ALREADY. PLEASE
 COORDINATE.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS. 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LINE OR
 LOW VOLTAGE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING
 CONTROLS, OVER RIDES, OVER RIDE LOCATION, OVER RIDE
 TIMES, SCHEDULING ETC.
 PLANS ONLY INDICATE STANDARD SWITCHES.
 PLEASE SEE ZONES BASED ON SQ FT.
 PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS
 WHICH CAN NOT BE REVIEWED AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE OCCUPANCY STATED ON PLANS IS
 STATED A *COMMERCIAL*? PLEASE VERIFYAND SEE ANY
 COMMENTS FROM OTHER TRADES FOR THIS.
 FBC 106.1.2
  
 4) NOTE: ** NOT A COMMENT FOR FORMICA AND ASSOC. PLEASE
 SEE THE CERTIFICATE OF AUTHORIZATION NUMBER LISTED FOR
 THE STRUCTURALLY ENGINEERING FIRM IS *DELINQUENT* AS OF
 THIS REVIEW DATE. PLEASE SEE THE ATTACHED PRINT OUT
 FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WHICH SHOWS THIS.
 PLEASE ALSO SEE THE ADDRESS ON TITLE BLOCKS IS NOT THAT
 AS LISTED WITH THE STATE OF FLORIDA.
 ** PLEASE KNOW THE ABOVE IS REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER TRADE.
  
 5) NOTE: PLEASE BE SURE ALL RAISED SEALS FOR THE
 ARCHITECT OF RECORD ARE CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEALS AS REQUIRED PER FAC 61G1-16.
 PLEASE SEE THERE ARE SOME SEALS WHICH ARE NOT
 CLEAR/VISIBLE WITH SOME INFORMATION.
  
 6) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT.
  
 7) NOTE: PLEASE SEE THE CODE SECTION FOR GFI PROTECTION
 FOR ALL RECEPTACLES IN KITCHEN AREAS SHOULD BE 210.8B3.
 THIS SECTION SEEMS TO BE MISPRINTED ON PLANS.
  
 8) NOTE: PLEASE SEE 408.4 WHICH REQUIRES ALL CIRCUITS
 TO BE SPECIFIC TO ALL ROOMS, AREAS, LOCATIONS AND
 CIRCUIT SPECIFIC. PLEASE SEE THE FOLLOWING TEXT FROM
 THE NEC.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS
 FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC
 11.4-28.1, .2 AND .3(4).
 ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE
 SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING
 PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM.
 FBC 106.3.5.1.1
  
 10) NOTE: PLEASE SEE THE CIRCUIT L2-36 WHICH APPEARS TO
 BE IN PLACE FOR THE REQUIRED SIGN CIRCUIT, HOWEVER
 PLEASE SEE 600.5 AS THE LOAD OF 1200VA PER OUTLET , MAY
 NOT FEED ANY OTHER OUTLETS. PLEASE ALSO INDICATE IF
 INDEED THIS IS FOR THE SIGN CIRCUIT(S).
  
 11) NOTE: PLEASE SEE L2-31 WHICH IS SHOWN FEEDING
 HOUSE/COMMON AREA WHICH MAY NOT BE FED FROM THE TENANT
 SPACE. THIS WOULD BE SHOWN FROM A HOUSE PANEL CIRCUIT.
 210.25, 240.24
  
 12) NOTE: PLEASE SEE THE MINIMUM CLEARANCES ARE NOT
 SHOWN FOR THE ELECTRICAL PANELS. IN FACT THERE ARE
 ITEMS/RACKS OR SOME OTHER NON-ELECTRICAL EQUIPMENT
 SHOWN ON PLANS WHICH ARE SHOWN IN THE AREA ABOUT
 ELECTRICAL EQUIPMENT WHICH IS NOT PERMITTED. 110.26
  
 13) NOTE: PLEASE SEE THE PLANS ARE MISSING THE LOCATION
 FOR THE REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE
 110.26 AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT
 THIS TIME.
 PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT
 BE ABOVE CEILING.
 PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS
 TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE
 INSTALLED.
 ** PLANS CURRENTLY MENTION THE LOCATION OF THE
 TRANSFORMER IS TO BE DETERMINED BY THE BUILDING
 ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON
 WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT
 WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL
 SUPPORT ETC.
 ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME**
  
 14) NOTE: PLEASE INDICATE IF THE PANEL *L* SECTION 1
 CONTAINS FEED-THRU LUGS OR IS THERE OVER CURRENT
 PROTECTION IN THIS PANEL WHICH FEEDS PANEL *L* SECTION
 2?
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF THE TRANSFORMER ARE NOT OF SUFFICIENT
 SIZE PER 310.16, 240.21C.
 PLEASE SEE THAT THE TAPPED CONDUCTORS SHALL TERMINATE
 IN OCP WHICH LIMITS THE LOAD ON THE CONDUCTOR WHICH IT
 IS RATED. (MAY NOT GO TO NEXT SIZE UP) (600MCM MIN).
  
 16) NOTE: PLEASE COORDINATE THE RISER AND THE PANEL
 SCHEDULES AS THE PANELS *L* SECTIONS ONE AND TWO ARE
 BOTH BEING SHOWN AS 225AMP PANELS, YET THE RISER SHOWS
 400AMP OVER CURRENT PROTECTION FEEDING THESE PANELS??
 PLEASE SEE THE LOADS ON PANEL *L* AFTER DE-RATING
 EXCEED THAT OF THE RATING OF THESE PANELS.
  
 17) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTORS
 ON RISER DIFFER FROM THOSE INDICATED ON PANELS *L* ONE
 AND TWO.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 18) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL
 INFORMATION ON FIXTURES BEING INSTALLED AND THE NUMBER
 OF FIXTURES. PLEASE SEE THE COMMENT ABOVE WITH RESPECT
 TO THE FBC CHAPTER 13.
 FBC 106.1.2, 106.3.5.1.2
  
 19) NOTE: PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS
 ON SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN
 SERVICE WITH NEW LOAD ADDED.
 THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON
 *L*.
 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42
 ETC
 FBC 106.3.5.1.2, 106.1.2.
 ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER
 POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT
 THE LOAD CALCULATIONS ON MAIN SERVICE.
  
 20) NOTE: PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL
 ELECTRICAL UNDER HOODS PER NFPA-96.
 PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS
 HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL.
  
 21) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OCP FOR THE
 AHU/HEAT. THE MINIMUM OCP IS TO BE SIZED AT 125%.
  
 22) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE
 ADDRESS AND SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC
 61G15-23.002, 61G1-16.004
  
 23) NOTE: PLEASE SEE THE BASED BUILDING PLANS HAD THE
 *DEMO PLANS* REMOVED FOR THE INTERIOR DEMO PERMIT,
 THESE SHEETS NEED TO BE REPLACED IN THIS SET OF PLANS.
  
 **PLEASE KNOW THERE MAY BE NEW COMMENTS IN THE FUTURE
 AS SOME ITEMS CAN NOT BE REVIEWED AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]