Text |
| 2007-05-10 15:45:23 | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE KNOW THAT CODE ADOPTED AS OF DECEMBER |
| | 8TH, 2006 IS LISTED AS FOLLOWS. |
| | PLEASE SEE THERE ARE PARTS OF THE PLANS WHICH REFLECT A |
| | 2004 NEC AND A 2002 NEC. |
| | PLEASE KNOW THAT THERE WAS NOT ANY 2004 NEC. PLEASE |
| | LIST THE FOLLOWING CODES AT A MINIMUM ON THE ELECTRICAL |
| | PAGES AND ARCHITECTURAL SHEETS. SOME CODES ARE ALREADY |
| | REFLECTED ON PLANS, HOWEVER WILL BE AS FOLLOWS FOR |
| | INFORMATION AS SOME NEED TO BE CHANGED. 2005 NFPA-70 |
| | (NEC). |
| | 2003 NFPA- 101 |
| | 2002 NFPA-72 |
| | 2004 FBC W/2006 REVISIONS. |
| | AS STATED, SOME OF THESE ARE DONE ALREADY. PLEASE |
| | COORDINATE. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13. |
| | PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS. 13-415.1.AB.1.1, 13-415.2 |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LINE OR |
| | LOW VOLTAGE. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING |
| | CONTROLS, OVER RIDES, OVER RIDE LOCATION, OVER RIDE |
| | TIMES, SCHEDULING ETC. |
| | PLANS ONLY INDICATE STANDARD SWITCHES. |
| | PLEASE SEE ZONES BASED ON SQ FT. |
| | PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS |
| | WHICH CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE SEE THE OCCUPANCY STATED ON PLANS IS |
| | STATED A *COMMERCIAL*? PLEASE VERIFYAND SEE ANY |
| | COMMENTS FROM OTHER TRADES FOR THIS. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: ** NOT A COMMENT FOR FORMICA AND ASSOC. PLEASE |
| | SEE THE CERTIFICATE OF AUTHORIZATION NUMBER LISTED FOR |
| | THE STRUCTURALLY ENGINEERING FIRM IS *DELINQUENT* AS OF |
| | THIS REVIEW DATE. PLEASE SEE THE ATTACHED PRINT OUT |
| | FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION WHICH SHOWS THIS. |
| | PLEASE ALSO SEE THE ADDRESS ON TITLE BLOCKS IS NOT THAT |
| | AS LISTED WITH THE STATE OF FLORIDA. |
| | ** PLEASE KNOW THE ABOVE IS REQUIRED WHETHER OR NOT |
| | COMMENT IS MADE BY ANY OTHER TRADE. |
| | |
| | 5) NOTE: PLEASE BE SURE ALL RAISED SEALS FOR THE |
| | ARCHITECT OF RECORD ARE CLEAR AND VISIBLE WITH ALL |
| | INFORMATION ON SAID SEALS AS REQUIRED PER FAC 61G1-16. |
| | PLEASE SEE THERE ARE SOME SEALS WHICH ARE NOT |
| | CLEAR/VISIBLE WITH SOME INFORMATION. |
| | |
| | 6) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT. |
| | |
| | 7) NOTE: PLEASE SEE THE CODE SECTION FOR GFI PROTECTION |
| | FOR ALL RECEPTACLES IN KITCHEN AREAS SHOULD BE 210.8B3. |
| | THIS SECTION SEEMS TO BE MISPRINTED ON PLANS. |
| | |
| | 8) NOTE: PLEASE SEE 408.4 WHICH REQUIRES ALL CIRCUITS |
| | TO BE SPECIFIC TO ALL ROOMS, AREAS, LOCATIONS AND |
| | CIRCUIT SPECIFIC. PLEASE SEE THE FOLLOWING TEXT FROM |
| | THE NEC. |
| | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS |
| | FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC |
| | 11.4-28.1, .2 AND .3(4). |
| | ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE |
| | SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING |
| | PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM. |
| | FBC 106.3.5.1.1 |
| | |
| | 10) NOTE: PLEASE SEE THE CIRCUIT L2-36 WHICH APPEARS TO |
| | BE IN PLACE FOR THE REQUIRED SIGN CIRCUIT, HOWEVER |
| | PLEASE SEE 600.5 AS THE LOAD OF 1200VA PER OUTLET , MAY |
| | NOT FEED ANY OTHER OUTLETS. PLEASE ALSO INDICATE IF |
| | INDEED THIS IS FOR THE SIGN CIRCUIT(S). |
| | |
| | 11) NOTE: PLEASE SEE L2-31 WHICH IS SHOWN FEEDING |
| | HOUSE/COMMON AREA WHICH MAY NOT BE FED FROM THE TENANT |
| | SPACE. THIS WOULD BE SHOWN FROM A HOUSE PANEL CIRCUIT. |
| | 210.25, 240.24 |
| | |
| | 12) NOTE: PLEASE SEE THE MINIMUM CLEARANCES ARE NOT |
| | SHOWN FOR THE ELECTRICAL PANELS. IN FACT THERE ARE |
| | ITEMS/RACKS OR SOME OTHER NON-ELECTRICAL EQUIPMENT |
| | SHOWN ON PLANS WHICH ARE SHOWN IN THE AREA ABOUT |
| | ELECTRICAL EQUIPMENT WHICH IS NOT PERMITTED. 110.26 |
| | |
| | 13) NOTE: PLEASE SEE THE PLANS ARE MISSING THE LOCATION |
| | FOR THE REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE |
| | 110.26 AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT |
| | THIS TIME. |
| | PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT |
| | BE ABOVE CEILING. |
| | PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS |
| | TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE |
| | INSTALLED. |
| | ** PLANS CURRENTLY MENTION THE LOCATION OF THE |
| | TRANSFORMER IS TO BE DETERMINED BY THE BUILDING |
| | ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON |
| | WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT |
| | WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL |
| | SUPPORT ETC. |
| | ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME** |
| | |
| | 14) NOTE: PLEASE INDICATE IF THE PANEL *L* SECTION 1 |
| | CONTAINS FEED-THRU LUGS OR IS THERE OVER CURRENT |
| | PROTECTION IN THIS PANEL WHICH FEEDS PANEL *L* SECTION |
| | 2? |
| | FBC 106.1.2 |
| | |
| | 15) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE |
| | SECONDARY SIDE OF THE TRANSFORMER ARE NOT OF SUFFICIENT |
| | SIZE PER 310.16, 240.21C. |
| | PLEASE SEE THAT THE TAPPED CONDUCTORS SHALL TERMINATE |
| | IN OCP WHICH LIMITS THE LOAD ON THE CONDUCTOR WHICH IT |
| | IS RATED. (MAY NOT GO TO NEXT SIZE UP) (600MCM MIN). |
| | |
| | 16) NOTE: PLEASE COORDINATE THE RISER AND THE PANEL |
| | SCHEDULES AS THE PANELS *L* SECTIONS ONE AND TWO ARE |
| | BOTH BEING SHOWN AS 225AMP PANELS, YET THE RISER SHOWS |
| | 400AMP OVER CURRENT PROTECTION FEEDING THESE PANELS?? |
| | PLEASE SEE THE LOADS ON PANEL *L* AFTER DE-RATING |
| | EXCEED THAT OF THE RATING OF THESE PANELS. |
| | |
| | 17) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTORS |
| | ON RISER DIFFER FROM THOSE INDICATED ON PANELS *L* ONE |
| | AND TWO. |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL |
| | INFORMATION ON FIXTURES BEING INSTALLED AND THE NUMBER |
| | OF FIXTURES. PLEASE SEE THE COMMENT ABOVE WITH RESPECT |
| | TO THE FBC CHAPTER 13. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 19) NOTE: PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS |
| | ON SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN |
| | SERVICE WITH NEW LOAD ADDED. |
| | THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON |
| | *L*. |
| | 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42 |
| | ETC |
| | FBC 106.3.5.1.2, 106.1.2. |
| | ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER |
| | POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT |
| | THE LOAD CALCULATIONS ON MAIN SERVICE. |
| | |
| | 20) NOTE: PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL |
| | ELECTRICAL UNDER HOODS PER NFPA-96. |
| | PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS |
| | HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL. |
| | |
| | 21) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OCP FOR THE |
| | AHU/HEAT. THE MINIMUM OCP IS TO BE SIZED AT 125%. |
| | |
| | 22) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE |
| | ADDRESS AND SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC |
| | 61G15-23.002, 61G1-16.004 |
| | |
| | 23) NOTE: PLEASE SEE THE BASED BUILDING PLANS HAD THE |
| | *DEMO PLANS* REMOVED FOR THE INTERIOR DEMO PERMIT, |
| | THESE SHEETS NEED TO BE REPLACED IN THIS SET OF PLANS. |
| | |
| | **PLEASE KNOW THERE MAY BE NEW COMMENTS IN THE FUTURE |
| | AS SOME ITEMS CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |