2007-06-07 15:28:55BUILDING PLAN REVIEW
 PERMIT: 07040835
 ADD: 701 S ROSEMARY # 232
 CONT: L. DAVIS CONSTRUCTION
 TEL: (561)718-8161
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COVERSHEET BLDG DESIGN DATA PLEASE CORRECT NUMBER OF
 STORIES, NOTE THE PARKING GARAGE AND B BLOCK RETAIL ARE
 CONSIDERED ONE BUILDING, NOT TWO.
  
 4) COVERSHEET CODE SUMMARY, 2.1 OCCUPANCY GROUP PLEASE
 CORRECT SEE
 SECTION 303 OF THE FBC- BUILDING.
  
 5) COVERSHEET FAILS TO MENTION IN THE CODE SUMMARY THE
 2006 EXISTING BUILDING CODE AND THE LEVEL OF ALTERATION
 TO BE COMPLETED UNDER THIS PERMIT.
  
 6) SHEET A-1 IN THE GENERAL NOTES# 1 PLANS INDICATE
 THAT CONSTRUCTION SHALL FOLLOW THE ?FLORIDA RESIDENTIAL
 CODE? PLEASE CORRECT.
  
 7) SHEET A-1 GENERAL NOTE# 10 INDICATES COMPLIANCE WITH
 THE STATES
 ENERGY SECTION 5024? PLEASE PROVIDE ADDITIONAL
 INFORMATION 106.1.2*.
  
 8) SHEET A-1 GENERAL NOTE# 15 PLEASE CORRECT THE
 EDITION THESTANDARDS REFERENCEINTHE 2006
 FBC-BUILDING CHAPTER 35.
 UPDATE 8A) ASTM C-83
 8B) ACI 318-83
 8C) ACI 301-84
 8D) ACI 531-79 (REVISE THE STANDARD
 NUMBER AND EDITION)
  
 9) PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING THE
 EGRESS PATTERNS, PROVIDE WIDTH OF THE AISLE AND
 OCCUPANT LOADS THROUGH TO THE EXIT DISCHARGE. PLANS
 ALSO INCLUDE AN ELEVATOR TO THE FIRST FLOOR, PLEASE
 PROVIDE ADDITIONAL INFORMATION ON THE FIRST FLOOR
 LEVEL, IS THE ELEVATOR USED BY ANY OTHER TENANT?
 DOES THE ELEVATOR COMMUNICATE WITH THE EXTERIOR, AND IF
 SO HOW/
 PLEASE INCORPORATE :
 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL
 BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36
 INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES
 OR BETWEEN A WALL AND THE TABLE EDGES.
 1013.4.2 SEATING AT TABLES.
 1013.4.2.2 TABLE AND SEATING ACCESSWAY WIDTH.
 1013.4.2.3 TABLE AND SEATING AISLE ACCESSWAY LENGTH.
  
 10) SHEET A-3 INDICATES THE USE OF A SINGLE STAIR ON TO
 TIERED PLATFORMS SEE SECTION: 1003.5.2 WHERE CHANGE IN
 ELEVATION OF 12 INCHES (305 MM) OR LESS OCCURS IN EXIT
 ACCESS CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS
 COMPLYING WITH SECTION 1010 SHALL BE PROVIDED.
  
 11) 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS
 NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A
 STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT.
  
 12)SHEET S-2 INDICATES THE VARIOUS TYPES OF MATERIALS
 TO BE USED IN CONSTRUCTING THE RAISED PLATFORMS PLEASE
 SEE SECTION:410.4 PLATFORM CONSTRUCTION.PERMANENT
 PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS AS REQUIRED
 FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN WHICH
 THE PERMANENT PLATFORMS IS LOCATED. PERMANENT PLATFORMS
 ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV
 CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30
 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN
 ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN
 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR
 ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR
 PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE
 SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 13) GLAZED OPENING WILL NEED TO COMPLY WITH: 1609.1.4
 PROTECTION OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS,
 EXTERIOR GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE
 LOWER 60 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO
 BE OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE
 REST OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS
 SUCH GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS
 AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203
 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 13A) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) WINDOWS FIXED
 B) SLIDERS
 C) GLAZED SLIDING GLASS DOORS
 D) GLAZED EXTERIOR SWING DOORS
 E) GLAZED SWING EXTERIOR DOORS
 F) OVERHEAD DOORS
 G) MULLIONS-HORIZONTAL FRAMING
 H) PRE-ENGINEERED A/C STANDS
  
 13B) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCTAPPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 13C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 14)2006 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES IN
 TERMS OF PSF.
 NOTE 5 STORY BUILDING POS/ NEG PRESSURE!
  
 15) PLEASE PROVIDE COMPLIANCE WITH :
 15A) 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
 15B) 11-5.4 DINING AREAS.
 IN NEW CONSTRUCTION, ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, LOGGIAS, AND OUTDOOR SEATING
 AREAS, SHALL BE ACCESSIBLE. IN ALTERATIONS,
 ACCESSIBILITY TO RAISED OR SUNKEN DINING AREAS, OR TO
 ALL PARTS OF OUTDOOR SEATING AREAS IS NOT REQUIRED
 PROVIDED THAT THE SAME SERVICES AND DECOR ARE PROVIDED
 IN AN ACCESSIBLE SPACE USABLE BY THE GENERAL PUBLIC AND
 ARE NOT RESTRICTED TO USE BY PEOPLE WITH DISABILITIES.
  
 15C) 11-4.32 FIXED OR BUILT-IN SEATING AND TABLES.
 11-4.32.1 MINIMUM NUMBER.
 FIXED OR BUILT-IN SEATING OR TABLES REQUIRED TO BE
 ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.32.
  
 15D) 11-4.32.2 SEATING.
 IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE
 PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH
 CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE
 THAN 19 INCHES (485 MM) (SEE FIGURE 45).
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION
 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
 WITH THE FOLLOWING REQUIREMENTS:
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
 11-4.32.3 KNEE CLEARANCES.
 IF SEATING FOR PEOPLE IN WHEELCHAIRS IS PROVIDED AT
 TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 INCHES (685
 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485
 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45).
 11-4.32.4 HEIGHT OF TABLES OR COUNTERS.
 THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE
 FROM 28 INCHES TO 34 INCHES (710 MM TO 865 MM) ABOVE
 THE FINISH FLOOR OR GROUND.
  
 16) THE RAISED PLATFORMS HAVE AN OCCUPANT LOAD GREATER
 THAN 50, THAT WILL REQUIRE 2 MEANS OF EGRESS BUT THERE
 IS ONLY ONE ACCESSIBLE RAMP. SEE TABLE 1018.2.
 11-4.3.10 EGRESS.
 ACCESSIBLE ROUTES SERVING ANY ACCESSIBLE SPACE OR
 ELEMENT SHALL ALSO SERVE AS A MEANS OF EGRESS FOR
 EMERGENCIES OR CONNECT TO AN ACCESSIBLE AREA OF RESCUE
 ASSISTANCE.
  
 17) SHEET E2.01 INDICATES AN EXIT LIGHT AT THE BACK OF
 THE PRIVATE MEETING ROOM ,1013.2 EGRESS THROUGH
 INTERVENING SPACES.EGRESS FROM A ROOM OR SPACE SHALL
 NOT PASS THROUGH ADJOINING OR INTERVENING ROOMS OR
 AREAS, EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED; ARE NOT A HIGH-HAZARD
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES. PLEASE CORRECT.
  
 18) PLANS DO NOT PROVIDE ANY INFORMATION FOR DOOR
 HARDWARE OR PANIC HARDWARE, SEE 1008.1.9.
  
 19)SHEETS A7-8 SHOW A CUT SECTION THROUGH THE
 RESTAURANT BUT THERE IS NO INFORMATION AS TO WALL AND
 CEILING FINISHES, PLEASE PROVIDE INFORMATION COMPLYING
 WITH: 803.1 GENERAL.
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH
 MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN
 ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEX.
 CLASS A:
 FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX 0-450.
 CLASS B:
 FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX 0-450.
 CLASS C:
 FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX
 0-450.
 EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN
 ACCORDANCE WITH SECTION 803.2.
 803.2INTERIOR WALL OR CEILING FINISHES OTHER THAN
 TEXTILES.
 INTERIOR WALL OR CEILING FINISHES, OTHER THAN TEXTILES,
 SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE WITH NFPA
 286. FINISHES TESTED IN ACCORDANCE WITH NFPA 286 SHALL
 COMPLY WITH SECTION 803.2.1.
  
 20) THE PLANS ALSO LACK FIRE SPRINKLER PLANS THIS IS A
 FIRE SPRINKLED BUILDING PLEASE PROVIDE THE FIRE
 SPRINKLER PLAN. NOTE: 2604.1.2(4) BE PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. WHERE THE COOLER OR FREEZER
 IS WITHIN A BUILDING, BOTH THE COOLER OR FREEZER AND
 THAT PART OF THE BUILDING IN WHICH IT IS LOCATED SHALL
 BE SPRINKLED.
  
 21) IT ALSO APPEARS THAT THE ENERGY CALCULATIONS SEE
 CHAPTER 13 OF THE FBC BUILDING.
  
 22) SEE ELECTRICAL COMMENTS ABOUT ARCHITECTURAL AND
 ENGINEERING DEFICIENCIES, SIGNATURES, DELINQUENCIES,
 CERTIFICATE OF AUTHORIZATION, ETC.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 TAVERNA OPA 1ST REVIEW.DOC