2007-08-27 08:59:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)SEE SHEET 6 OF THE PRODUCT APPROVAL.OPENING 4
 HAS A SPAN OF OVER 12'.SEE HIGHLIGHTED PRODUCT
 APPROVAL.A DESIGN PRESSURE OF -57 (CANNOT USE -45 AS
 YOU ARE DESIGNING TO -48), C2 CONNECTION, REQUIRES 6"
 SPACING (YOU'VE SPECIFIED 12").YOU HAVE CIRCLED C1,
 45PSF ON THE PRODUCT APPROVAL BUT THIS DOES NOT
 CORRELATE WITH YOUR JOB.CIRCLING ITEMS ON THE PRODUCT
 APPROVAL IS HELPFUL FOR PLAN REVIEW AND INSPECTIONS BUT
 IS OPTIONAL AND MUST CORRELATE WITH THE JOB.
  