| Notes |
| Date |
Text |
| 2007-08-27 08:59:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)SEE SHEET 6 OF THE PRODUCT APPROVAL.OPENING 4 | | | HAS A SPAN OF OVER 12'.SEE HIGHLIGHTED PRODUCT | | | APPROVAL.A DESIGN PRESSURE OF -57 (CANNOT USE -45 AS | | | YOU ARE DESIGNING TO -48), C2 CONNECTION, REQUIRES 6" | | | SPACING (YOU'VE SPECIFIED 12").YOU HAVE CIRCLED C1, | | | 45PSF ON THE PRODUCT APPROVAL BUT THIS DOES NOT | | | CORRELATE WITH YOUR JOB.CIRCLING ITEMS ON THE PRODUCT | | | APPROVAL IS HELPFUL FOR PLAN REVIEW AND INSPECTIONS BUT | | | IS OPTIONAL AND MUST CORRELATE WITH THE JOB. | | | |
|