2007-05-07 17:04:21** UNSAT 2ND REVIEW**
  
 ***** IMPORTANT *****
 ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THAT THERE ARE SEVERAL NEW COMMENTS
 BASED ON THE RESPONSES AND THE REVISED PLANS. MANY
 ITEMS WERE SUBSTANTIALLY REVISED INCLUDING THE SCOPE OF
 WORK PER FLOOR UNDER SEPARATE PERMITS.
  
 ** THIS IS A REVIEW FOR SECOND FLOOR UNDER A NEW PERMIT
 NUMBER HOWEVER THE REVIEW WAS PREVIOUSLY CONDUCTED
 UNDER #07011148 WHEN BOTH FLOORS WERE SUBMITTED UNDER
 ONE PERMIT.
 PLEASE SEE MANY OF THE COMMENTS ON THE ABOVE REFERENCED
 NUMBER MAY AFFECT THESE PLANS AND INFORMATION.
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 MANY COMMENTS ARE FROM THE FIRST REVIEW.
  
 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 PLEASE SEE THE ARCHITECTURAL PLANS STILL INDICATE THE
 PREVIOUS CODES. PLEASE LIST THE FOLLOWING AS REQUESTED
 ON PREVIOUS REVIEW. PLEASE SEE ONLY THE CORRECTED CODES
 WERE ADDED TO THE ELECTRICAL SHEETS AND NOT TO A
 SHEETS.
 PLEASE SEE THE CODES SHALL BE STATED ON THE PLANS. ALL
 APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE UNDER THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE
 STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS
 STATE LATEST EDITION.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON
 PLANS.
 SAME NOTE AS PREVIOUS REVIEW. ONLY THE ELECTRICAL
 SHEETS WERE CORRECTED TO INDICATE THE SUITE/UNIT
 NUMBER. PLEASE SEE THIS COMMENT IS FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
 ** PLEASE KNOW THAT ANY SHEETS WHICH ARE NOT REQUIRED
 TO BE CORRECTED FOR ANY TRADE/CODE RELATED COMMENT MAY
 HAVE THE SUITE/UNIT NUMBER WRITTEN/PRINTED OR STAMPED
 ON TITLE BLOCKS.
 FBC 106.1.2,
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004.
 THIS COMMENT WAS MADE ON THE PREVIOUS REVIEW AND THE
 RESPONSE MENTIONS THAT PERHAPS THIS WAS MISSED AS IT IS
 LISTED ON THE UPPER RIGHT HAND CORNER OF THE
 PLANS/TITLE BLOCKS.
 PLEASE SEE THE TITLE BLOCKS INDICATE THE PRINTED *FIRM*
 CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS OK AND
 REQUIRED BUT DOES NOT INDICATE THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT AS REQUIRED PER SECTION STATED
 PREVIOUSLY. NONE OF THE SHEETS CONTAIN THIS "PRINTED
 LICENSE NUMBER" OF THE ARCHITECT.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
 PLEASE REVISE AND ADDRESS ACCORDINGLY. ** ONE SHEETS
 WHICH DO NOT NEED TO BE REVISED BY OTHER TRADES FOR
 CODE COMPLIANCE, THIS MAY BE PRINTED/STAMPED ON
 SHEETS.
  
 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND
 PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2. NO
 CALCULATIONS COULD BE LOCATED.
 ONLY THE LIGHTING PERFORMANCE FOR LIGHTING WAS LOCATED
 ON PLANS. PLEASE VERIFY THE NUMBER OF FIXTURES, THE
 WATTAGES, AND SQ FT FOR LPD.
 THE TOTAL WATTAGE WHICH WAS DERIVED USING THE NUMBER OF
 FIXTURES ON PLANS AND THE WATTAGE FOR EACH AS LISTED ON
 FIXTURE LEGEND SEEMS TO BE SLIGHTLY DIFFERENT THAN THAT
 SHOWN ON LIGHTING PLANS.
  
 5) NOTE:PLEASE SEE THIS NOTE AS LISTED IS THE SAME AS
 PREVIOUS REVIEW. IN FACT ONE OF THE SAME ELECTRICAL
 SHEETS SUBMITTED ON PREVIOUS PLANS WAS NOW SUBMITTED AS
 E3.3 WHICH IS MISSING MUCH OF THE INFORMATION WHICH WAS
 SHOWN ON PREVIOUS PLANS ON SHEET E3?
 PLEASE SEE NO SCHEDULING, OVER RIDE TIMES, SYSTEM,
 CONTROL PANEL LOCATION, CIRCUITS, ZONES, ETC IS SHOWN.
 ** PLEASE SEE THAT THE LIGHTING PANEL WHICH IS ON THE
 3RD FLOOR MAY NOT BE USED FOR SECOND FLOOR.
 PLEASE SEE RESPONSE MENTIONS 1HR OVER RIDES, HOWEVER ON
 AN OCCUPANCY SENSOR TYPE DEVICES, THE MAXIMUM OVER RIDE
 TIME IS 30MINS.
 PLEASE REVISE PLANS, PROVIDE COMPLETE DETAILS FOR
 CHAPTER 13 CODE COMPLIANCE.
 ** PLEASE SEE THERE ARE NOTES ON LIGHTING SHEETS WHICH
 REFLECT TO A NOTE #4, THIS NOTE #4 MENTIONS TO SEE
 DETAILS ON SHEET E-4,HOWEVER NO SHEET E4 IS IN SETS
 PR SUBMITTED?
 DEVICES ON LEGEND NEED TO COORDINATE WITH DETAIL FOR
 ALL DEVICES, TIMES, TYPES ETC. THE LEGEND DOES NOT
 INDICATE ANY SENTRY DEVICE AS NOTED ON PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE SCHEDULING FOR THE TIMES IN USE
 FOR THE LIGHTING CONTROL SYSTEM. PLEASE SEE THE SECTION
 OF THE CODE OF CHAPTER 13 QUOTED AS 413 SHOULD BE 415.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS
 MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND
 CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE
 MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S).
 (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS
 ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES
 FOR COMPLIANCE WITH CHAPTER 13.
  
  
 6) NOTE:THIS SAME NOTE WILL REMAIN AS THE SCOPE OF
 WORK APPLIED FOR UNDER 3RD AND 2ND FLOOR IS NOT CLEAR
 ON HOW THE PANELS ETC FOR THE IT ROOM WILL BE DONE. THE
 NOTE IS THE SAME OF THAT WHICH IS ON 07011148IT ROOM
 REQUIREMENTS SEEMS TO HAVE BEEN ADDRESSED, HOWEVER
 QUESTION HAS NOW RISEN OVER SCOPE OF WORK AND WHICH
 PERMIT THIS WORK WILL BE UNDER. PLEASE SEE THE
 ELECTRICAL RISER NOW SHOWS, NOTES AND INDICATES THIS
 SCOPE OF WORK IS NOT INCLUDED FOR THIRD FLOOR AND IS
 UNDER 2ND FLOOR SCOPE?? PLEASE SEE THE PERMIT
 APPLICATION AND PLANS FOR THE SECOND FLOOR ALSO STATE
 THE SAME THING?
 PLEASE BE SURE TO COORDINATE ALL SCOPES OF WORK, UNDER
 WHICH PERMIT AND REVISE PLANS AS NEEDED. HOW WILL THE
 3RD FLOOR WHICH IS UNDER A SEPARATE PERMIT FROM THE 2ND
 FLOOR OBTAIN A FINAL/CERTIFICATE OF COMPLETE ION OR
 OCCUPANCY WHEN THE SCOPE FOR THAT FLOOR HAS NOT BEEN
 DONE YET?
 PLEASE SUBMIT THE SPECS/PLANS AND DOCUMENTS UNDER THE
 PERMIT BEING APPLIED FOR.
 FBC 106.1.2, 106.3.5.1.2ADMIN SECTION.
  
 7) NOTE: ** THIS COMMENT IS NOT FOR MEP FIRM: PLEASE
 SEE FIRE REVIEW COMMENTS AS THE FP SHEETS IN NEW SETS
 ARE OF NEW DESIGNER AND NOTE THAT SUBMITTED FROM
 PREVIOUS REVIEWED PLANS.
 PLEASE SEE THE FOLLOWING ITEMS ARE REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY THE FIRE REVIEWER.
 PLEASE SEE NEW REVISED SHEET FP-2 IS THE ONLY SHEET IN
 SETS.
 ** PLEASE SEE THE SEAL WHICH IS NOW BEING USED ON THE
 REVISED FP-2 SHEETS IS NO LONGER VALID WITH THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS. PLEASE SEE RULING FAC
 61G15-23.001 WHICH CHANGED IN FEB *04* REQUIRING ALL
 SEALS FOR ENGINEERS TO CHANGE AND USE THE WORDING OF
 *LICENSE* IN SAID SEAL AND COULD NOT LONGER USE THE
 WORDING OF *CERTIFICATE*. AN EXTENSION WAS GRANTED BY
 THE BOARD TO THE DATE OF 12/31/05 HOWEVER ALL SEALING
 OF DOCUMENTS AFTER THAT DATE MUST BE DONE USING NEW
 SEAL.
 PLEASE OBTAIN CORRECTED SEAL FROM THE STATE/BOARD.
 **PLEASE ALSO SEE MISSING TITLE BLOCK INFORMATION
 REQUIRED FOR THE ENGINEER OF RECORD FOR THE FP SHEETS.
 PLEASE KNOW IF THE ENGINEER OF RECORD IS EMPLOYED BY
 THE FIRE PROTECTION COMPANY ( PHILLIPS FIRE SPRINKLERS
 INC) WHICH IS OFFERING ENGINEERING SERVICES, THEN SAID
 COMPANY SHALL OBTAIN AN ENGINEERING BUSINESS LICENSE
 NUMBER AS REQUIRED UNDER FLORIDA STATUTES 471.023 AND
 SHALL INCLUDE THIS INFORMATION ON TITLE BLOCKS AS
 REQUIRED PER FAC 61G15-23.002
 PLEASE KNOW THAT IF THE ENGINEER IS PRACTICING AS AN
 INDIVIDUAL AND NOT EMPLOYED BY THE SAID COMPANY THEN
 THE SHEETS ARE REQUIRED TO CONTAIN INFORMATION FOR THE
 INDIVIDUAL TITLE BLOCK AS REQUIRED UNDER THE SAME
 SECTION OF THE FLORIDA ADMINISTRATIVE CODE.
 ** THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND THE BOARDS LEGAL COUNSEL. IF
 THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THE
 BOARD AS NOTED.
  
 8) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED IN WHICH THERE ARE SEVERAL
 NEW COMMENTS AS WELL AS SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE IN NEED OF ADDRESSING.
 SOME OF THE BELOW IS TAKEN FROM THE NOTES UNDER
 07011148. PLEASE COORDINATE BOTH PERMITS, PLANS AND
 SCOPE OF WORK.
 PLEASE SEE THE RISER NOW INDICATES 277/480V SERVICE
 BEING INSTALLED FROM A NEW 1MA AND THE RISER STILL
 INDICATES THE BUS-DUCT RISER AS 277/480V? PLEASE SEE
 THE RISER FOR DISCONNECT WHICH IS NOTED #14 WHICH
 INDICATES THIS DISCONNECT AS 120/208V?
 PLEASE SEE RISER, WHICH SHOWS THE DISCONNECT FOR THE
 ASSUMED 277/480 OR 120/208 ON THE FORTH FLOOR WHICH IS
 FOR THE THIRD FLOOR AND THE DISCONNECT WHICH IS ON THE
 THIRD FLOOR WHICH FEEDS THE SECOND FLOOR? AS THE
 VOLTAGES CONFLICT, IT APPEARS THERE ARE TWO COMPLETELY
 SEPARATE 277/480VOLT SERVICES BEING FED FROM TWO
 SEPARATE MAINS??
 PLEASE SEE THE 2ND FLOOR WHICH CONTAINS LIGHTING
 CONTROLS WHICH IS BEING FED FROM THE THIRD FLOOR
 ELECTRICAL SERVICE WHICH IS NOT PERMITTED.( IN THE
 EVENT POWER IS NEEDED TO BE SHUT DOWN FOR THIS FLOOR,
 THESE SWITCHES WOULD REMAIN ENERGIZED).
  
 PLEASE SEE DISCONNECT #22 INDICATES A NEUTRAL ON THE
 LINE SIDE OF THE TRANSFORMER? IF THIS IS SUPPOSED TO BE
 A SEPARATELY DERIVED SYSTEM, THEN A NEUTRAL CONDUCTOR
 WOULD NOT BE INSTALLED TO THE TRANSFORMER FROM THIS
 DISCONNECT NOTED AS #22. SEE NOTE #15 FOR CONDUCTORS.
 THE RISER IS NOT CLEAR FOR VOLTAGES, SERVICES, CROSSING
 OVER OF SYSTEMS, WHAT IS OR IS NOT SEPARATELY DERIVED
 ETC. THESE ITEMS CAN NOT BE ASSUMED.
 PLEASE CLARIFY PANELS 3LA AND 3LB AS BOTH ARE SHOWN AS
 100AMP MCB, HOWEVER THIS IS BEING NOTED AND SHOWN ON
 RISER THAT EACH PANEL CONTAINS THIS AS PART OF THE
 EQUIPMENT, YET PANEL 3LB ALSO INDICATES THE PANEL
 CONTAINING A BACK FED BREAKER? IF THIS IS THE CASE,
 PLEASE NOTE REJECTION CLIP REQUIRED. 408.36F PLEASE SEE
 NEC 2005.
 FBC 106.3.5.1.2, 106.1.2.
  
 9) NOTE: PLEASE SEE THE NEW 1MA WHICH IS NOW SHOWN AS A
 500AMP MCB/MAIN CIRCUIT BREAKER PANEL WHICH CONTAINS AS
 BUS RATED AT 225AMPS.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE.
 PLEASE SEE THE LOAD CALCULATIONS FOR THIS SAME PANEL
 INDICATES THE LOAD AT 297AMPS, AND THE BUS/SERVICE
 BEING RATED FOR 225AMPS.
 (ALSO LABELED AS 3MA)??
 THIS RISER IS STILL UNCLEAR FOR VOLTAGES AND
 INSTALLATION OF THE EQUIPMENT.
 PLEASE SEE THE 2005 NEC. PANELS AND EQUIPMENT MUST BE
 RATED FOR THE LOADS, ETC.
 FBC 106.3.5.1.2, 106.1.2
 ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY
 CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE
 OR ARE MISSING AT THIS TIME.
  
 10) NOTE:NOTE TO REMAIN AS RISER IS THE SAME OF THAT
 ON 07011148PLEASE INDICATE ANY GROUNDING ATTACHMENTS
 AND SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66,
 AND 250.50
 THIS WAS NOTED ON PREVIOUS REVIEW. INDICATE THE
 ATTACHMENT LOCATIONS.
  
 11) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON
 ALL EXISTING WITH NEW LOADS BEING ADDED.
 THIS IS NOT ONLY FOR THE PANELS SHOWN, BUT FOR ALL
 EQUIPMENT WHICH LOADS, PANELS ETC ARE BEING ADDED.
 PLEASE SEE NOTE # 9 ABOVE WITH RESPECT TO 1MA. PLEASE
 SEE 220.10, 220.12, 220.14, 220.42, ETC, CONTINUOUS
 LOADS AT 125% PER 215.3, 230.42 ETC.
  
 12) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY NOTED AT THIS TIME.
 ** ONE SET OF EACH OF THE SETS OF PLANS SUBMITTED WILL
 BE RETAINED BY THIS OFFICE.
  
 ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT
 YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]