Plan Review Notes
Plan Review Notes For Permit 07040785
Permit Number 07040785
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-14 19:49:11 
  
  
 PROJECT: 250 SOUTH AUSTRALIAN, SUITE 200
  
 CONTRACTOR: ITASCA
 BUILDING CODE: FEBC AND FBC 2004 WITH 2006 REVISIONS
  
 1ST REVIEW
 STATUS: DENIED
  
 COMMENTS:
  
 1) FBC 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW. PLEASE CONTACT ALEX ORTEGA OF
 THE DEP FOR DEMOLITION CLEARANCE AT 561.355.3023,
 EXT.48.
  
 2) FEBC 1302.1REMODELING AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING REMODELING, ALTERATIONS,
 REPAIRS OR ADDITIONS TO ANY BUILDING OR STRUCTURE.
 EXCEPTIONS:
 1. WHEN SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING
 REMODELED, ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE
 PROVISIONS SHALL BE MADE.
 2. WHEN THE EXISTING BUILDING IS NOT OCCUPIED.
  
 3)FEBC1309.1WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND
 SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATE
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 4)FEBC 1310.2MAINTENANCE OF EXITS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS AND ADDITIONS TO ANY BUILDING. EXCEPTION:
 APPROVED TEMPORARY MEANS OF EGRESS SYSTEMS AND
 FACILITIES.
  
 5) PLEASE INDICATE BUILDING CONSTRUCTION TYPE ( TYPE 1A
 OR TYPE 1B), OCCUPANCY LOADS AS PER FBC 1004.1 AND
 LEVEL OF ALTERATION AS PER FEBC 305.1 WITHIN THE
 PROJECT INFORMATION LOCATED ON SHEET A-1. ALSO REVISE
 THE BUILDING CODES TO INDICATE FBC AND FEBC WITH 2006
 REVISIONS WITHIN THE SAME.
  
 6) FIRE RESISTANT CONSTRUCTION REQUIREMENTS:
  
 PLEASE PROVIDE DETAILS OF THROUGH PENETRATION
 FIRESTOP SYSTEMS APPLICABLE TO THIS PROJECT AS PER THE
 FOLLOWING:
  
 712.4 HORIZONTAL ASSEMBLIES.
 PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE
 CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 707. PENETRATIONS
 PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL
 COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4.
 EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR
 UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO
 HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1,
 2, 5, 7, 8 OR 9 IN SECTION 707.2.
  
 712.4.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 712.4.1.1 OR 712.4.1.2.
 EXCEPTIONS:
 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS,
 PIPES, TUBES, VENTS, CONCRETE, OR MASONRY THROUGH A
 SINGLE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY WHERE THE
 ANNULAR SPACE IS PROTECTED WITH MATERIALS THAT PREVENT
 THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE
 COTTON WASTE WHEN SUBJECTED TO ASTM E 119
 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AT THE LOCATION OF THE PENETRATION FOR THE
 TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE RATING OF
 THE CONSTRUCTION PENETRATED. PENETRATING ITEMS WITH A
 MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER SHALL NOT BE
 LIMITED TO THE PENETRATION OF A SINGLE
 FIRE-RESISTANCE-RATED FLOOR ASSEMBLY PROVIDED THAT THE
 AREA OF THE PENETRATION DOES NOT EXCEED 144 SQUARE
 INCHES (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF
 FLOOR AREA.
 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL,
 FERROUS OR COPPER CONDUITS, PIPES, TUBES AND VENTS WITH
 A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER PROVIDED
 CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL
 THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO
 MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING
 ITEMS WITH A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER
 SHALL NOT BE LIMITED TO THE PENETRATION OF A SINGLE
 CONCRETE FLOOR PROVIDED THAT THE AREA OF THE
 PENETRATION DOES NOT EXCEED 144 SQUARE INCHES (0.0929
 M2).
 3. ELECTRICAL OUTLET BOXES OF ANY MATERIAL ARE
 PERMITTED PROVIDED THAT SUCH BOXES ARE TESTED FOR USE
 IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN
 ACCORDANCE WITH THE TESTED ASSEMBLY.
  
 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING
 AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
 EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED
 WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING.
  
 715.3.5 LABELED PROTECTIVE ASSEMBLIES.
 FIRE DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED
 AGENCY. THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL
 BE PERMANENTLY AFFIXED TO THE DOOR OR FRAME.
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II
 CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE
 PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE.
 COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN CONCEALED
 CEILING SPACES WHERE INSTALLED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, MECHANICAL AND THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 7) SYMBOL LEGEND, NEW PARTITION TYPES REFERS TO SHEET
 A-10; SHOULD REFER TO SHEET A-6. ALSO REFERENCES TO TO
 DOOR SCHEDULE IS SHEET A-10A: SHOULD BE SHEET A-6.
 PLEASE REVISE.
  
 8) PLAN INDICATES TWO WALL TYPES AT GRIDLINE 6 AT THE
 COPY STORAGE ROOM. PLEASE PROVIDE CLARIFICATION.
  
 9) PROVIDE MECHANICAL ATTACHMENT DETAILS FOR METAL WALL
 FRAMING AT THE TOP AND BOTTOM RUNNERS AND THE DIAGONAL
 METAL SUPPORTS TO CEILING SLAB INTERFACE AS SHOWN ON
 SHETT A-6, WALL TYPES 1-3. PLEASE CLARIFY THE USE OF #8
 TEK SCREWS INTO CONCRETE AS REFLECT ED ON THE WALL TYPE
 DETAILS 1 AND 2 ON SHEET A-6.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 FAX: 561.805.6676
 E-MAIL: [email protected]
  