| 2007-06-14 19:49:11 | |
| | |
| | |
| | PROJECT: 250 SOUTH AUSTRALIAN, SUITE 200 |
| | |
| | CONTRACTOR: ITASCA |
| | BUILDING CODE: FEBC AND FBC 2004 WITH 2006 REVISIONS |
| | |
| | 1ST REVIEW |
| | STATUS: DENIED |
| | |
| | COMMENTS: |
| | |
| | 1) FBC 105.9 ASBESTOS. |
| | THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT |
| | FOR THE DEMOLITION OR RENOVATION OF AN EXISTING |
| | STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT |
| | WHICH INDICATES THE OWNER?S OR OPERATOR?S |
| | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION |
| | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT |
| | OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO |
| | REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH |
| | STATE AND FEDERAL LAW. PLEASE CONTACT ALEX ORTEGA OF |
| | THE DEP FOR DEMOLITION CLEARANCE AT 561.355.3023, |
| | EXT.48. |
| | |
| | 2) FEBC 1302.1REMODELING AND ADDITIONS. |
| | REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE |
| | PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE |
| | MAINTAINED AT ALL TIMES DURING REMODELING, ALTERATIONS, |
| | REPAIRS OR ADDITIONS TO ANY BUILDING OR STRUCTURE. |
| | EXCEPTIONS: |
| | 1. WHEN SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING |
| | REMODELED, ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE |
| | PROVISIONS SHALL BE MADE. |
| | 2. WHEN THE EXISTING BUILDING IS NOT OCCUPIED. |
| | |
| | 3)FEBC1309.1WHERE REQUIRED. |
| | ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| | DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE |
| | APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| | SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND |
| | SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS: |
| | 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATE |
| | 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 4)FEBC 1310.2MAINTENANCE OF EXITS. |
| | REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL |
| | TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR |
| | ALTERATIONS AND ADDITIONS TO ANY BUILDING. EXCEPTION: |
| | APPROVED TEMPORARY MEANS OF EGRESS SYSTEMS AND |
| | FACILITIES. |
| | |
| | 5) PLEASE INDICATE BUILDING CONSTRUCTION TYPE ( TYPE 1A |
| | OR TYPE 1B), OCCUPANCY LOADS AS PER FBC 1004.1 AND |
| | LEVEL OF ALTERATION AS PER FEBC 305.1 WITHIN THE |
| | PROJECT INFORMATION LOCATED ON SHEET A-1. ALSO REVISE |
| | THE BUILDING CODES TO INDICATE FBC AND FEBC WITH 2006 |
| | REVISIONS WITHIN THE SAME. |
| | |
| | 6) FIRE RESISTANT CONSTRUCTION REQUIREMENTS: |
| | |
| | PLEASE PROVIDE DETAILS OF THROUGH PENETRATION |
| | FIRESTOP SYSTEMS APPLICABLE TO THIS PROJECT AS PER THE |
| | FOLLOWING: |
| | |
| | 712.4 HORIZONTAL ASSEMBLIES. |
| | PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE |
| | CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 707. PENETRATIONS |
| | PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL |
| | COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4. |
| | EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR |
| | UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO |
| | HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1, |
| | 2, 5, 7, 8 OR 9 IN SECTION 707.2. |
| | |
| | 712.4.1 THROUGH PENETRATIONS. |
| | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED |
| | HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION |
| | 712.4.1.1 OR 712.4.1.2. |
| | EXCEPTIONS: |
| | 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS, |
| | PIPES, TUBES, VENTS, CONCRETE, OR MASONRY THROUGH A |
| | SINGLE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY WHERE THE |
| | ANNULAR SPACE IS PROTECTED WITH MATERIALS THAT PREVENT |
| | THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE |
| | COTTON WASTE WHEN SUBJECTED TO ASTM E 119 |
| | TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AT THE LOCATION OF THE PENETRATION FOR THE |
| | TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE RATING OF |
| | THE CONSTRUCTION PENETRATED. PENETRATING ITEMS WITH A |
| | MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER SHALL NOT BE |
| | LIMITED TO THE PENETRATION OF A SINGLE |
| | FIRE-RESISTANCE-RATED FLOOR ASSEMBLY PROVIDED THAT THE |
| | AREA OF THE PENETRATION DOES NOT EXCEED 144 SQUARE |
| | INCHES (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF |
| | FLOOR AREA. |
| | 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL, |
| | FERROUS OR COPPER CONDUITS, PIPES, TUBES AND VENTS WITH |
| | A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER PROVIDED |
| | CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL |
| | THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO |
| | MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING |
| | ITEMS WITH A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER |
| | SHALL NOT BE LIMITED TO THE PENETRATION OF A SINGLE |
| | CONCRETE FLOOR PROVIDED THAT THE AREA OF THE |
| | PENETRATION DOES NOT EXCEED 144 SQUARE INCHES (0.0929 |
| | M2). |
| | 3. ELECTRICAL OUTLET BOXES OF ANY MATERIAL ARE |
| | PERMITTED PROVIDED THAT SUCH BOXES ARE TESTED FOR USE |
| | IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN |
| | ACCORDANCE WITH THE TESTED ASSEMBLY. |
| | |
| | 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND |
| | TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A |
| | MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH |
| | (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING |
| | AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS |
| | THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. |
| | EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED |
| | WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING. |
| | |
| | 715.3.5 LABELED PROTECTIVE ASSEMBLIES. |
| | FIRE DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED |
| | AGENCY. THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL |
| | BE PERMANENTLY AFFIXED TO THE DOOR OR FRAME. |
| | |
| | 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II |
| | CONSTRUCTION. |
| | COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES |
| | OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS: |
| | 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION |
| | 603. |
| | 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF |
| | THE FLORIDA BUILDING CODE, MECHANICAL. |
| | 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE |
| | PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED |
| | IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE. |
| | COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN CONCEALED |
| | CEILING SPACES WHERE INSTALLED IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, MECHANICAL AND THE FLORIDA |
| | BUILDING CODE, PLUMBING. |
| | |
| | 7) SYMBOL LEGEND, NEW PARTITION TYPES REFERS TO SHEET |
| | A-10; SHOULD REFER TO SHEET A-6. ALSO REFERENCES TO TO |
| | DOOR SCHEDULE IS SHEET A-10A: SHOULD BE SHEET A-6. |
| | PLEASE REVISE. |
| | |
| | 8) PLAN INDICATES TWO WALL TYPES AT GRIDLINE 6 AT THE |
| | COPY STORAGE ROOM. PLEASE PROVIDE CLARIFICATION. |
| | |
| | 9) PROVIDE MECHANICAL ATTACHMENT DETAILS FOR METAL WALL |
| | FRAMING AT THE TOP AND BOTTOM RUNNERS AND THE DIAGONAL |
| | METAL SUPPORTS TO CEILING SLAB INTERFACE AS SHOWN ON |
| | SHETT A-6, WALL TYPES 1-3. PLEASE CLARIFY THE USE OF #8 |
| | TEK SCREWS INTO CONCRETE AS REFLECT ED ON THE WALL TYPE |
| | DETAILS 1 AND 2 ON SHEET A-6. |
| | |
| | PLAN REVIEW: KEN CONRAD |