2007-04-30 11:27:56 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, 106.3.5.4 FBC.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. INDICATE SIZE AND SYSTEM ON THE PLAN.
  
 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  