| Date |
Text |
| 2007-07-27 13:11:00 | *** UNSAT3RD REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | REMAIN. |
| | |
| | 1) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS |
| | REVIEW, PLEASE COMPLY WITH FBC CHAPTER 13 FOR LIGHTING |
| | CONTROLS.ALL NEW BEING INSTALLED NEEDS TO COMPLY. |
| | THIS TENANT SPACE IS NOT DEFINED AS A BUILDING AND THIS |
| | SPACE IS LOCATED IN A BUILDING GREATER THAN 5K SQ FT. |
| | THE RESPONSE MENTIONS THIS IS 2400 + SQ FT AND DOES NOT |
| | NEED LIGHTING CONTROLS. THIS IS NOT THE CASE.PLEASE |
| | SEE THE DEFINITIONS OF A BUILDING IN BOTH CHAPTER 13 |
| | AND FBC DEFINITIONS. TENANT OCCUPANCIES LOCATED IN A |
| | BUILDING OVER 5K SQ FT EVEN IF 200 SQ FT FOR EXAMPLE |
| | FOR THE INDIVIDUAL TENANT SPACE STILL REQUIRES LIGHTING |
| | CONTROLS FOR AUTOMATED SHUTTING OFF/TURNING OFF OF |
| | LIGHTS. |
| | THIS HAS BEEN CONFIRMED WITH THE STATE ON MANY |
| | OCCASIONS AND THE STATE TAC COMMITTEE WHEN THE CODE |
| | CHANGE WAS MADE ALMOST TWO EARS AGO. |
| | PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE CONFIRMED |
| | AND DO NOT CORRELATE FOR LIGHTING CONTROLS AND PLANS. |
| | 13-415.1.ABC.1.1, .1.2, 13-415.1.A, 13-415.2 |
| | 13-101. |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED THE |
| | ADDRESS OF THE UNIT OR SUITE NUMBER TO BE ADDED TO THE |
| | PLANS, HOWEVER THE RESPONSE MENTIONS THIS ENTIRE |
| | BUILDING IS ONE TENANT. |
| | PLEASE SEE THE ENERGY CALCULATIONS WHICH WERE SUBMITTED |
| | BY THE ARCHITECT STATES A UNIT/SUITE OF #118? |
| | PLEASE CLARIFY HOW THIS IS POSSIBLE. |
| | |
| | 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE |
| | NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE A FEE HAS NOW BEEN ASSESSED TO THE DESIGN |
| | PROFESSIONAL AS REQUIRED PER THE ABOVE FLORIDA STATUTE. |
| | THIS FEE OF $1800.00 IS DUE BEFORE PLANS CAN BE |
| | RESUBMITTED. |
| | ONE COPY OF ELECTRICAL PLANS ALONG WITH ONE COPY OF |
| | ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE. |
| | TO DATE NO ONE HAS CONTACTED THIS REVIEWER TO GO OVER |
| | ANY OF THE COMMENTS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |