| Date |
Text |
| 2007-06-18 11:16:08 | |
| | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS ARE STILL |
| | IN NEED OF ADDRESSING. |
| | ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS |
| | SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW |
| | COMMENTS ON RE-SUBMITTAL OF PLANS. |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE |
| | FBC HAS NOT BEEN ADDRESSED. THE REQUIRED LIGHTING |
| | CONTROLS AS PREVIOUSLY NOTED HAVE NOT BEEN PLACED ON |
| | PLANS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE |
| | NOT CORRECT. THE FIXTURES DO NOT CORRELATE, THE TYPES, |
| | THE CONTROLS ETC. |
| | PLEASE SEE ALL OF CHAPTER AND THE SECTIONS AS |
| | PREVIOUSLY GIVEN. |
| | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, |
| | 13-415.2, 13-415.2.ABC.1.2 |
| | |
| | 2) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WHICH |
| | STATED THE MISSING REQUIRED INFORMATION ON TITLE BLOCKS |
| | PER 61G1-16.004. (STILL MISSING THE PRINTED LICENSE |
| | NUMBER OF THE ARCHITECT). |
| | |
| | 3) NOTE: PLEASE SEE THE CIRCUITING MAY NOT ONLY USE |
| | LIGHTING, RECEPTACLES ETC. THESE NEED TO BE SPECIFIC TO |
| | ROOMS, AREAS, OR OTHER TYPE OF DESIGNATION. MAY USE A |
| | NUMERICAL DESIGNATION TO OFFICES OR OTHER LOCATIONS. |
| | PLEASE SEE 408.4 |
| | |
| | 4) NOTE: PLEASE SEE ADDRESS ONLY INDICATES THE |
| | LOCATION. THIS BUILDING CONTAINS MORE THAN ONE |
| | SUITE/UNIT NUMBER? IF SO PLEASE SEE THE PERMIT |
| | APPLICATION NEEDS TO STATE THE SUITE/UNIT ALONG WITH |
| | THE PLANS. |
| | |
| | 5) NOTE: PLEASE SEE MISPRINT FOR NEW PANEL L1C, WHICH |
| | IS SHOWN AS LC1 ON PANEL AND L1C ON RISER. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE FS 553.802B WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A NOTICE |
| | GIVEN AT THIS TIME. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |