Plan Review Notes
Plan Review Notes For Permit 07040749
Permit Number 07040749
Review Stop P
Sequence Number 2
Notes
Date Text
2007-08-15 12:06:46****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 405.3.1 A WATER CLOSET
 OR LAVATORY SHALL NOT BE SET CLOSER THAN 15 INCHES FROM
 ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR OTHER
 OBSTRUCTION, OR CLOSER THAN 30 INCHES CENTER-TO-CENTER
 BETWEEN THE WATER CLOSETS OR ADJACENT FIXTURES. THERE
 SHALL BE AT LEAST A 21 INCH CLEARANCE IN FRONT OF THE
 WATER CLOSET OR LAVATORY TO ANY WALL, FIXTURE OR DOOR.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER