| 2007-08-15 12:06:46 | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING, SECTION 405.3.1 A WATER CLOSET | | | OR LAVATORY SHALL NOT BE SET CLOSER THAN 15 INCHES FROM | | | ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR OTHER | | | OBSTRUCTION, OR CLOSER THAN 30 INCHES CENTER-TO-CENTER | | | BETWEEN THE WATER CLOSETS OR ADJACENT FIXTURES. THERE | | | SHALL BE AT LEAST A 21 INCH CLEARANCE IN FRONT OF THE | | | WATER CLOSET OR LAVATORY TO ANY WALL, FIXTURE OR DOOR. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] | | | | | | |
|