2007-08-15 17:53:30 
  
 DENIED 2ND REVIEW
  
 THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED FROM
 THE FIRST REVIEW:
  
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025
 FOR MOREINFORMATION.
  
 *******STAMP MUST BE PRESENT ON THE DRAWINGS EVEN IF NO
 FEE IS REQUIRED*******
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. AMOUNT DUE $1.20
  
 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL
  
 ******NOTE ENERGY CALC'S WERE NOT SIGNED BY THE
 OWNER/AGENT, ALSO THE INFORMATION PROVIDED ON THE
 ENERGY CALC'S DOES NOT MATCH DRAWINGS, THEWALLS ARE
 SHOWN AS CONCRETE WITH R4.2 INSULATION BUT ARE WOOD
 FRAME CONSTRUCTION AND NO INSULATION VALUE HAS BEEN
 GIVEN ON THE DRAWINGS AND THE ROOF IS SHOWN AS R19 AND
 THE CALC'S STATE R30. PLEASE MAKE CORRECTIONS TO
 DRAWINGS AND ENERGY CALC'S******
  
 4)THE FOLLOWING CORRECTIONS ARE REQUIRED ON THE
 PRODUCT APPROVALS
 A)2 DIFFERENT ROOFING SYSTEMS ARE INCLUDED IN THE GAF
 MODIFIED ROOFING PRODUCT APPROVAL ONE FOR COLD APPLIED
 AND ONE FOR HEAT WELD, PLEASE CHOOSE THE METHOD THAT
 WILL BE USED.
 ******BOTH ROOFING SYSTEMS ARE STILL INCLUDED IN THE
 PRODUCT APPROVAL*******
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 *******SHALL BE REVIEWED AND APPRVED FOR USE BY
 DESIGNER*******
  
 7)PROVIDE THE FOLLOWING INFORMATION ON THE DRAWINGS:
 E)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION
 ON THE WALL SECTIONS PER R403.1.4 FBC RES.
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716