2007-05-07 15:54:41DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: EVERY TRAP AND
 TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING
 METHODS SPECIFIED IN THIS CHAPTER.
 NOTE: A VENT IS REQUIRED FOR THE BATHROOM GROUP IN THE
 PROPOSED BATHROOM ADDITION. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 2. PER FBC-2004 PLUMBING, SECTION 708.3.5 BUILDING
 DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 NOTE: PLEASE INDICATE A TWO-WAY CLEANOUT FOR THE
 PROPOSED BATHROOM ADDITION ON THE RESUBMITTAL.
  
 3. PER FBC-2004 PLUMBING, SECTION 416 PLEASE CORRECTLY
 IDENTIFY THE FIXTURE IN THE PROPOSED BATHROOM ADDITION
 AS A LAVATORY (LAV) ON THE RESUBMITTAL.
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: PLEASE CLEARLY SIZE THE LAV WASTE,VENT AND TRAP
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721