| 2007-05-07 15:54:41 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PER FBC-2004 PLUMBING, SECTION |
| | 901.2.1 VENTING REQUIRED: EVERY TRAP AND |
| | TRAPPED FIXTURE SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING |
| | METHODS SPECIFIED IN THIS CHAPTER. |
| | NOTE: A VENT IS REQUIRED FOR THE BATHROOM GROUP IN THE |
| | PROPOSED BATHROOM ADDITION. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | 2. PER FBC-2004 PLUMBING, SECTION 708.3.5 BUILDING |
| | DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A TWO-WAY |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | NOTE: PLEASE INDICATE A TWO-WAY CLEANOUT FOR THE |
| | PROPOSED BATHROOM ADDITION ON THE RESUBMITTAL. |
| | |
| | 3. PER FBC-2004 PLUMBING, SECTION 416 PLEASE CORRECTLY |
| | IDENTIFY THE FIXTURE IN THE PROPOSED BATHROOM ADDITION |
| | AS A LAVATORY (LAV) ON THE RESUBMITTAL. |
| | |
| | 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | NOTE: PLEASE CLEARLY SIZE THE LAV WASTE,VENT AND TRAP |
| | ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |