Plan Review Notes
Plan Review Notes For Permit 07040738
Permit Number 07040738
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-10 19:15:26 
  
 DENIED
  
 1)MAKE CORRECTIONS TO DRAWINGS TO MATCH ENERGY
 CALC'S, IF TAKING A CREDIT FOR R11 FOR RAISED SLAB
 PLEASE SHOW THE INSULATION ON THE DRAWINGS. WALL
 DETAILS SHOW NO FINISH FOR 2ND FLOOR CEILING/SLAB.
  
 2)STAIR DETAILS DO NOT PROVIDE CORRECT INFORMATION,
 RISE 7" AND RUN 11" CANNOT WORK. PLEASE SEE THAT FIN.
 FL. ELEVATION SHOULD MATCH ALL OTHER DETAILS (SHOWS
 10'-0" NOT 10'-4" AS OTHER DETAILS SHOW, DIVIDED
 EQUALLY THEIR ARE 18 RISERS AT 6 7/8" +/-AND 17
 TREADS AT 11 OR 11 1/4" SO TOTAL RUN WOULD BE 15'-11
 1/4" IF 11 1/4" TREADS WERE USED.)
  
 3)METAL ROOFING SHINGLES OR PANELS CANNOT BE APPLIED
 TO SLOPES LESS THAN 3/12 PER R905.4.2 AND R905.10.2 FBC
 RES
  
 4)THE FOLLOWING PRODUCT APPROVALS REQUIRE
 CORRECTIONS:
  
 A) THE MIAMI-DADE REPORT FOR CASTCRETE LINTELS IS FOR
 4,6 & 12 INCH WIDE BLOCK THE CORRECT REPORT FOR 8" IS
 REQUIRED 03-0605.05, ALSO BE SURE TO SUBMIT THE ENTIRE
 REPORT AS ONLY ONE PAGE OF THE INCORRECT REPORT WAS
 SUBMITTED.
  
 B) THE JELD-WEN DOOR PRODUCT APPROVAL HAS BEEN REVISED
 FOR THE 2004 CODE CYCLE FL# 539-R2 WITH NEW MIAMI- DADE
 REPORT # 07-0314.05
  
 C) THE PRODUCT APPROVAL FOR THE TRACO TR 9100 WINDOWS
 ARE ONLY RATED AS SMALL MISSILE IMPACT, ALL OPENINGS
 WITHIN 30 FEET OF GRADE ARE REQUIRED TO BE LARGE
 MISSILE IMPACT RATED.
  
 5)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING
 THE NOTICE IS VOID PLEASE HAVE NOC RERECORDED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716