| 2007-08-10 19:15:26 | |
| | |
| | DENIED |
| | |
| | 1)MAKE CORRECTIONS TO DRAWINGS TO MATCH ENERGY |
| | CALC'S, IF TAKING A CREDIT FOR R11 FOR RAISED SLAB |
| | PLEASE SHOW THE INSULATION ON THE DRAWINGS. WALL |
| | DETAILS SHOW NO FINISH FOR 2ND FLOOR CEILING/SLAB. |
| | |
| | 2)STAIR DETAILS DO NOT PROVIDE CORRECT INFORMATION, |
| | RISE 7" AND RUN 11" CANNOT WORK. PLEASE SEE THAT FIN. |
| | FL. ELEVATION SHOULD MATCH ALL OTHER DETAILS (SHOWS |
| | 10'-0" NOT 10'-4" AS OTHER DETAILS SHOW, DIVIDED |
| | EQUALLY THEIR ARE 18 RISERS AT 6 7/8" +/-AND 17 |
| | TREADS AT 11 OR 11 1/4" SO TOTAL RUN WOULD BE 15'-11 |
| | 1/4" IF 11 1/4" TREADS WERE USED.) |
| | |
| | 3)METAL ROOFING SHINGLES OR PANELS CANNOT BE APPLIED |
| | TO SLOPES LESS THAN 3/12 PER R905.4.2 AND R905.10.2 FBC |
| | RES |
| | |
| | 4)THE FOLLOWING PRODUCT APPROVALS REQUIRE |
| | CORRECTIONS: |
| | |
| | A) THE MIAMI-DADE REPORT FOR CASTCRETE LINTELS IS FOR |
| | 4,6 & 12 INCH WIDE BLOCK THE CORRECT REPORT FOR 8" IS |
| | REQUIRED 03-0605.05, ALSO BE SURE TO SUBMIT THE ENTIRE |
| | REPORT AS ONLY ONE PAGE OF THE INCORRECT REPORT WAS |
| | SUBMITTED. |
| | |
| | B) THE JELD-WEN DOOR PRODUCT APPROVAL HAS BEEN REVISED |
| | FOR THE 2004 CODE CYCLE FL# 539-R2 WITH NEW MIAMI- DADE |
| | REPORT # 07-0314.05 |
| | |
| | C) THE PRODUCT APPROVAL FOR THE TRACO TR 9100 WINDOWS |
| | ARE ONLY RATED AS SMALL MISSILE IMPACT, ALL OPENINGS |
| | WITHIN 30 FEET OF GRADE ARE REQUIRED TO BE LARGE |
| | MISSILE IMPACT RATED. |
| | |
| | 5)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN |
| | THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING |
| | THE NOTICE IS VOID PLEASE HAVE NOC RERECORDED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |