| Plan Review Notes For Permit 07040738 |
| Permit Number |
07040738 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-15 12:55:27 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) MECHANICAL PLANS NEED TO BE SIGNED BY DESIGNER. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | 3) NEED TO SHOW GRILL SIZE AND CFM'S AT SUPPLY AIR | | | GRILLS THAT WERE YELLOW HIGH LIGHTED ON MECHANICAL | | | PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|