| Plan Review Notes For Permit 07040735 |
| Permit Number |
07040735 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-26 10:56:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | FROM PREVIOUS LIST: | | | | | | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED | | | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER | | | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE | | | LIMITATIONS. | | | | | | THE APPROVED ASSEMBLIES WILL BE FOUND IN PAGES 9 | | | THROUGH 31. | | | | | | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES. | | | | | | FASTENING WAS ACCEPTABLE BUT STATES "AS REQUIRED BY FBC | | | 2005".THIS FASTENING EXCEEDS REQUIREMENTS OF RAS117 | | | AND THE CORRECT BUILDING CODE IS FBC2004.YOU MAY | | | REMOVE OR REVISE THIS STATEMENT; NOT REQUIRED FOR | | | PERMITTING. |
|