| 2007-09-05 19:13:08 | ** DENIED 2ND REVIEW ** |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR, ALL MATERIALS, ALL |
| | PERMANENTLY INSTALLED EQUIPMENT, ARCHITECTURAL AND |
| | DESIGN FEES ETC. |
| | PLEASE SEE THE ELECTRICAL SCOPE OF WORK AS ORIGINALLY |
| | SHOWN HAS SUBSTANTIALLY INCREASED ALONE. |
| | PLEASE MAKE ADJUSTMENTS OR A VALUE WILL BE APPLIED |
| | USING GUIDES ADOPTED UNDER THE FBC AND ADOPTED |
| | REFERENCE BOOKS. |
| | |
| | 2) NOTE: PLEASE SEE THE NEW ENERGY CALCULATIONS |
| | SUBMITTED ARE NOT COMPLETE. PLEASE SEE THE LIGHTING |
| | DENSITIES ARE SHOWN BLANK. |
| | PLEASE SEE THE SIGNATURE NOT THE TYPED NAME OF PERSON |
| | PREPARING DOCUMENT IS REQUIRED. 13-103.1.1.1 |
| | PLEASE SEE THE ENGINEER OF RECORD AS LISTED IS NOT |
| | SIGN, DATED AND SEALED. FBC 13-103.1.1.1, FAC |
| | 61G15-23.002, FS 471.025 |
| | PLEASE SEE THE OWNER AGENT IS BLANK. |
| | FBC 13-415.1.C |
| | |
| | ** ELECTRICAL PLANS ARE IN GOOD SHAPE AS THE ENGINEER |
| | DID A GOOD JOB ADDRESSING THE ELECTRICAL COMMENTS. WELL |
| | DONE. |
| | |
| | ** PLEASE ADDRESS COMMENTS #1 AND #2. THE ELECTRICAL |
| | SHEETS WILL BE STAMPED AT THIS TIME. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |