| 2007-06-06 12:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. |
| | OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD SERVICE |
| | LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE CITY |
| | FOR REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH REVIEW |
| | STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" |
| | ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR |
| | REVIEW. SECTION 102.2.1. |
| | |
| | 2. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| | ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. |
| | PLEASE CONTACE RODNEY COMPO, (561) 822-2272 OR CALVIN |
| | WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561) |
| | 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected] |
| | AND [email protected]. MUNICIPAL CODE ARTICLE III |
| | SECTION 90-124. |
| | |
| | 3. THE FLOOR DRAINS IN THE KITCHEN ANDBAKERY AREAS AS |
| | WELL AS THE MOP SINK SHALL DISCHARGE INTO THE GREASE |
| | WASTE SYSTEM, NOT THE SANITARY.SECTION 90-124(7) |
| | |
| | 4. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, |
| | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE |
| | THROUGH AN INDIRCET WASTE PIPE BY MEANS OF AN AIR GAP. |
| | SECTION 802.1. SEE THE THREE COMPARTMENT SINK AND THE |
| | TWO COMPARTMENT SINK. A FLOOR SINK SHALL BE REQUIRED. |
| | SECTION 802.3. |
| | |
| | 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| | VALVES, AND WATER HAMMER ARRESTORS REQUIRED FOR QUICK |
| | CLOSING VALVES. WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO |
| | THE RESTAURANT. SECTION 608.13.2. |
| | |
| | 7. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION |
| | 607.3.1. PLEASE INDICATE METHOD. |
| | |
| | 8. SHT A-1 SCHEMATIC RISER DIAGRAM, NEW HAND SINKS ARE |
| | NOT VENTED AS SHOWN. PLEASE SHOW COMPLIANCE WITH |
| | SECTION 901.2.1.--THE EXISING LINE BEING DEMO'D |
| | SHALL COMPLY WITH SECTION 704.5. NO DEAD ENDS. |
| | |
| | 9. SHT A-1 CODE REVIEW NOTES CONCERNING GREASE |
| | INTERCEPTORS. THE WEST PALM BEACH MUNICIPAL CODE, |
| | ARTICLE III SECTION 90-124(7)(A THRU G) SHALL GOVERN |
| | THE INSTALLATION, TYPE, MANITENANCE ETC OF THE GREASE |
| | INTERCEPTOR. SEE ATTACHED SHEET FOR REQUIREMENTS. |
| | |
| | 10. SHT A-2 PLUMBING GENERAL NOTES #4. SUBMIT A |
| | CONDENSATE RISER DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, |
| | VENTS AND INDICATE THE TERMINATION POINT. SECTION |
| | 106.3.5.1.3(13).--NOTE #6PVC PIPEIS NOT ALLOWED |
| | FOR DISTRIBUTION PIPE PER TABLE 605.4.--NOTE #8 AIR |
| | CHAMBERS ARE NOT APPROVED. PDI-WH 201 AND SECTION |
| | 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR ALL |
| | QUICK CLOSING VALVES. |
| | |
| | 11. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES. |
| | A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |