| Date |
Text |
| 2007-04-27 16:35:49 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE VALUE FOR SCOPE OF WORK SHALL |
| | INCLUDE ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY |
| | OF THESE ARE OWNER SUPPLIED. |
| | PLEASE SEE THE VALUE IS LOW AT THIS TIME AND WILL NEED |
| | TO BE ADJUSTED. |
| | PLEASE THAT A VALUE MAY BE ASSESSED BY USING GUIDES AS |
| | ADOPTED BY THE FBC. 108.3 |
| | |
| | 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | ** PLEASE SEE THE INCORRECT NEC IS NOTED. |
| | |
| | 3) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING |
| | CONTROLS BEING INSTALLED. PLEASE PROVIDE DETAIL ON |
| | OCCUPANCY DEVICE AND PLEASE SEE SOME AREAS LIKE THE |
| | KITCHEN IN WHICH THE SINGLE WALL WHICH AT LOCATION |
| | SHOWN MAY NOT PROVIDE THE NEEDED COVERAGE. |
| | PLEASE DETAIL THE CONNECTION IN BAR AREA AND ALL OTHER |
| | AREAS. |
| | PLEASE SEE THE EXISTING BATH ROOMS WILL REQUIRE |
| | DEVICES. |
| | PLEASE SEE NOT ALL AREAS INDICATE LIGHTING POWER |
| | DENSITIES. |
| | PLEASE SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE. |
| | PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETED WITH ALL |
| | FIXTURE TYPES, WATTAGES ETC. (THESE MAY BE REVISED AT A |
| | LATER DATE IF CHANGED). |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3, |
| | 13-415.1.AB.1.1, 13-415.2 ETC. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL RECEPTACLES SERVING |
| | KITCHEN AREAS AS GFI. MOST ARE DONE AND ONLY ONE IS |
| | MISSING IN THIS DESIGNATED AREA. |
| | PLEASE ALSO SEE ONLY MISPRINT FOR THE CODE SECTION AS |
| | NOTED IN GENERAL ELECTRICAL NOTES. |
| | PLEASE SEE 210.8B3. |
| | |
| | 5) NOTE: PLEASE SEE ELECTRICAL SHEETS IN TWO OF THE |
| | SETS ARE INSERTED UPSIDE DOWN, BACKWARDS AND THERE ARE |
| | MORE SHEETS THAN SHOULD BE IN SETS. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND INSERT NEW |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE BE SURE TO CHECK THE SHEETS. |
| | PLEASE ONLY SUBMIT ONE COPY OF THE OLD/VOIDED REMOVED |
| | SHEETS. |
| | ** PLEASE BE CAREFUL NOT TO DISCARD ANY SHEETS STAMP BY |
| | THE DIVISION OF HOTELS ETC). |
| | |
| | 6) NOTE: PLEASE INDICATE IF THE PANELS CONTAIN |
| | FEED-THRU LUGS OR IS THERE OVER CURRENT PROTECTION FROM |
| | ONE TO THE OTHER? |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE LOADS AS SHOWN ON PANEL *A* IS |
| | LOWER THAN THE LOAD ON LOAD CALCULATIONS.THIS IS NOT |
| | POSSIBLE WHEN PANEL USUALLY SHOW THE CONNECTED LOAD OR |
| | THE SAME DE-RATED LOAD AS FIGURED IN THE LOAD |
| | CALCULATIONS. |
| | PLEASE COORDINATE THESE. |
| | FBC 106.1.2 |
| | NEC 220 |
| | |
| | 8) NOTE: PLEASE SEE 422.13 AS THIS WAS REVISED IN THE |
| | 2005 CODE TO REQUIRE ALL ELECTRIC WATER HEATER LOADS TO |
| | BE SHOWN AND DONE AT 125%. |
| | |
| | 9) NOTE: PLEASE INDICATE THE EXISTING LIGHTING FIXTURES |
| | IN THE BATHROOMS. |
| | |
| | 10) NOTE: PLEASE SEE THE TITLE COVER SHEET INDICATES |
| | PLANS SUBMITTED BY MARTEK, YET NO MECHANICAL PLANS WERE |
| | SUBMITTED FOR REVIEW? PLEASE VERIFY. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE OR REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |