| 2008-12-02 10:53:22 | |
| | |
| | REVISION DENIED |
| | |
| | THE PERMIT SET OF PLANS WERE ISSUED UNDER PROVISO'S TO |
| | BE CORRECTED ON THE FIRST REVISION. THE FOLLOWING HAVE |
| | NOT BEEN CORRECTED ON THE ELECTRICAL PLAN SHEET E2. |
| | |
| | 1} BATH CIRCUITS PER 210.11(C)(3)*** BATHROOM BRANCH |
| | CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS.***CIRCUIT #10 LABELED "FLORIDA ROOM |
| | RECEPTACLES" SERVE THE BATH RECEPTACLES IN VIOLATION OF |
| | THIS ARTICLE. INDICATE BATH CIRCUIT ON THE PANEL |
| | SCHEDULE PER 408.4. |
| | |
| | 2} .R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** THE |
| | NOTE (#9) REQUIRING THAT ARTICLE WAS REMOVED FROM THE |
| | PLAN. ALSO SEE THAT EACH SMOKE ALARM (MISMARKED |
| | "DETECTORS") IS ON A DIFFERENT CIRCUIT THEREFORE NOT |
| | INTERCONNECTED PER MANUFACTURE SPECIFICATION. |
| | |
| | NEW COMMENT: |
| | |
| | 3} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED |
| | TO REVISE HIS/HER PLAN. PER 481.229(1)(B) JOSEPH |
| | DRAGONMUST MAKE ANY CHANGES TO THIS SHEET. |
| | |
| | NOTE: THE PANEL LOCATION SUBMITTED IS CODE COMPLIANT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |