| Date |
Text |
| 2008-02-29 16:13:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET D3, SANITARY ISOMETRIC RISER DOES NOT REFLECT |
| | THE FLOOR PLAN OF SHEET F1 AND IS NOT CODE COMPLIANT. |
| | PROVIDE THE FLAT PLAN SANITARY UNDERGROUND PLUMBING |
| | LAYOUT ON SHEET F1 AND REFLECT THAT ON THE RESUBMITTED |
| | SANITARY ISOMETRIC. PER FBC PLUMBING SECTION 701.1 |
| | SCOPE. |
| | |
| | 2. SHEET D3 SANITARY ISOMETRIC RISER DIAGRAM THE BAR |
| | SINK IS MISSING FROM THE RISER DIAGRAM. PER FBC |
| | PLUMBING SECTION 701.1 SCOPE. |
| | |
| | 3. THE WASHING MACHINE CAN NOT DRAIN INTO THE WET |
| | VENTED BATHROOM GROUP. THE WASHING MACHINE MUST DRAIN |
| | DOWN STREAM OF THE BATHROOM GROUP. PER FBC PLUMBING |
| | SECTION 909.1 WET VENT PERMITTED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |