| 2008-02-27 07:59:37 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 |
| | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| | THE FOLLOWING: |
| | |
| | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| | FAC. |
| | |
| | 2} THE LOAD CALCULATIONS SUBMITTED DO NOT MEET THE |
| | REQUIREMENTS OF THE NEC. PROVIDE LOAD CALCULATIONS PER |
| | ARTICLE 220 PART III, STANDARD OR PART IV OPTIONAL, |
| | INDICATE METHOD USED. SEE 220.1. |
| | |
| | 3}} PROVIDE PANEL SCHEDULES PER 408.4. INCLUDE OCP |
| | AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005 |
| | NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT |
| | DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM |
| | ALL OTHERS." |
| | |
| | 4} THE RISER DIAGRAM INDICATES A METER/MAIN TYPE OF |
| | SERVICE EQUIPMENT. INDICATE THE SIZE OF THE MAIN |
| | BREAKER (DETERMINED BY THE LOAD CALCULATION) SO THE |
| | CORRECT SIZE OF THE GROUNDING ELECTRODE MAY BE |
| | DETERMINED PER 250.66. |
| | |
| | 5} AN EQUIPMENT GROUND PER 250.122 MUST BE RAN WITH THE |
| | FEEDER CONDUCTOR TO THE PROPOSED PANEL. VERIFY THAT |
| | NONE WERE RAN WITH THE EXISTING FEEDER RUNS AS THEY ARE |
| | REQUIRED PER THAT ARTICLE. |
| | |
| | 6} THEDISCONNECTING MEANS FOR THE WATER HEATER DOES |
| | NOT COMPLY WITH THE CLEARANCE REQUIREMENTS OF 110.26. |
| | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND |
| | 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| | |
| | 7}COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14, |
| | MUST ALSO COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. A |
| | RECEPTACLE(S) ARE SHOWN AT THE CONDENSER LOCATIONS. |
| | |
| | 8} THE SQUARE FOOTAGE OF THE ADDITION IS LISTED AS |
| | 1,375 ON SHEET E2 AND F1, THE SQUARE FOOTAGE ON THE |
| | APPLICATION IS LISTED AS 750. CORRELATE SAME. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |