| 2007-05-11 09:58:03 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE VERIFY THE CONFIGURATION OF THE METER AND |
| | DISCONNECTS SHOWN. THEY WOULD APPEAR TO BE A |
| | METER/MAIN, RATHER THAN SEPARATE DISCONNECTS AS NOTED. |
| | CORRECT THE RISER. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL |
| | SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230 |
| | CAN BE REVIEWED. THE "PROPOSED 100 AMP" PANEL MAY BE |
| | REQUIREED TO BE GROUNDED PER 250.32 AND HAVE A MAIN PER |
| | 225.31, DEPENDING ON LOCATION. |
| | |
| | 4 } 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN |
| | ELECTRODE ENCASED BY AT LEAST 50 MM (2 IN.) OF |
| | CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF A |
| | CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT |
| | CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 6.0 M |
| | (20 FT) OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER |
| | ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS |
| | OR RODS OF NOT LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, |
| | OR CONSISTING OF AT LEAST 6.0 M (20 FT) OF BARE COPPER |
| | CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS |
| | SHALL BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL |
| | STEEL TIE WIRES OR OTHER EFFECTIVE MEANS. THIS IS |
| | AVAILABLE GIVEN A FOOTER IS BEING POURED. PLEASE ADD TO |
| | RISER. |
| | |
| | 5} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |