| 2007-08-23 11:13:05 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) IT APPEARS MOST DUCT WORK AND GRILLS ARE BEING | | | REPLACED OR RELOCATED. PLEASE SUBMIT MECHANICAL PLANS | | | SHOWING ALL DUCT WORK WITH SIZES AND LIST AS NEW OR | | | EXISTING. PLEASE DO NOT SHOW OLD LOCATION OF GRILLS | | | BEING REMOVED. | | | | | | 2) WHEN SHOWING DUCT SIZES DO NOT SHOW AS 5? OR 7? | | | BECAUSE I DO NOT KNOW THE DUCT SIZES AND CAN NOT ANSWER | | | THE QUESTION. | | | | | | 3) THE MECHANICAL PLAN HAS TO MUCH FURNITURE AND TILE | | | FLOOR DETAIL ON IT AND IS DIFFICULT TO READ. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. | | | PER 2004 FBC 106.1.1. | | | | | | 4) SHOW ALL SUPPLY AIR GRILLS WITH SIZES AND LIST AS | | | NEW OR EXISTING, ALSO SHOW LOCATION OF RETURN AIR | | | GRILLS. | | | | | | 5) PLAN SHOWS A HEAT PUMP UNIT IS TO BE REPLACED, | | | PLEASE PROVIDE AN EQUIPMENT LISTING. | | | | | | 6) PROVIDE OUT-SIDE AIR CALCULATIONS AND OUT-SIDE AIR | | | IF REQUIRES, SEE MECH. 401.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] | | | | | | | | | . |
|