2007-08-23 11:13:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) IT APPEARS MOST DUCT WORK AND GRILLS ARE BEING
 REPLACED OR RELOCATED. PLEASE SUBMIT MECHANICAL PLANS
 SHOWING ALL DUCT WORK WITH SIZES AND LIST AS NEW OR
 EXISTING. PLEASE DO NOT SHOW OLD LOCATION OF GRILLS
 BEING REMOVED.
  
 2) WHEN SHOWING DUCT SIZES DO NOT SHOW AS 5? OR 7?
 BECAUSE I DO NOT KNOW THE DUCT SIZES AND CAN NOT ANSWER
 THE QUESTION.
  
 3) THE MECHANICAL PLAN HAS TO MUCH FURNITURE AND TILE
 FLOOR DETAIL ON IT AND IS DIFFICULT TO READ.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY.
 PER 2004 FBC 106.1.1.
  
 4) SHOW ALL SUPPLY AIR GRILLS WITH SIZES AND LIST AS
 NEW OR EXISTING, ALSO SHOW LOCATION OF RETURN AIR
 GRILLS.
  
 5) PLAN SHOWS A HEAT PUMP UNIT IS TO BE REPLACED,
 PLEASE PROVIDE AN EQUIPMENT LISTING.
  
 6) PROVIDE OUT-SIDE AIR CALCULATIONS AND OUT-SIDE AIR
 IF REQUIRES, SEE MECH. 401.2.
  
 MECHANICAL PLAN REVIEW BY;