| Plan Review Notes For Permit 07040703 |
| Permit Number |
07040703 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-22 12:13:25 | *** PROVISO *** | | | 1) DOOR D15 TO EXISTING MECHANICAL ROOM WILL COMPLY | | | WITH 2004 FBC/M 602.2.1 MATERIALS EXPOSED WITHIN | | | PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME | | | SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED | | | INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE | | | WITH ASTM E 84. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|