| Date |
Text |
| 2007-05-03 12:53:12 | *****DENIED***** | | | | | | | | | 1.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER ACCESS TO OR EGRESS FROM THE FLOOR OR THE | | | BUILDING. | | | | | | 4.NEW INTERIOR WALL AND CEILING FINISH MATERIALS | | | SHALL BE CLASS A, CLASS B, OR CLASS C.PLEASE | | | SPECIFY. | | | | | | 5.AS PER YOUR PERMIT APPLICATION, IT IS STATED THAT | | | THE SCOPE OF WORK INCLUDES CHANGES TO THE FIRE | | | SPRINKLER DEVICES.BE ADVISED, AS PER WEST PALM BEACH | | | FIRE PREVENTION BUREAU, NO SEPARATE PLANS AND PERMIT | | | ARE REQUIRED WHEN THE ALTERATION INVOLVES LESS THAN | | | FIVE (5) HEADS AS LONG AS THE WORK IS DONE BY A | | | CERTIFIED FIRE SPRINKLER CONTRACTOR.HOWEVER, A LAYOUT | | | OF THE SPRINKLER HEADS IN THE AFFECTED AREA ALONG WITH | | | THE MODIFICATIONS WILL BE REQUIRED FOR PLAN REVIEW AND | | | COMPLIANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|