| 2008-10-31 08:11:25 | |
| | ** DENIED REVIEW** |
| | |
| | 1) NOTE: ** A CALL WAS PLACED TO THE CHUCK FROM |
| | FRONTIER BUILDING. LET HIM KNOW THERE WERE SEVERAL |
| | SHEETS IN ONE OF THE SETS WHICH WERE NOT SIGNED OR |
| | SEALED BY THE ENGINEER OF RECORD. AS THIS IS THE ONLY |
| | COMMENT FOR NEW SHEETS NEEDED THESE MAY BE BROUGHT IN |
| | WITHOUT FEE. THE OLD SHEETS WHICH ARE NOT SIGNED OR |
| | SEALED NEED TO BE REMOVED AND HAVE NEW SHEETS INSERTED. |
| | THE MECHANICAL REVIEW STILL NEEDS TO TAKE PLACE. FS |
| | 471.025, FAC 61G15-23.002 |
| | PLEASE SEE LIST BELOW. |
| | E1.1,1.2, 3.0,4.1 ARE NEEDED. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |