| Plan Review Notes For Permit 07040695 |
| Permit Number |
07040695 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-05-20 11:31:54 | ***PROVISOS*** | | | | | | 1.SEPARATE ROOF PERMIT REQUIRED (ENGINEERING & | | | ASSEMBLY NOT PROVIDED) | | | DOR REVIEWED SOPREMA MODIFIED OVER STEEL DECK, NOA | | | 04-0927.05 (ENGINEERING RQ'D FOR ENHANCED FASTENING IF | | | REQUIRED, INSULATION BOARD RQ'D PER PLAN, PRESSURES ON | | | SHEET S1.0 -44,-54.5, -89.8) | | | METAL BUILDING COMPONENTS, CRAFTSMAN SB METAL ROOFING | | | SYSTEM 07-0305.10 (NEED TO SELECT APPROVED ASSEMBLY) | | | | | | 2.REVISE INDEX SHEET TO CORRECTLY REFLECT PAGES IN | | | THE PLAN |
|