| 2008-05-22 13:14:28 | ** DENIED4TH REVIEW** |
| | |
| | ** PLEASE SEE SOME OF THE EXACT SAME COMMENTS FROM |
| | PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE NOT FILLED OUT CORRECTLY. PLEASE SEE THE |
| | CERTIFICATION SHEET DOES NOT CONTAIN THE PRINTED NAME |
| | OF DESIGNER(S) ETC. IN FACT IT LIST THE ENGINEERING |
| | FIRM (KAMM) AS THE ELECTRICAL, MECHANICAL AND PLUMBING |
| | DESIGNER(S). HOW IS THIS POSSIBLE WHEN CLEARLY THE |
| | DESIGNER OF RECORD FOR EACH OF THESE IS NOT THE FIRM |
| | (KAMM). |
| | PLEASE BE SURE THESE ARE DATED WHEN NEW SIGNED AND |
| | SEALED CALCULATIONS ARE COMPLETED AS REQUIRED. PLEASE |
| | COMPLETE. |
| | PLEASE BE SURE THE OWNER AGENT IS SIGNED. |
| | FBC 13-103.1, FAC 61G15-23.002, FS471.025 |
| | |
| | 2) NOTE: PLEASE SEE AS MENTIONED ON PREVIOUS REVIEWS |
| | PLEASE BE SURE ALL LIGHTING ON PLANS IS IN THE INPUT |
| | DATA REPORT FOR ENERGY CALCULATIONS. |
| | THERE ARE STILL FIXTURES ON THE PLANS WHICH ARE NOT IN |
| | THE CALCULATIONS. |
| | PLEASE SEE EXTERIOR LIGHT FIXTURES, SOME OF THESE ARE |
| | LABELED AS EMERGENCY LIGHT FIXTURES WHICH ARE OFF |
| | DURING NORMAL OPERATION. THIS IS NOT POSSIBLE!! THERE |
| | ARE OUTSIDE LIGHTS ON PLANS WHICH ARE EMERGENCY BATTERY |
| | BACK UP FIXTURES HOWEVER THEY ARE ON FOR NORMAL USE AND |
| | GENERAL ILLUMINATION. SOME OF THESE ARE ALSO SHOWN WITH |
| | BATTERY BACK UP. |
| | PLEASE SEE PLANS ALSO LIST ON FIXTURE LEGEND FIXTURES |
| | AS *EXTERIOR* HOWEVER PLANS CLEARLY SHOW THESE INSIDE |
| | THE BUILDING. |
| | PLEASE SEE THE WATTAGE SHALL BE BASED ON THE FIXTURE |
| | RATING, NOT BULBS. |
| | PLEASE SEE THE NUMBER OF FIXTURES ON PLANS AND THE |
| | WATTAGE OF THOSE FIXTURES ARE ONE GAIN NOT ON THE IDR. |
| | FOR EXAMPLE: |
| | ANOTHER WOULD BE SITE LIGHTING PLANS, AND FIXTURES. |
| | NONE FOUND YET, THERE IS MOST CERTAINLY SITE LIGHTING |
| | WHICH WAS EXISTING AND WAS SHOWN ON PREVIOUS PLANS |
| | SUBMITTED. (POLE LIGHTS). WILL THERE BE SITE LIGHTING? |
| | WILL EXISTING POLE LIGHTS BE RE-USED? WILL EXISTING |
| | POLE LIGHTS BE REMOVED? ETC. |
| | FOR EXAMPLE: |
| | PLEASE SEE TRACK LIGHTING DOES NO COORDINATE. MUST USE |
| | MAXIMUM VA PER FIXTURE, OR 30VA PER FT WHICH EVER IS |
| | GREATER. WHERE ARE THESE ON THE IDR? THESE ARE NOT |
| | SHOWN AS LOW VOLTAGE. |
| | PLEASE SEE ANOTHER EXAMPLE IS THE EXTERIOR DOORS. |
| | PLEASE SEE BUILDING REVIEW COMMENTS AS DOORS ON PLANS |
| | ARE NOT THE SAME AS THE IDR. |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. 13-400.3.A |
| | |
| | 3) NOTE: PLEASE SEE THAT ALL EM LTS SHALL BE CIRCUITED |
| | PER 700.12F |
| | |
| | 4) NOTE: PLEASE SEE THE LIFE SAFETY PLANS DO NOT |
| | CORRELATE WITH THE ELECTRICAL PLANS FOR LIGHTING. |
| | PLEASE COORDINATE AND SUBMIT. |
| | FBC 106.1.2 FOR COORDINATION AND LS 101 7.8,7.9. |
| | |
| | 5) NOTE: PLEASE KNOW WHEN PLANS ARE RESUBMITTED ALONG |
| | WITH ENERGY CALCULATIONS THESE ALL SHALL COORDINATE. AS |
| | CORRECT DOCUMENTS WERE NOT SUBMITTED ON SOME OF THE |
| | PREVIOUS REVIEWS FS 553.80(2) WOULD NOT HAVE BEEN A |
| | FEE. PLEASE KNOW IF THE CODE SECTIONS ARE REPEATED ON |
| | THE FOLLOWING REVIEW A 4X FEE WILL BE ASSESSED FOR THE |
| | PLAN REVIEW PORTION OF THE BASE PERMIT FEE AS REQUIRED |
| | BY STATUTE. THIS FEE WILL BE $5,100.00 |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |