Plan Review Notes
Plan Review Notes For Permit 07040695
Permit Number 07040695
Review Stop E
Sequence Number 4
Notes
Date Text
2008-05-22 13:14:28** DENIED4TH REVIEW**
  
 ** PLEASE SEE SOME OF THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING.
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT FILLED OUT CORRECTLY. PLEASE SEE THE
 CERTIFICATION SHEET DOES NOT CONTAIN THE PRINTED NAME
 OF DESIGNER(S) ETC. IN FACT IT LIST THE ENGINEERING
 FIRM (KAMM) AS THE ELECTRICAL, MECHANICAL AND PLUMBING
 DESIGNER(S). HOW IS THIS POSSIBLE WHEN CLEARLY THE
 DESIGNER OF RECORD FOR EACH OF THESE IS NOT THE FIRM
 (KAMM).
 PLEASE BE SURE THESE ARE DATED WHEN NEW SIGNED AND
 SEALED CALCULATIONS ARE COMPLETED AS REQUIRED. PLEASE
 COMPLETE.
 PLEASE BE SURE THE OWNER AGENT IS SIGNED.
 FBC 13-103.1, FAC 61G15-23.002, FS471.025
  
 2) NOTE: PLEASE SEE AS MENTIONED ON PREVIOUS REVIEWS
 PLEASE BE SURE ALL LIGHTING ON PLANS IS IN THE INPUT
 DATA REPORT FOR ENERGY CALCULATIONS.
 THERE ARE STILL FIXTURES ON THE PLANS WHICH ARE NOT IN
 THE CALCULATIONS.
 PLEASE SEE EXTERIOR LIGHT FIXTURES, SOME OF THESE ARE
 LABELED AS EMERGENCY LIGHT FIXTURES WHICH ARE OFF
 DURING NORMAL OPERATION. THIS IS NOT POSSIBLE!! THERE
 ARE OUTSIDE LIGHTS ON PLANS WHICH ARE EMERGENCY BATTERY
 BACK UP FIXTURES HOWEVER THEY ARE ON FOR NORMAL USE AND
 GENERAL ILLUMINATION. SOME OF THESE ARE ALSO SHOWN WITH
 BATTERY BACK UP.
 PLEASE SEE PLANS ALSO LIST ON FIXTURE LEGEND FIXTURES
 AS *EXTERIOR* HOWEVER PLANS CLEARLY SHOW THESE INSIDE
 THE BUILDING.
 PLEASE SEE THE WATTAGE SHALL BE BASED ON THE FIXTURE
 RATING, NOT BULBS.
 PLEASE SEE THE NUMBER OF FIXTURES ON PLANS AND THE
 WATTAGE OF THOSE FIXTURES ARE ONE GAIN NOT ON THE IDR.
 FOR EXAMPLE:
 ANOTHER WOULD BE SITE LIGHTING PLANS, AND FIXTURES.
 NONE FOUND YET, THERE IS MOST CERTAINLY SITE LIGHTING
 WHICH WAS EXISTING AND WAS SHOWN ON PREVIOUS PLANS
 SUBMITTED. (POLE LIGHTS). WILL THERE BE SITE LIGHTING?
 WILL EXISTING POLE LIGHTS BE RE-USED? WILL EXISTING
 POLE LIGHTS BE REMOVED? ETC.
 FOR EXAMPLE:
 PLEASE SEE TRACK LIGHTING DOES NO COORDINATE. MUST USE
 MAXIMUM VA PER FIXTURE, OR 30VA PER FT WHICH EVER IS
 GREATER. WHERE ARE THESE ON THE IDR? THESE ARE NOT
 SHOWN AS LOW VOLTAGE.
 PLEASE SEE ANOTHER EXAMPLE IS THE EXTERIOR DOORS.
 PLEASE SEE BUILDING REVIEW COMMENTS AS DOORS ON PLANS
 ARE NOT THE SAME AS THE IDR.
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. 13-400.3.A
  
 3) NOTE: PLEASE SEE THAT ALL EM LTS SHALL BE CIRCUITED
 PER 700.12F
  
 4) NOTE: PLEASE SEE THE LIFE SAFETY PLANS DO NOT
 CORRELATE WITH THE ELECTRICAL PLANS FOR LIGHTING.
 PLEASE COORDINATE AND SUBMIT.
 FBC 106.1.2 FOR COORDINATION AND LS 101 7.8,7.9.
  
 5) NOTE: PLEASE KNOW WHEN PLANS ARE RESUBMITTED ALONG
 WITH ENERGY CALCULATIONS THESE ALL SHALL COORDINATE. AS
 CORRECT DOCUMENTS WERE NOT SUBMITTED ON SOME OF THE
 PREVIOUS REVIEWS FS 553.80(2) WOULD NOT HAVE BEEN A
 FEE. PLEASE KNOW IF THE CODE SECTIONS ARE REPEATED ON
 THE FOLLOWING REVIEW A 4X FEE WILL BE ASSESSED FOR THE
 PLAN REVIEW PORTION OF THE BASE PERMIT FEE AS REQUIRED
 BY STATUTE. THIS FEE WILL BE $5,100.00
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]