| 2008-03-29 18:02:25 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | MUNICIPAL CODE WPB |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | ******FROM PREVIOUS REVIEWS. |
| | |
| | 1. OK |
| | |
| | 2. SHT AS5.1 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE TOTAL SQUARE FOOT AREA BEING |
| | DRAINED BY EACH ROOF DRAIN AND INDICATE 1/2 AREA OF ALL |
| | VERTICAL WALLS ADDED TO THE SQUARE FOOTAGE IN THE |
| | CALCULATIONS. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE SHEET P3.0 SUBMITTED HAS |
| | THE ADDRESS NW136TH & I-595 SUNRISE FLORIDA. |
| | |
| | 3. SHT AS5.4 SHOW A DRAIN IN THE DUMPSTER ENCLOSURE. |
| | THIS DRAIN IS NOT APPROVED, AS IT WOULD HAVE TO CONNECT |
| | TO THE GREASE INTERCEPTOR WHICH CAN NOT DRAIN STORM |
| | WATER, NOR CAN IT CONNECT TO THE SANITARY FOR THE SAME |
| | REASON. PLEASE INDICATE IF THE ENCLOSURE WILL BE |
| | PROTECTED FROM THE STORM WATER. IF NOT DELETE THE |
| | DRAIN. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE DRAIN IS STILL SHOWN ON |
| | SHT AS5.4. IF THE DRAIN IS TO BE DELETED, DELETE FROM |
| | ALL SHEETS. |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED COMPLETLY. SEE |
| | WATER HAMMER ARRESTORS AT THE WATER HEATER. |
| | ******RESPONSE NOTED, BUT THE SHEET P4.1 SUBMITTED HAS |
| | THE ADDRESS NW136TH & I-595 SUNRISE FLORIDA. |
| | |
| | |
| | 7. OK |
| | ******RESPONSE NOTED, WILL PROVISO THAT INFORMATION |
| | WILL BE REQUIRED AT PLUMBING FINAL. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHTS IR1 & IR2, (NEW SHEETS). AN RPZV BACKFLOW |
| | INSTALLED BY THE PLUMBING CONTRACTOR IS REQUIRED. |
| | PLEASE INDICATE THE LOCATION ON THE IRRIGATION PLANS. |
| | SECTION 608.3.2. BACKFLOW SHALL BE INSTALLED AS CLOSE |
| | TO THE METER AS POSSIBLE ON PRIVATE PROPERTY. |
| | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 2B. SUBMIT A STORM ISOMETRIC RISER DIAGRAM FOR THE |
| | PRIMARY AND ONE FOR THE SECONDARY DRAINAGE SYSTEMS. |
| | SECTION 106.3.5.1.3(7)(13). |
| | ******RESPONSE NOTED, BUT THE SHEET P4.1SUBMITTED HAS |
| | THE ADDRESS NW136TH & I-595 SUNRISE FLORIDA. |
| | |
| | 3B. SHT PS2.0 ROOF DOWNSPOUTS INDICATES "TERMINATE |
| | PIPING APPROXIMATELY 3" FROM WALL" PER SECTION 1506.3 |
| | ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1' FROM THE |
| | STRUCTURAL WALL. PLEASE SHOW COMPLIANCE. |
| | ******RESPONSE NOTED, BUT SHT PS1.0 DOES NOT ADDRESS |
| | COMMENT, SHT PS2.0 STILL INDICATES 3" FROM WALL AND |
| | SHTS P3.0 & P4.1 SUBMITTED HAVE THE ADDRESS NW136TH & |
| | I-595 SUNRISE FLORIDA. |
| | |
| | 4B. OK |
| | |
| | ***********NEW COMMENT*********** |
| | |
| | 1C. NEW IRRIGATION SHEETS. THE ADDRESS ON THE TITLE |
| | BLOCK FOR AVID GROUP DOES NOT REFLECT THE ADDRESS OF |
| | RECORD ON THE FLORIDA STATE DBPR WEBSITE. PLEASE UPDATE |
| | THE TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO |
| | RESUBMITTING TO THE CITY WPB FOR REVIEW. FAC |
| | 61G1-16.004(1) & FS 481.2055. (SEE ATTACHED SHEET). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |