Plan Review Notes
Plan Review Notes For Permit 07040695
Permit Number 07040695
Review Stop P
Sequence Number 3
Notes
Date Text
2008-03-29 18:02:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 MUNICIPAL CODE WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS.
  
 1. OK
  
 2. SHT AS5.1 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE TOTAL SQUARE FOOT AREA BEING
 DRAINED BY EACH ROOF DRAIN AND INDICATE 1/2 AREA OF ALL
 VERTICAL WALLS ADDED TO THE SQUARE FOOTAGE IN THE
 CALCULATIONS.
 ****RESPONSE NOTED, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SHEET P3.0 SUBMITTED HAS
 THE ADDRESS NW136TH & I-595 SUNRISE FLORIDA.
  
 3. SHT AS5.4 SHOW A DRAIN IN THE DUMPSTER ENCLOSURE.
 THIS DRAIN IS NOT APPROVED, AS IT WOULD HAVE TO CONNECT
 TO THE GREASE INTERCEPTOR WHICH CAN NOT DRAIN STORM
 WATER, NOR CAN IT CONNECT TO THE SANITARY FOR THE SAME
 REASON. PLEASE INDICATE IF THE ENCLOSURE WILL BE
 PROTECTED FROM THE STORM WATER. IF NOT DELETE THE
 DRAIN.
 ****RESPONSE NOTED, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE DRAIN IS STILL SHOWN ON
 SHT AS5.4. IF THE DRAIN IS TO BE DELETED, DELETE FROM
 ALL SHEETS.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 ****RESPONSE NOTED, BUT NOT ADDRESSED COMPLETLY. SEE
 WATER HAMMER ARRESTORS AT THE WATER HEATER.
 ******RESPONSE NOTED, BUT THE SHEET P4.1 SUBMITTED HAS
 THE ADDRESS NW136TH & I-595 SUNRISE FLORIDA.
  
  
 7. OK
 ******RESPONSE NOTED, WILL PROVISO THAT INFORMATION
 WILL BE REQUIRED AT PLUMBING FINAL.
  
 **********NEW COMMENTS**********
  
 1B. SHTS IR1 & IR2, (NEW SHEETS). AN RPZV BACKFLOW
 INSTALLED BY THE PLUMBING CONTRACTOR IS REQUIRED.
 PLEASE INDICATE THE LOCATION ON THE IRRIGATION PLANS.
 SECTION 608.3.2. BACKFLOW SHALL BE INSTALLED AS CLOSE
 TO THE METER AS POSSIBLE ON PRIVATE PROPERTY.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2B. SUBMIT A STORM ISOMETRIC RISER DIAGRAM FOR THE
 PRIMARY AND ONE FOR THE SECONDARY DRAINAGE SYSTEMS.
 SECTION 106.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE SHEET P4.1SUBMITTED HAS
 THE ADDRESS NW136TH & I-595 SUNRISE FLORIDA.
  
 3B. SHT PS2.0 ROOF DOWNSPOUTS INDICATES "TERMINATE
 PIPING APPROXIMATELY 3" FROM WALL" PER SECTION 1506.3
 ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1' FROM THE
 STRUCTURAL WALL. PLEASE SHOW COMPLIANCE.
 ******RESPONSE NOTED, BUT SHT PS1.0 DOES NOT ADDRESS
 COMMENT, SHT PS2.0 STILL INDICATES 3" FROM WALL AND
 SHTS P3.0 & P4.1 SUBMITTED HAVE THE ADDRESS NW136TH &
 I-595 SUNRISE FLORIDA.
  
 4B. OK
  
 ***********NEW COMMENT***********
  
 1C. NEW IRRIGATION SHEETS. THE ADDRESS ON THE TITLE
 BLOCK FOR AVID GROUP DOES NOT REFLECT THE ADDRESS OF
 RECORD ON THE FLORIDA STATE DBPR WEBSITE. PLEASE UPDATE
 THE TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW. FAC
 61G1-16.004(1) & FS 481.2055. (SEE ATTACHED SHEET).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]