Plan Review Notes
Plan Review Notes For Permit 07040695
Permit Number 07040695
Review Stop M
Sequence Number 3
Notes
Date Text
2008-03-25 18:09:20REVIEW #: 3RD
 ACTION:DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1.0: THIS PAGE HAS AN ADDRESS FOR A JOB IN THE
 CITY OF SUNRISE, WHILE PAGE M2.0 HAS THE CORRECT WEST
 PALM BEACH ADDRESS. PLEASE SHOW THE CORRECT ADDRESS FOR
 THE PROPOSED WORK ON EACH SHEET.
  
 2. PAGE M1.0 AND PAGE M2.0 HAVE TWO DIFFERENT
 SIGNATURES FROM THE SAME ENGINEER, BASED ON THE STAMP
 BEING USED AND THE TITLE BLOCK. WHICH SIGNATURE IS THE
 LEGAL SIGNATURE OF THE DESIGN PROFESSIONAL? PLEASE
 CORRECT AND RESUBMIT.
  
 3. PAGE MS1.0: CURB DETAIL NOTE SAYS THE DETAIL IS FOR
 REFERENCE ONLY AND THAT A STRUCTURAL ENGINEER WILL
 DETERMINE AND VERIFY CODE COMPLIANCE WITH WIND LOAD
 REQUIREMENTS. NO STRUCTURAL INFORMATION COULD BE FOUND
 IN PLANS REGARDING WIND LOADS FOR OUTDOOR APPLIANCES OR
 ATTACHMENTS TO STRUCTURE. PROVIDE STRUCTURAL
 CALCULATIONS FOR BUILDING PLAN REVIEW DEMONSTRATING
 ATTACHMENTS TO STRUCTURE ARE SUFFICIENT FOR ANTICIPATED
 WIND PRESSURES. ALSO, PROVIDE APPLIANCE MANUFACTURER?S
 DATA SHOWING APPLIANCES HAVE BEEN DESIGNED TO WITHSTAND
 WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13 AND FBCB
 1609.
  
 4. ENERGY CALCULATIONS: FLA/COM V3.00 HAS BEEN
 SUBMITTED. THIS IS NOT THE CORRECT FORM. AN ACCURATELY
 COMPLETED FORM 400A-04R (GENERATED BY THE FLA/COM-2004
 COMPUTER PROGRAM, VERSION 2.5) SHALL BE SUBMITTED IN
 ACCORDANCE WITH FBCB 13-400.3.A.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]