| 2008-03-25 18:09:20 | REVIEW #: 3RD |
| | ACTION:DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M1.0: THIS PAGE HAS AN ADDRESS FOR A JOB IN THE |
| | CITY OF SUNRISE, WHILE PAGE M2.0 HAS THE CORRECT WEST |
| | PALM BEACH ADDRESS. PLEASE SHOW THE CORRECT ADDRESS FOR |
| | THE PROPOSED WORK ON EACH SHEET. |
| | |
| | 2. PAGE M1.0 AND PAGE M2.0 HAVE TWO DIFFERENT |
| | SIGNATURES FROM THE SAME ENGINEER, BASED ON THE STAMP |
| | BEING USED AND THE TITLE BLOCK. WHICH SIGNATURE IS THE |
| | LEGAL SIGNATURE OF THE DESIGN PROFESSIONAL? PLEASE |
| | CORRECT AND RESUBMIT. |
| | |
| | 3. PAGE MS1.0: CURB DETAIL NOTE SAYS THE DETAIL IS FOR |
| | REFERENCE ONLY AND THAT A STRUCTURAL ENGINEER WILL |
| | DETERMINE AND VERIFY CODE COMPLIANCE WITH WIND LOAD |
| | REQUIREMENTS. NO STRUCTURAL INFORMATION COULD BE FOUND |
| | IN PLANS REGARDING WIND LOADS FOR OUTDOOR APPLIANCES OR |
| | ATTACHMENTS TO STRUCTURE. PROVIDE STRUCTURAL |
| | CALCULATIONS FOR BUILDING PLAN REVIEW DEMONSTRATING |
| | ATTACHMENTS TO STRUCTURE ARE SUFFICIENT FOR ANTICIPATED |
| | WIND PRESSURES. ALSO, PROVIDE APPLIANCE MANUFACTURER?S |
| | DATA SHOWING APPLIANCES HAVE BEEN DESIGNED TO WITHSTAND |
| | WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13 AND FBCB |
| | 1609. |
| | |
| | 4. ENERGY CALCULATIONS: FLA/COM V3.00 HAS BEEN |
| | SUBMITTED. THIS IS NOT THE CORRECT FORM. AN ACCURATELY |
| | COMPLETED FORM 400A-04R (GENERATED BY THE FLA/COM-2004 |
| | COMPUTER PROGRAM, VERSION 2.5) SHALL BE SUBMITTED IN |
| | ACCORDANCE WITH FBCB 13-400.3.A. |
| | |