2008-04-04 16:59:50*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEWS STILL NEED TO BE ADDRESSED:
  
 1.CONSTRUCTION, RENOVATION, AND DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.ADD COMMENT TO AN
 APPROPIATE PLAN SHEET OR ADD NFPA 241 TO DESIGN CODE
 SUMMARY ON SHEET G1.0
  
 2.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE
 BOULEVARD.AS PER WEST PALM BEACH CODE,NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.SHOW ACTUAL ADDRESS NUMBERS ON AN
 APPROPIATE EXTERIOR ELEVATION
  
 5.SMOKE DUCT DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER LOCAL CODES.ADD COMMENT TO SHEET TO AN
 APPROPIATE "M" SHEET
  
 *NEW COMMENT:
  
 A.SHEET AS0.1 INDICATES THERE IS A M1.0 & M2.0,
 WHEREASSHEET G1.0 AND M1.0 INDICATES THAT THERE IS
 M1.0, M2.0, AND M3.0;PLEASE CORRELATE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  