Plan Review Notes
Plan Review Notes For Permit 07040695
Permit Number 07040695
Review Stop B
Sequence Number 3
Notes
Date Text
2008-04-03 12:21:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. WHEN RESUBMITTING, INDICATE THE REVISION AND REMOVE
 AND REPLACE ANY PAGES AS NECESSARY.A RESPONSE LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
  
 2. ADVISORY COMMENT REGARDING NOTICE OF COMMENCEMENT,
 FS713.13.
  
 3.FBC1802.2.1, 3RD REQUEST; PLEASE PROVIDE THE SOILS
 INVESTIGATION REPORT. TWO ORIGINAL SETS ARE REQUIRED
 FOR PERMIT ISSUANCE.THE ENGINEER?S RESPONSE LETTER
 STATES THAT THIS WAS ADDRESSED BY ADDING A COMMENT TO
 THE PLAN IN THE FIRST REVIEW.FOR ALL NEW BUILDINGS,
 AND FOR SOME ADDITIONS, SOILS REPORT IS REQUIRED.THIS
 WILL BE REQUIRED PRIOR TO PERMIT ISSUANCE.
  
 4. ADVISORY COMMENT REGARDING THE IMPACT OF
 CONSTRUCTION, FBC*109.3.10.
  
 5.ADVISORY COMMENT REGARDING HURRICANE PROTECTION
 DURING CONSTRUCTION, FBC*109.3.10.1.
  
 6. COMMENTS REGARDING SHEET AS0.1:
  
 6A-6C, ADDRESSED.
  
 6D. 3RD REQUEST, THE DESIGN PRESSURES FOR OPENINGS ARE
 ALL LOW; PLEASE SEE FBC TABLE 1609.6.2.1(2).
  
 3RD REVIEW, MWFRS AND COMPONENT & CLADDING PRESSURES
 DECLARED BY ARCHITECT AND ENGINEER ARE NOT CONSISTENT.
 TO WHICH ONE IS THE BUILDING DESIGNED?PLEASE EITHER
 MAKE THE TWO SETS OF DESIGN PRESSURES THE SAME OR
 ESTABLISH TO WHICH THE BUILDING HAS BEEN DESIGNED AND
 REMOVE ONE.
  
 SHEET AS0.1, SEE THE TABLE PREPARED BY ROBERT H. BURKE,
 JR., ARCHITECT TITLED MAXIMUM DESIGN WIND PRESSURES AND
 THE TABLE TITLED PRESSURES FOR OPENINGS.THE DESIGN
 PRESSURES SPECIFIED ARE TOO LOW FOR THIS WIND ZONE,
 PLEASE SEE FBC TABLES 1609.6.2.1(1) AND (2).IF THESE
 PRESSURES REMAIN ON THE PLAN, PROVIDE CALCULATIONS FOR
 MWFRS AND COMPONENTS AND CLADDING PRESSURES.
  
 SHEET S1.0, PREPARED BY THE STRUCTURAL ENGINEER,
 BRADFORD T. BISHOP, ROOF UPLIFT PRESSURE APPEARS LOW
 FOR ZONE 1 (PROVIDE CALCULATIONS) AND IS TOO LOW FOR
 ZONES 2 AND 3.SEE FBC TABLE 1609.6.2.1(2).
  
 6E. (NEW COMMENT)THIS IS A PLAN CHECK ONLY. GOVERNING
 CODE FOR A PERMIT SHALL BE ESTABLISHED BASED ON
 APPLICATION DATE.PLEASE REVISE GOVERNING CODE TO
 INCLUDE 2007 REVISIONS/SUPPLEMENTS WHICH BECAME
 EFFECTIVE JULY 1, 2007.THIS COMMENT MAY APPLY TO
 OTHER SHEETS; PLEASE CHECK ALL REFERENCES.
  
 7. SEE THE PREVIOUS LIST, AS0.4 SECTION 7720/102(1),
 COMMENT NOT PROPERLY ADDRESSED.THE GOVERNING CODE WAS
 CHANGED TO FBC2006, BUT SHOULD BE FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS (NO FBC2006 IN EXISTENCE).THE
 ENGINEERING STANDARD REFERENCE WAS CHANGED FROM
 ASCE7-98 TO ?ASCE7-02 OR LATEST EDITION?.THIS IS NOT
 CORRECT AS FBC CHAPTER 35 SPECIFICALLY REFERS TO
 ASCE7-02, AND THE LATEST EDITION (ASCE7-05) CANNOT BE
 USED AT THIS TIME.PLEASE REVISE.
  
 ALSO, THIS CHANGE WAS NOT CLOUDED.ALL CHANGES TO THE
 PLAN ARE TO BE CLEARLY INDICATED WITH CLOUDS AND
 REVISION NUMBERS.
  
 8. SHEET S1.0, SEVERAL LOCATIONS, INCLUDE 2007
 REVISIONS/SUPPLEMENTS IN GOVERNING CODE (PLANS
 CURRENTLY DECLARE FBC2004 WITH 2006 REVISIONS).NOTE
 THAT GOVERNING CODE IS BASED ON APPLICATION DATE, AND
 AS THIS IS A PLAN CHECK, GOVERNING CODE MAY CHANGE.
  
 8A-C, ADDRESSED.
  
 8D, SEE COMMENT 6D.THIRD REQUEST.
  
 9. FBC1609.1.4, IMPACT PROTECTION REQUIRED.SOME
 PRODUCT APPROVALS SUBMITTED AND REVIEWED/APPROVED BY
 THE ARCHITECT ARE NON IMPACT.USE OF IMPACT PROTECTION
 ON COMMERCIAL BUILDINGS ARE TO BE APPROVED BY THE
 BUILDING OFFICIAL, SEE ATTACHED.A HURRICANE
 INSTALLATION PLAN PROPOSING USE OF REMOVABLE PANELS MAY
 BE SENT PRIOR TO RESUBMITTAL VIA EMAIL TO [email protected]
 FOR PRELIMINARY REVIEW.NOTE ALSO THAT EXIT DOORS MUST
 BE IMPACT, SEE FBC1003.6.SOME OF THE PRODUCT
 APPROVALS SUBMITTED ARE FOR NON IMPACT GLAZING. PRODUCT
 APPROVALS AND THE ATTACHED INSTALLATION SCHEDULE ARE
 REQUIRED FOR SHUTTER PERMITS.
  
 10. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOAS SUBMITTED, FAC9B72.PLEASE
 PRINT THE STATE PRODUCT APPROVAL FROM THE WEBSITE,
 WWW.FLORIDABUILDING.ORG.IF UNAVAILABLE, PLEASE ADVISE
 AND IF CODE COMPLIANT, A LOCAL PRODUCT APPROVAL WILL BE
 ISSUED USING THE NOA.
  
 SEE PREVIOUS LISTS, ITEMS 10A AND 10B.THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEET MUST BE SUBMITTED
 WITH THE NOA, FAC9B72.
  
 ***ALSO PLEASE NOTE THAT, UPON PERMIT APPLICATION, ALL
 PRODUCT APPROVALS? EXPIRATION DATE WILL BE REVIEWED.
 THE PRODUCT APPROVALS ARE TO BE CURRENT AS OF APPLI
  
 A. STOREFRONT SYSTEM; AS ADVISED, THERE MAY BE ISSUES
 WITH THE ANCHORING AS A STRESS INCREASE MAY HAVE BEEN
 USED IN CALCULATIONS.THE NOA SUBMITTED IS FOR NON
 IMPACT.SEE COMMENT 9; THIS CANNOT BE APPROVED UNTIL A
 PLAN REGARDING SHUTTER INSTALLATION IN THE EVENT OF A
 HURRICANE WARNING IS ISSUED.PROVIDE FLORIDA STATE OR
 LOCAL PRODUCT APPROVAL.
  
 B. PREVIOUS REVIEW NOTED THAT THERE MAY BE ISSUES WITH
 THE READY ACCESS DRIVE THROUGH WINDOW.SEE DETAIL 12
 AS8.1 AND SHEET 1 OF9 (DRAWINGS) OF THE READY ACCESS
 DRIVE THROUGH WINDOW.THE PRODUCT APPROVAL SHOWS A MAX
 FRAME HEIGHT OF 60.5INCHES, THE DETAIL SHOWS A HEIGHT
 OF 5FT3IN.GRAPHICALLY THE HEAD DETAIL 1 THE BUCK IS
 SHOWN AS VERY SMALL, AND THE DETAIL 13 WHICH SHOULD BE
 THE SILL DETAIL IS NOTED AS NOT USED (ALTHOUGH
 REFERENCED ONDETAIL 12C).CLARIFY FRAME SIZE.
  
 C. YKK STOREFRONT DOOR, PREVIOUS LIST REQUESTED THAT
 TYPE OF GLASS BE HIGHLIGHTED.THIS WAS NOT DONE.ALSO
 SEE ITEM 9, IF THIS IS USED IN A REQUIRED EXIT DOOR
 LOCATION, IMPACT REQUIRED.PLEASE NOTE ON THE PRODUCT
 APPROVAL WHERE THIS DOOR WILL BE INSTALLED.
  
 D. INGERSOLL RAND H16-4 OK; PLEASE SEE ITEM 10 AND
 PROVIDE FL PRODUCT APPROVAL.
  
 E. SUPREMA MODIFIED, SEE PREVIOUS LIST, NO SYSTEM
 SELECTED.THE SYSTEM AND ENHANCED FASTENING
 CALCULATIONS REQUIRED (SEE GENERAL LIMITATION #7) CAN
 BE SUBMITTED WITH THE ROOF PERMIT APPLICATION. HOWEVER,
 SEE DETAIL 4 AS5.2, AS6.2, S2.2, S3.1, THE ROOF
 STRUCTURE IS SHOWN AS STEEL.THE PRODUCT APPROVAL
 SUBMITTED IS FOR WOOD DECK, BUT WAS REVIEWED/APPROVED
 BY THE ARCHITECT.PLEASE ADDRESS OR CLARIFY.
  
 F. EFIS SYSTEM, NO PRODUCT APPROVALS SUBMITTED.SEE
 FAC9B72, PRODUCT APPROVALS REQUIRED AND TO BE REVIEWED
 BY DOR PRIOR TO SUBMITTAL.
  
 G. METAL ROOF PRODUCT APPROVAL SUBMITTED, BUT FL
 PRODUCT APPROVAL IS ALSO REQUIRED, AND THIS PRODUCT
 WILL NOT BE REVIEWED UNTIL ROOF COMPONENT & CLADDING
 DESIGN PRESSURES ARE ESTABLISHED.THERE ARE TWO
 SYSTEMS, A1 AND A2.IT APPEARS THAT SYSTEM A1
 LIMITATION MIGHT NOT MEET THE PRESSURES FOR ZONE 3.
 PRIOR TO ROOF PERMIT ISSUANCE, A SYSTEM IS TO BE
 SELECTED.
  
 11. ADDRESSED.
  
 12. ENGINEER'S RESPONSE IS NOTED; 146MPH IS ACCEPTABLE
 AS IT EXCEEDS THE MINIMUM CODE.THE CITY OF WEST PALM
 BEACH IS ENTIRELY IN THE 140MPH ZONE.
  
 13. SEE PREVIOUS LIST, THERE IS STILL A DISCREPANCY
 BETWEEN AS6.3 AND S3.1 DETAIL 1, AND NEITHER IS
 COMPLIANT WITH FBC2114.2.THE ENGINEER'S RESPONSE
 STATES THAT THERE IS NOT SECONDARY POUR, ARCHITECT?S
 DETAIL SHOWS A COLD JOINT.DETAIL 1 S3.1 SHOWS THE
 VENEER SITTING ON WHAT LOOKS LIKE CONCRETE BLOCK, WITH
 JOINTS WHICH DO NOT HAVE A PHYSICAL BARRIER (TERMITES
 CAN GET INTO THE WALL FIRST HORIZONTALLY AT THE BASE OF
 THE BLOCK UNDER THE VENEER, THEN UP THE WALL).PLEASE
 ADDRESS.
  
 FOR ALL DETAILS, PLEASE CONFIRM THAT THERE ARE NO OTHER
 CONFLICTS BETWEEN ARCHITECTURAL AND STRUCTURAL DETAILS,
 OR A AND AS SHEETS.THIS WILL CREATE DELAYS IN THE
 FIELD AS IT IS POSSIBLE THAT, IF TWO DETAILS CONFLICT,
 A REVISION IN THE FIELD MAY BE REQUIRED AND INSPECTIONS
 MAY BE DELAYED UNTIL CONFLICTS ARE RESOLVED THROUGH
 PLAN REVIEW.PLEASE ADDRESS ALL INCONSISTENCIES NOW
 AND NOTE POSSIBLE CHANGES IN THE NEXT RESPONSE LETTER.
 IF DESIGNERS FIND NO INCONSISTENCIES, THIS ITEM DOES
 NOT NEED TO BE ADDRESSED. THIS COMMENT IS MADE AS
 ADVISORY AND AS A COURTESY TO TRY TO ASSIST IN FUTURE
 INSPECTIONS.
  
 14. ADDRESSED.
  
 15. 3RD REQUEST, DETAIL 8 S5.2, ANCHORING OF THE
 CORNICE BRACKET NOT SPECIFIED.BRACKET ANCHORS ARE
 SHOWN GRAPHICALLY BUT NO INFORMATION PROVIDED REGARDING
 MATERIAL, DIAMETER, EMBEDMENT, TYPE.
  
 16. ADDRESSED.
  
 17. PROVISO; AWNINGS UNDER SEPARATE PERMIT.DESIGNER
 GAVE TWO OPTIONS AS DESIGN CRITERIA.
  
 18. ADDRESSED.
  
 19. A2.0 WALL TYPE LEGEND WAS REVISED, WALL TYPE 1
 PREVIOUSLY STATED EXISTING WALL, NOW STATES NEW WALL,
 BUT THE WALL TYPE KEY WAS NOT REVISED.THE
 GRAPHIC/LEGEND STILL SHOWS AN EXISTING WALL ON THE
 CONSTRUCTION PLAN.
  
 NEW COMMENT:
  
 21. AS0.1 STATES (UNDER FBC TABLE 403.1 REQUIRED
 PLUMBING FIXTURES) THAT THIS IS A SHELL PERMIT ONLY AT
 THIS TIME.PLEASE REMOVE.
  
 22.(ADVISORY) PRIOR TO ISSUANCE OF A BUILDING PERMIT,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY,
 561-233-5025.THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.IF THIS HAS
 ALREADY BEEN DONE, PLEASE PROVIDE THE STAMPED FLOOR
 PLAN OR SITE PLAN AND A COPY OF THE RECEIPT.
  
 23. (ADVISORY) AS FIRE SPRINKLERS ARE REQUIRED BY THE
 WESTWARD SHOPPING PLAZA, FIRE SPRINKLER PLANS MUST
 REMAIN IN THE PACKAGE.NOTE THAT THE DESIGNER HAS
 DECLARED A FULLY SPRINKLERED BUILDING, BUT THIS EXCEEDS
 MINIMUM CODE REQUIREMENTS.NO ACTION NEEDED; ADVISORY
 ONLY.
  
 24.SEE ELECTRIC REVIEW COMMENT REGARDING TWO SETS OF
 PLANS INCLUDED IN THIS PERMIT APPLICATION.SUBMITTAL
 OF TWO SETS OF ELEVATIONS, TWO SETS OF LIFE SAFETY,
 ETC. CAUSES SOME CONFUSION.PLEASE SEE OTHER COMMENT
 REGARDING INCONSISTENCIES WITHIN THE PLAN.
  
 25.PLEASE NOTE THAT A BUILDING REVIEW IS REQUIRED
 EACH TIME NEW ENERGY CALCS ARE SUBMITTED.PLEASE
 CONFIRM THAT ALL BUILDING COMPONENTS ON THE ENERGY CALC
 INPUT DATA REPORT ARE CONSISTENT WITH THE PLANS (DOORS,
 WINDOWS, INSULATION, HOT WATER HEATER, FLOOR AREA,
 ETC.).(ADDED 4/8; INFORMED ARCHITECT.)