Plan Review Notes For Permit 07040695
Permit Number 07040695
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-20 18:39:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 MUNICIPAL CODE WPB
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT AS5.1 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE TOTAL SQUARE FOOT AREA BEING
 DRAINED BY EACH ROOF DRAIN AND INDICATE 1/2 AREA OF ALL
 VERTICAL WALLS ADDED TO THE SQUARE FOOTAGE IN THE
 CALCULATIONS.
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 3. SHT AS5.4 SHOW A DRAIN IN THE DUMPSTER ENCLOSURE.
 THIS DRAIN IS NOT APPROVED, AS IT WOULD HAVE TO CONNECT
 TO THE GREASE INTERCEPTOR WHICH CAN NOT DRAIN STORM
 WATER, NOR CAN IT CONNECT TO THE SANITARY FOR THE SAME
 REASON. PLEASE INDICATE IF THE ENCLOSURE WILL BE
 PROTECTED FROM THE STORM WATER. IF NOT DELETE THE
 DRAIN.
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 4. SHTS PS1.0 & PS2.0 THE GREASE INTERCEPTOR SHALL BE
 SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT
 RODNEY COMPO, (561) 822-2272 OR CALVIN WILLIAMS, (561)
 822-2284. THEIR FAX NUMBER IS (561) 2287 & E-MAIL'S ARE
 [email protected] OR [email protected].
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 5. OK
  
 6. SHT A5.0 NOTE #6STATES "FOR WALL TILE SCHED. SEE
 SHEET A4.0" NO WALL TILE SCHEDLUE IS LOCATED ON SHEET
 A4.0. PLEASE CLARIFY. WALLS WITHIN 2FT OF THE W/C'S
 SHALL COMPLY WITH SECTION 1210.2.
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 7. SHT P1.0 THE SIZING FORMULA FOR THE GREASE
 INTERCEPTOR INDICATES AN "EXISTING GREASE INTERCEPTOR.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SIZING TO BE BY THE UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE.
  
 8. OK
  
 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 ****RESPONSE NOTED, BUT NOT ADDRESSED COMPLETLY. SEE
 WATER HAMMER ARRESTORS AT THE WATER HEATER.
  
 7. THE REVERSE OSMOSIS DRINKING WATER TREATMENTS SHALL
 MEET THE REQUIREMENTS OF NSF-58, REVERSE OSMOSIS
 DRINKING WATER TREATMENT UNITS, OR WATER QUALITY
 ASSOCIATION STANDARD S-300, POINT-OF-USE LOW PRESSURE
 REVERSE OSMOSIS DRINKING WATER SYSTEMS. SECTION 611.2.
 PLEASE SUBMIT MANUF SPECIFICATION SHEETS INDICATING
 COMPLIANCE.
 ****RESPONSE NOTED, NOT ADDRESSED. MANUF. SPECIFICATION
 SHEETS REQUIRED.
  
 **********NEW COMMENTS**********
  
 1B. SHTS IR1 & IR2, (NEW SHEETS). AN RPZV BACKFLOW
 INSTALLED BY THE PLUMBING CONTRACTOR IS REQUIRED.
 PLEASE INDICATE THE LOCATION ON THE IRRIGATION PLANS.
 SECTION 608.3.2. BACKFLOW SHALL BE INSTALLED AS CLOSE
 TO THE METER AS POSSIBLE ON PRIVATE PROPERTY.
  
 2B. SUBMIT A STORM ISOMETRIC RISER DIAGRAM FOR THE
 PRIMARY AND ONE FOR THE SECONDARY DRAINAGE SYSTEMS.
 SECTION 106.3.5.1.3(7)(13).
  
 3B. SHT PS2.0 ROOF DOWNSPOUTS INDICATES "TERMINATE
 PIPING APPROXIMATELY 3" FROM WALL" PER SECTION 1506.3
 ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1' FROM THE
 STRUCTURAL WALL. PLEASE SHOW COMPLIANCE.
  
 4B. ENERGY INPUT DATA REPORT DOES NOT REFLECT THE
 PLANS. DATA REPORT INDICATES THE WATER HEATER I/P RT.
 AT 9KW, BUT SHT P1.01 INDICATES THE WATER HEATER AT 12
 KW. PLEASE CORRELATE. FBC-2004 BUILDING SECTION
 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]