| Date |
Text |
| 2007-09-20 18:39:16 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | MUNICIPAL CODE WPB |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHT AS5.1 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE TOTAL SQUARE FOOT AREA BEING |
| | DRAINED BY EACH ROOF DRAIN AND INDICATE 1/2 AREA OF ALL |
| | VERTICAL WALLS ADDED TO THE SQUARE FOOTAGE IN THE |
| | CALCULATIONS. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | |
| | 3. SHT AS5.4 SHOW A DRAIN IN THE DUMPSTER ENCLOSURE. |
| | THIS DRAIN IS NOT APPROVED, AS IT WOULD HAVE TO CONNECT |
| | TO THE GREASE INTERCEPTOR WHICH CAN NOT DRAIN STORM |
| | WATER, NOR CAN IT CONNECT TO THE SANITARY FOR THE SAME |
| | REASON. PLEASE INDICATE IF THE ENCLOSURE WILL BE |
| | PROTECTED FROM THE STORM WATER. IF NOT DELETE THE |
| | DRAIN. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | |
| | 4. SHTS PS1.0 & PS2.0 THE GREASE INTERCEPTOR SHALL BE |
| | SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT |
| | RODNEY COMPO, (561) 822-2272 OR CALVIN WILLIAMS, (561) |
| | 822-2284. THEIR FAX NUMBER IS (561) 2287 & E-MAIL'S ARE |
| | [email protected] OR [email protected]. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | |
| | 5. OK |
| | |
| | 6. SHT A5.0 NOTE #6STATES "FOR WALL TILE SCHED. SEE |
| | SHEET A4.0" NO WALL TILE SCHEDLUE IS LOCATED ON SHEET |
| | A4.0. PLEASE CLARIFY. WALLS WITHIN 2FT OF THE W/C'S |
| | SHALL COMPLY WITH SECTION 1210.2. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | |
| | 7. SHT P1.0 THE SIZING FORMULA FOR THE GREASE |
| | INTERCEPTOR INDICATES AN "EXISTING GREASE INTERCEPTOR. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SIZING TO BE BY THE UTILITY |
| | DEPT. ENVIRONMENTAL COMPLIANCE. |
| | |
| | 8. OK |
| | |
| | 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED COMPLETLY. SEE |
| | WATER HAMMER ARRESTORS AT THE WATER HEATER. |
| | |
| | 7. THE REVERSE OSMOSIS DRINKING WATER TREATMENTS SHALL |
| | MEET THE REQUIREMENTS OF NSF-58, REVERSE OSMOSIS |
| | DRINKING WATER TREATMENT UNITS, OR WATER QUALITY |
| | ASSOCIATION STANDARD S-300, POINT-OF-USE LOW PRESSURE |
| | REVERSE OSMOSIS DRINKING WATER SYSTEMS. SECTION 611.2. |
| | PLEASE SUBMIT MANUF SPECIFICATION SHEETS INDICATING |
| | COMPLIANCE. |
| | ****RESPONSE NOTED, NOT ADDRESSED. MANUF. SPECIFICATION |
| | SHEETS REQUIRED. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHTS IR1 & IR2, (NEW SHEETS). AN RPZV BACKFLOW |
| | INSTALLED BY THE PLUMBING CONTRACTOR IS REQUIRED. |
| | PLEASE INDICATE THE LOCATION ON THE IRRIGATION PLANS. |
| | SECTION 608.3.2. BACKFLOW SHALL BE INSTALLED AS CLOSE |
| | TO THE METER AS POSSIBLE ON PRIVATE PROPERTY. |
| | |
| | 2B. SUBMIT A STORM ISOMETRIC RISER DIAGRAM FOR THE |
| | PRIMARY AND ONE FOR THE SECONDARY DRAINAGE SYSTEMS. |
| | SECTION 106.3.5.1.3(7)(13). |
| | |
| | 3B. SHT PS2.0 ROOF DOWNSPOUTS INDICATES "TERMINATE |
| | PIPING APPROXIMATELY 3" FROM WALL" PER SECTION 1506.3 |
| | ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1' FROM THE |
| | STRUCTURAL WALL. PLEASE SHOW COMPLIANCE. |
| | |
| | 4B. ENERGY INPUT DATA REPORT DOES NOT REFLECT THE |
| | PLANS. DATA REPORT INDICATES THE WATER HEATER I/P RT. |
| | AT 9KW, BUT SHT P1.01 INDICATES THE WATER HEATER AT 12 |
| | KW. PLEASE CORRELATE. FBC-2004 BUILDING SECTION |
| | 13-103. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |