| Plan Review Notes For Permit 07040695 |
| Permit Number |
07040695 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-17 19:19:27 | REVIEW #: 2 | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PG MS1.0: CURB DETAIL, PLEASE REFERENCE THE CORRECT | | | CODES WHICH WERE/ARE IN EFFECT AT TIME OF PERMIT | | | APPLICATION, SUCH AS FBC 2004 AND NOT SBCCI OR SFBC. | | | | | | 2. M1.0 AND M2.0: WHY IS ALL AIR HANDLING EQUIPMENT | | | SHOWN AS EXISTING? THIS PERMIT APPLICATION IS FOR A NEW | | | BUILDING. IS THE PROPOSED EQUIPMENT USED OR BEING | | | RELOCATED FROM ANOTHER STORE? | | | | | | 3. ENERGY CALCULATIONS: INPUT DATA REPORT, LIST EACH | | | PACKAGE UNIT SEPARATELY BY ZONE. FOR ADDITIONAL | | | INFORMATION ON WHAT CONSTITUTES A ZONE, PLEASE SEE FBC | | | 13-407.1.ABC.2.2.1. BY GROUPING ALL A/C UNITS INTO ONE | | | SYSTEM, THE REQUIRED EFFICIENCIES ARE DISTORTED AND AN | | | UNDUE CREDIT FOR EQUIPMENT EFFICIENCY IS GIVEN. PLEASE | | | CORRECT CALCULATIONS AND RESUBMIT. | | | | | | 4. THE WRITTEN RESPONSE TO PREVIOUS REVIEW COMMENT | | | STATED THAT NO EXHAUST FOR OVEN(S) IS REQUIRED OR | | | PROVIDED. HOWEVER, DETAIL 12 ON PG A7.3 SHOWS DUCTWORK | | | ABOVE OVENS THROUGH CASEWORK. PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|