Date Text
2007-10-12 14:19:22***DENIED***
  
 MANY OF THE PREVIOUS FIRE REVIEW COMMENTS HAVE BEEN
 ANSWERED WITH "TO BE SUPPLIED BY OTHERS". IF THESE
 COMMENTS HAVE BEEN ADDRESSED, PLEASE INDICATE WHERE I
 CAN FIND THE RESPONSE OR WHERE ON THE PLANS THEY HAVE
 BEEN ADDRESSED. PLEASE SEE SOME COMMENTS TAKEN FROM THE
 LAST REVIEW:
  
 1) CONSTRUCTION, RENOVATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 2) BUILDING ADDRESS TO BE PROVIDED ON THE PROPER
 ELEVATION. PLEASE INDICATE ON PLANS SHOWING CHARACTERS
 COMPLYING WITH CITY OF WEST PALM BEACH REQUIREMENTS FOR
 COMMERCIAL BUILDINGS.
  
 3) SITE PLAN DOES NOT ILLUSTRATE ANY EXISTING OR NEW
 FIRE HYDRANTS.
  
 4) OK
  
 5) YOUR RESPONSE INDICATES THAT THIS COMMENT HAS BEEN
 ADDRESSED ON M3.0 HOWEVER NO SUCH SHEET WAS SUBMITTED.
  
 6) OK
  
 7) FIRE EXTINGUISHERS TO BE MOUNTED AT DISTANCE NOT TO
 EXCEED 75'.
  
 8) OK
  
 9) OK
  
 NEW COMMENT:
  
 1) PLEASE SEE ZONING COMMENT #6 REGARDING A REQUIRED
 FIRE SPRINKLER SYSTEM. FIRE SPRINKLER LAYOUT IS
 REQUIRED TO BE INCLUDED WITH THIS SUBMITTAL. A
 PROFESSIONAL ENGINEER SHALL SIGN, SEAL AND DATE ALL
 PLANS, SPECIFICATIONS ETC TO BE FILED FOR PUBLIC
 RECORD. SEPARATE SHOP DRAWINGS ARE REQUIRED FOR FIRE
 SPRINKLER AND OR FIRE ALARM SYSTEMS PRIOR TO
 INSTALLATION.
  
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756