2007-09-18 13:34:50***** FAILED *****
  
 PLEASE PROVIDE THE FOLLOWING INFO:
  
 1.YOUR STORM WATER MANAGEMENT SYSTEM REPORT SUBMITTED
 TO US DOES NOT EXPLAIN HOW DID YOU DETERMINE FLOOR
 ELEVATION.FIRST FLOOR ELEVATION MUST MEETFLOOD ZONE
 AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIATO DETERMINE
 THE FIRST FLOOR ELEVATION, MUST MEET THESE MINIMUM
 REQUIREMENTS. PLEASE SHOW CROWN OF THE ROADS
 ELEVATIONS, SIDEWALK ELEVATIONS TOO.
 2.PLEASE SHOW IN YOUR STORM WATER QUALITY CALCULATIONS,
 WHAT CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1"
 OVER ENTIRE SITE OR2.5"CRITERIA, ETC?
 3. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ? PLEASE SHOW ON DRAWINGS, ALSO, WHAT IS TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT. THESE SITE
 AREA MUST BE SAME AS SHOWN IN DRAWINGS AND WATER
 QUALITY CALS.
 4.PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE BEST PIPE TO CONNECT WITH THE STORM
 WATERFROM ALL OTHER STORM WATER PIPES.
 5. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  