Plan Review Notes
Plan Review Notes For Permit 07040695
Permit Number 07040695
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-09 14:45:232007-09-09 14:45:23
  
 *** DENIED 2ND REVIEW ***
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
 STARBUCKS LOCATION AT 2623 OKEECHOBEE BLVD.
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH
 NUMEROUS NEW COMMENTS BASED ON THE CHANGES MADE TO
 MADE, THE PLANS SUBMITTED AND THE SCOPE SHOWN ON PLANS
 NOT ON THIS PROJECT ETC. PLEASE SEE COMMENTS BELOW FOR
 FURTHER EXPLANATION.
  
 1) NOTE: PLEASE SEE THESE PLANS AS SUBMITTED ARE
 SUPPOSED TO BE FOR A * NEW FREE STANDING BUILDING* YET
 MECHANICAL AND ELECTRICAL SHEETS M-1, M-2, E1.0-E4.1
 INDICATE AT NUMEROUS LOCATIONS ITEMS WHICH ARE
 *EXISTING*. THIS IS A NEW BUILDING BEING CONSTRUCTED ON
 AN EMPTY LOT AND ALL OF THESE ELECTRICAL AND MECHANICAL
 ITEMS CAN NOT POSSIBLY EXIST. THE PREVIOUS
 BUILDING/STRUCTURE WHICH WAS A GAS STATION WAS
 DEMOLISHED SOME TIME AGO.
 THIS IS THE SECOND TIME PLANS ARE BEING SUBMITTED WHICH
 SEEMS TO MIX DESIGN WITH THE STARBUCKS REMODEL PROJECT
 WHICH IS AT A COMPLETELY SEPARATE LOCATION. (CORNER OF
 DIXIE HWY AND OKEECHOBEE BLVD)
 PLEASE COORDINATE ALL PLANS, ELECTRICAL AND OTHER
 SHEETS FOR NEW ELECTRICAL. MANY ITEMS NOTED WITH AN *E*
 FOR EXISTING AS WELL AS BEING PRINTED IN LIGHT GRAY AND
 DASHED LINES LEADING TO ALSO BEING EXISTING.
 FBC106.3.5.1.2, 106.1.2, 110.1.2 ETC.
 ** THIS WAS NOTED ON PREVIOUS REVIEW NOTE #2 AS PLANS
 WERE SUBMITTED WITHOUT THE COORDINATION NEEDED.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PANELS, LOADS ETC
 WHICH IS SHOWN ON THE ES SHEETS DO NOT CORRELATE WITH
 THE E-SHEETS AS SUBMITTED.
 PLEASE COORDINATE AND COMPLETE PLANS.
 FBC 106.3.5.1.2, 106.1.2, 106.1
  
 3) NOTE: PLEASE BE SURE ALL TITLE BLOCKS ARE COMPLETE
 WITH ADDRESS. PLEASE SEE ONLY SOME SHEETS CONTAIN THE
 CORRECT ADDRESS. THIS IS FOR OTHER TRADE SHEETS
 (ARCHITECTURAL) AS WELL AS ELECTRICAL SITE PLANS
 SHEETS. PLEASE SEE ALL SHEETS REQUIRED TO MAKE
 ADJUSTMENTS.
 FAC 61G1-16.004, 61G15-23.002, FBC 106.3.5.1.2, 110.1.2
 ETC.
  
 4) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS AT A
 MINIMUM AS WELL AS COVER SHEET(S) WHICH CONTAINS
 REFERENCED CODES FOR PROJECT.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
  
 5) NOTE: PLEASE BE SURE TO SEE FBC 2004W/ 2006
 REVISIONS TO CHAPTER 13. PLEASE BE SURE THE ENERGY
 CALCULATIONS COORDINATE WITH THE PLANS SUBMITTED FOR
 FIXTURES, WATTAGES, AND TYPES. THIS WAS THE SAME NOTE
 ON PLANS AS PREVIOUS REVIEW.
 PLEASE SEE THE PLANS SEEM TO INDICATE MULTIPLE FIXTURES
 BEING USED AT THE SAME LOCATION HOWEVER ENERGY
 CALCULATIONS WERE NOT SUBMITTED FOR ALL OPTION
 FIXTURES. PLEASE DESIGN FOR ONE TYPE OF FIXTURE AT EACH
 LOCATION AND KNOW THAT THESE MAY BE REVISED AT A LATER
 DATE ON THE PROJECT AS LONG AS REVISED PLANS AND ENERGY
 CALCULATIONS ARE SUBMITTED. THE OTHER CHOICE WOULD BE
 TO SUBMIT CALCULATIONS FOR ALL OPTIONS, WHICH WOULD
 STILL NEED REVISED PLANS AND CALCULATIONS ONCE THE
 FINAL CHOICE HAS BEEN MADE SO THE RECORD SETS OF PLANS,
 INSTALLATIONS AND PERMITTING IS ACCURATE FOR SCOPE OF
 WORK.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING AS THE
 ENERGY CALCULATIONS SUBMITTED DO NOT INDICATE THESE.
 PLEASE SEE THE LIGHTING ON PLANS DO NOT CORRELATE WITH
 THE ENERGY CALCULATIONS FOR EXTERIOR LIGHTING PER
 13-415.2.ABC.1.3.
 PLEASE SEE FIXTURE LEGEND IS NOT COMPLETE AS MANY
 FIXTURE WATTAGES ARE NOT COMPLETE AT THIS TIME. PLEASE
 SEE 13-415.1.A, 13-415.2.
 PLEASE SEE THE EXTERIOR LIGHTING ON PLANS DOES NOT
 CORRELATE
  
 6) NOTE: PLEASE SUBMIT THE WIND LOADING INFORMATION FOR
 SITE LIGHTING POLES INCLUDING INFORMATION FOR EFFECTIVE
 PROJECTED AREAS FOR FIXTURES ON POLES. THESE MUST MEET
 THE FBC 140 MPH AND WILL BE REVIEWED BY THE
 BUILDING/STRUCTURAL REVIEWER.
 ** RESPONSE LETTER MENTIONS THIS IS TO BE SUPPLIED BY
 OTHERS; HOWEVER THIS INFORMATION WHICH IS REQUIRED
 COULD NOT BE LOCATED ON PLANS.
 PLEASE KNOW THE LIGHTING POLES, CONSTRUCTION DETAILS;
 WIND LOAD INFORMATION IS REQUIRED AT A MINIMUM AT THIS
 TIME.
 IF THIS INFORMATION IS NOT INCLUDED ON PLANS, ALL SITE
 LIGHTING, PHOTO-METRICS, STRUCTURAL, CIRCUITING,
 CONDUITS ETC, ETC WILL ALL BE REQUIRED TO BE UNDER
 SEPARATE PERMITS, PLANS, FEES ETC.
 ** THIS OFFICE CAN NOT MAKE THIS DETERMINATION FOR THE
 DESIGN TEAM, OWNER OR CONTRACTOR, ONLY THAT PLANS NEED
 TO SHOW COMPLETE AND MINIMUM CODE COMPLIANCE.
  
 7) NOTE:PLEASE SUBMIT AIC RATING FOR ALL SERVICE
 EQUIPMENT INCLUDING MAIN.
 110.9. THIS WAS DONE ON SHEET E-4.0 HOWEVER AS ES 1.0
 DOES NOT CORRELATE, THIS NOTE REMAINS.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE 422.13 FOR WATER HEATER LOADS
 REQUIRED AT 125%. COULD NOT LOCATED THIS AND HOW THIS
 IS SHOWN.
  
 9) NOTE: THE PREVIOUS NOTES 8,9 AND 10 REQUESTED TO
 COMPLETE LOAD CALCULATIONS. THIS PROJECT IS UNDER THE
 2005 NEC/NFPA-70 HOWEVER PLEASE SEE CODE REFERENCED
 SECTIONS ON LOAD CALCULATIONS ON SHEET E4.1 ARE NOT
 FROM THE 2005 NEC>
 PLEASE EXPLAIN AND SHOW WHERE ALL CONTINUOUS LOADS HAVE
 BEEN FIGURED AT THE MINIMUM 125%.
 PLEASE SEE MISSING LOADS FIGURED AND SHOWN FOR SHOW
 WINDOWS.
 PLEASE SEE MISSING LOADS FIGURED AND SHOWN FOR TRACK
 LIGHTING.
 ETC.
 215.3, 230.42, 220.12, 220.14, 220.42,220.43,220.44
 ETC.
  
 10) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 ABOVE WEST WINDOW. MOST WINDOWS ARE SHOWN BUT NOT ALL.
 THIS WAS NOTED ON PREVIOUS REVIEW, HOWEVER PLEASE SEE
 TWO WINDOWS ARE STILL MISSING RECEPTACLES TO BE LOCATED
 ABOVE WINDOWS.
 PLEASE SEE 210.62, AND CALCULATIONS PER 220.43, 220.14
 (6-WINDOW SECTIONS SHOWN, 6-MINIMUM REQUIRED).
  
  
 11) NOTE:** PLEASE KNOW THAT AS THE EXACT PLANS WHICH
 NEED TO BE REVIEWED ARE UNKNOWN AND THERE IS
 COORDINATION NEEDED, ANY CHANGES IN PLANS AND/OR
 DESIGNS MAY GENERATE NEW COMMENTS WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  