| Date |
Text |
| 2007-09-09 14:45:23 | 2007-09-09 14:45:23 |
| | |
| | *** DENIED 2ND REVIEW *** |
| | |
| | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. |
| | STARBUCKS LOCATION AT 2623 OKEECHOBEE BLVD. |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH |
| | NUMEROUS NEW COMMENTS BASED ON THE CHANGES MADE TO |
| | MADE, THE PLANS SUBMITTED AND THE SCOPE SHOWN ON PLANS |
| | NOT ON THIS PROJECT ETC. PLEASE SEE COMMENTS BELOW FOR |
| | FURTHER EXPLANATION. |
| | |
| | 1) NOTE: PLEASE SEE THESE PLANS AS SUBMITTED ARE |
| | SUPPOSED TO BE FOR A * NEW FREE STANDING BUILDING* YET |
| | MECHANICAL AND ELECTRICAL SHEETS M-1, M-2, E1.0-E4.1 |
| | INDICATE AT NUMEROUS LOCATIONS ITEMS WHICH ARE |
| | *EXISTING*. THIS IS A NEW BUILDING BEING CONSTRUCTED ON |
| | AN EMPTY LOT AND ALL OF THESE ELECTRICAL AND MECHANICAL |
| | ITEMS CAN NOT POSSIBLY EXIST. THE PREVIOUS |
| | BUILDING/STRUCTURE WHICH WAS A GAS STATION WAS |
| | DEMOLISHED SOME TIME AGO. |
| | THIS IS THE SECOND TIME PLANS ARE BEING SUBMITTED WHICH |
| | SEEMS TO MIX DESIGN WITH THE STARBUCKS REMODEL PROJECT |
| | WHICH IS AT A COMPLETELY SEPARATE LOCATION. (CORNER OF |
| | DIXIE HWY AND OKEECHOBEE BLVD) |
| | PLEASE COORDINATE ALL PLANS, ELECTRICAL AND OTHER |
| | SHEETS FOR NEW ELECTRICAL. MANY ITEMS NOTED WITH AN *E* |
| | FOR EXISTING AS WELL AS BEING PRINTED IN LIGHT GRAY AND |
| | DASHED LINES LEADING TO ALSO BEING EXISTING. |
| | FBC106.3.5.1.2, 106.1.2, 110.1.2 ETC. |
| | ** THIS WAS NOTED ON PREVIOUS REVIEW NOTE #2 AS PLANS |
| | WERE SUBMITTED WITHOUT THE COORDINATION NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE THE ELECTRICAL PANELS, LOADS ETC |
| | WHICH IS SHOWN ON THE ES SHEETS DO NOT CORRELATE WITH |
| | THE E-SHEETS AS SUBMITTED. |
| | PLEASE COORDINATE AND COMPLETE PLANS. |
| | FBC 106.3.5.1.2, 106.1.2, 106.1 |
| | |
| | 3) NOTE: PLEASE BE SURE ALL TITLE BLOCKS ARE COMPLETE |
| | WITH ADDRESS. PLEASE SEE ONLY SOME SHEETS CONTAIN THE |
| | CORRECT ADDRESS. THIS IS FOR OTHER TRADE SHEETS |
| | (ARCHITECTURAL) AS WELL AS ELECTRICAL SITE PLANS |
| | SHEETS. PLEASE SEE ALL SHEETS REQUIRED TO MAKE |
| | ADJUSTMENTS. |
| | FAC 61G1-16.004, 61G15-23.002, FBC 106.3.5.1.2, 110.1.2 |
| | ETC. |
| | |
| | 4) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS AT A |
| | MINIMUM AS WELL AS COVER SHEET(S) WHICH CONTAINS |
| | REFERENCED CODES FOR PROJECT. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | |
| | 5) NOTE: PLEASE BE SURE TO SEE FBC 2004W/ 2006 |
| | REVISIONS TO CHAPTER 13. PLEASE BE SURE THE ENERGY |
| | CALCULATIONS COORDINATE WITH THE PLANS SUBMITTED FOR |
| | FIXTURES, WATTAGES, AND TYPES. THIS WAS THE SAME NOTE |
| | ON PLANS AS PREVIOUS REVIEW. |
| | PLEASE SEE THE PLANS SEEM TO INDICATE MULTIPLE FIXTURES |
| | BEING USED AT THE SAME LOCATION HOWEVER ENERGY |
| | CALCULATIONS WERE NOT SUBMITTED FOR ALL OPTION |
| | FIXTURES. PLEASE DESIGN FOR ONE TYPE OF FIXTURE AT EACH |
| | LOCATION AND KNOW THAT THESE MAY BE REVISED AT A LATER |
| | DATE ON THE PROJECT AS LONG AS REVISED PLANS AND ENERGY |
| | CALCULATIONS ARE SUBMITTED. THE OTHER CHOICE WOULD BE |
| | TO SUBMIT CALCULATIONS FOR ALL OPTIONS, WHICH WOULD |
| | STILL NEED REVISED PLANS AND CALCULATIONS ONCE THE |
| | FINAL CHOICE HAS BEEN MADE SO THE RECORD SETS OF PLANS, |
| | INSTALLATIONS AND PERMITTING IS ACCURATE FOR SCOPE OF |
| | WORK. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING AS THE |
| | ENERGY CALCULATIONS SUBMITTED DO NOT INDICATE THESE. |
| | PLEASE SEE THE LIGHTING ON PLANS DO NOT CORRELATE WITH |
| | THE ENERGY CALCULATIONS FOR EXTERIOR LIGHTING PER |
| | 13-415.2.ABC.1.3. |
| | PLEASE SEE FIXTURE LEGEND IS NOT COMPLETE AS MANY |
| | FIXTURE WATTAGES ARE NOT COMPLETE AT THIS TIME. PLEASE |
| | SEE 13-415.1.A, 13-415.2. |
| | PLEASE SEE THE EXTERIOR LIGHTING ON PLANS DOES NOT |
| | CORRELATE |
| | |
| | 6) NOTE: PLEASE SUBMIT THE WIND LOADING INFORMATION FOR |
| | SITE LIGHTING POLES INCLUDING INFORMATION FOR EFFECTIVE |
| | PROJECTED AREAS FOR FIXTURES ON POLES. THESE MUST MEET |
| | THE FBC 140 MPH AND WILL BE REVIEWED BY THE |
| | BUILDING/STRUCTURAL REVIEWER. |
| | ** RESPONSE LETTER MENTIONS THIS IS TO BE SUPPLIED BY |
| | OTHERS; HOWEVER THIS INFORMATION WHICH IS REQUIRED |
| | COULD NOT BE LOCATED ON PLANS. |
| | PLEASE KNOW THE LIGHTING POLES, CONSTRUCTION DETAILS; |
| | WIND LOAD INFORMATION IS REQUIRED AT A MINIMUM AT THIS |
| | TIME. |
| | IF THIS INFORMATION IS NOT INCLUDED ON PLANS, ALL SITE |
| | LIGHTING, PHOTO-METRICS, STRUCTURAL, CIRCUITING, |
| | CONDUITS ETC, ETC WILL ALL BE REQUIRED TO BE UNDER |
| | SEPARATE PERMITS, PLANS, FEES ETC. |
| | ** THIS OFFICE CAN NOT MAKE THIS DETERMINATION FOR THE |
| | DESIGN TEAM, OWNER OR CONTRACTOR, ONLY THAT PLANS NEED |
| | TO SHOW COMPLETE AND MINIMUM CODE COMPLIANCE. |
| | |
| | 7) NOTE:PLEASE SUBMIT AIC RATING FOR ALL SERVICE |
| | EQUIPMENT INCLUDING MAIN. |
| | 110.9. THIS WAS DONE ON SHEET E-4.0 HOWEVER AS ES 1.0 |
| | DOES NOT CORRELATE, THIS NOTE REMAINS. |
| | FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE 422.13 FOR WATER HEATER LOADS |
| | REQUIRED AT 125%. COULD NOT LOCATED THIS AND HOW THIS |
| | IS SHOWN. |
| | |
| | 9) NOTE: THE PREVIOUS NOTES 8,9 AND 10 REQUESTED TO |
| | COMPLETE LOAD CALCULATIONS. THIS PROJECT IS UNDER THE |
| | 2005 NEC/NFPA-70 HOWEVER PLEASE SEE CODE REFERENCED |
| | SECTIONS ON LOAD CALCULATIONS ON SHEET E4.1 ARE NOT |
| | FROM THE 2005 NEC> |
| | PLEASE EXPLAIN AND SHOW WHERE ALL CONTINUOUS LOADS HAVE |
| | BEEN FIGURED AT THE MINIMUM 125%. |
| | PLEASE SEE MISSING LOADS FIGURED AND SHOWN FOR SHOW |
| | WINDOWS. |
| | PLEASE SEE MISSING LOADS FIGURED AND SHOWN FOR TRACK |
| | LIGHTING. |
| | ETC. |
| | 215.3, 230.42, 220.12, 220.14, 220.42,220.43,220.44 |
| | ETC. |
| | |
| | 10) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES |
| | ABOVE WEST WINDOW. MOST WINDOWS ARE SHOWN BUT NOT ALL. |
| | THIS WAS NOTED ON PREVIOUS REVIEW, HOWEVER PLEASE SEE |
| | TWO WINDOWS ARE STILL MISSING RECEPTACLES TO BE LOCATED |
| | ABOVE WINDOWS. |
| | PLEASE SEE 210.62, AND CALCULATIONS PER 220.43, 220.14 |
| | (6-WINDOW SECTIONS SHOWN, 6-MINIMUM REQUIRED). |
| | |
| | |
| | 11) NOTE:** PLEASE KNOW THAT AS THE EXACT PLANS WHICH |
| | NEED TO BE REVIEWED ARE UNKNOWN AND THERE IS |
| | COORDINATION NEEDED, ANY CHANGES IN PLANS AND/OR |
| | DESIGNS MAY GENERATE NEW COMMENTS WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |