2007-09-17 12:56:58BUILDING PLAN REVIEW
 PERMIT: 07040695
 ADD: 2633 OKEECHOBEE BLVD
 CONT: "PLAN REVIEW"
 TEL: (561)744-3399
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS, 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
  
 4 ) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERMORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER.THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING IN A DECREASE
 IN EXCESS OF 800SQ FT OF PERMEABLE LAND AREA ON ANY
 PARCELL SHALL AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
  
 5) 109.3.10.1 HURICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6) SHEET AS0.1
 6A-B) COMPLIED.
  
 6C) 2ND REQUEST, BOTTOM CENTER OF PLAN IS ILLEGABLE,
 PLEASE CORRECT.
  
 6D)2ND REQUEST,PRESSURES FOR OPENINGS ARE ALL LOW
 PLEASE SEE 2006 FBC TABLE 1609.6.2.1(2).
  
 7) 2ND REQUEST, SHEET AS0.4 SECTION 7720/ 102 (1)
 CORRECT TO THE FBC 2004/W2006 AMENDMENTS (2) CORRECT
 ASCE 7-98 TO ASCE 7-02
  
 8) SHEET S1.0 :
 8A) COMPLIED.
  
 8B) 2ND REQUESST, CORRECT WIND SPEED ZONE SEE FIGURE
 1609.
  
 8C) COMPLIED.
  
 8D) 2ND REQUEST, WIND PRESSURES FORFLAT ROOF ZONES 1,
 2 & 3 ARE LOW SEE TABLE 1609.6.2.1(2)
  
 8E)2ND REQUEST,WIND PRESSURE ZONES FOR WALL ZONES 4 &
 5 ARE BOTH LOW 10 SQ FT- 100 SQ FT.
  
 9)1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS ,MISSING REPORTS ARE AS FOLLOWS: A)
 STOREFRONT SYSTEMS - THE REPORT SUBMITTED NO IMPACT
 TESTING
 B) READY ACCESS ALUMINIUM DRIVE THROUGH, MAY BE ISSUES
 WITH MULLIONS AND TRNSOM ABOVE
 C) YKK AP 35H OUTSWING DOORHIGHLIGHT TYPE OF GLAZING
 TO BE INSTALLED.
 D) INGERSOLL- RAND H16-4 GOOD FOR +/- 70 OK
 E) SOPREMA NODIFIED ROOFING - NO SUBSYSTEM INDICATED
 F) EFIS SYSTEMS- NO REPORT SUBMITTED
 G) METAL ROOFING- NO REPORT SUBMITTED
 H) TRUSS ANCHORS AND CLIPS ( CURVED CANOPY)
  
 10A)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
  
 10B)PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 11) 2ND REQUEST' READY ACCESS ALUMINIUM DRIVE THROUGH
 WINDOW SHOWN ON SHEET AS2.1 INDICATES A SECTION 3 AS7.1
 IS MISSING, PLEASE PROVIDE.
 11A) SHEET S2.1 SAME WINDOW INDICATES A 4X4 STEEL
 COLUMN BETWEEN TWO WINDOWS BUT NONE IN THE CORENER, IS
 THIS CORNER TO BE BUTT GLAZING?
  
 12)2ND REQUEST, SHEET S2.1 & S2.2 BOTH NEED TO
 CORRECT THE WIND SPEEDZONE, SEE FIGURE 1609.
  
 13) 2ND REQUEST, THERE APPEARS TO BE A DESCREPANCY
 BETWEEN AS6.3 FOUNDATION DETAILS AND S3.1 DETAIL# 1. IN
 ALL CASES SEE 2114.2 REQUIREMENTS FOR TERMITE
 INSPECTION. 2114.2 CONCRETE BEARING LEDGE.
 BRICK , STONE OR OTHER VENEER SHALL BE SUPPORTED BY A
 CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL
 THICKNESS OF THE BRICK , STONE OR OTHER VENEER, WHICH
 IS POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO
 SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL
 CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT
 SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE
 IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL
 BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL
 SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED
 IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW
 GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED
 TO THE CAVITY CREATED BETWEEN THE VENEER AND THE
 FOUNDATION, IN LIEU OF A PHYSICAL BARRIER. EXCEPTION:
 VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL SECURED TO
 THE FOUNDATION SIDEWALL IN ACCORDANCE WITH ACI 530/ASCE
 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152 MM) CLEAR
 INSPECTION SPACE OF THE FOUNDATION SIDEWALL EXTERIOR
 EXIST BETWEEN THE VENEER AND THE TOP OF ANY SOIL, SOD,
 MULCH OR OTHER ORGANIC LANDSCAPING COMPONENT, DECK,
 APRON, PORCH, WALK OR ANY OTHER WORK IMMEDIATELY
 ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 14)2ND REQUEST,AS6.3 AND AS8.1 BOTH INDICATE VARIOUS
 BRICK APPLICATIONS NO MENTION OFWALL TIES OR JOINT
 REINFORCEMENT. 2103.11.2 JOINT REINFORCEMENT. JOINT
 REINFORCEMENT SHALL COMPLY WITH ASTM A 951. THE MAXIMUM
 SPACING OF CROSSWIRES IN LADDER-TYPE JOINT
 REINFORCEMENT AND OF POINT OF CONNECTION OF CROSS WIRES
 TO LONGITUDINAL WIRES OF TRUSS-TYPE REINFORCEMENT SHALL
 BE 16 INCHES (400 MM).
 2103.11.5 ANCHORS, TIES AND ACCESSORIES.
 ANCHORS, TIES AND ACCESSORIES SHALL CONFORM TO THE
 FOLLOWING STANDARDS: ASTM A 36 FOR STRUCTURAL STEEL;
 ASTM A 82 FOR PLAIN STEEL WIRE FOR CONCRETE
 REINFORCEMENT; ASTM A 185 FOR PLAIN STEEL-WELDED WIRE
 FABRIC FOR CONCRETE REINFORCEMENT; ASTM A 167, TYPE
 304, FOR STAINLESS AND HEAT-RESISTING CHROMIUM-NICKEL
 STEEL PLATE, SHEET AND STRIP AND ASTM A 366 FOR
 COLD-ROLLED CARBON STEEL SHEET, COMMERCIAL QUALITY.
  
 15)2ND REQUEST,AS5.2 AND AS6.3 BOTH INDICATE A METAL
 CORNICE SECTION AROUND THE PERIMETER OF THE ROOF. THE
 DETSIL 8 SHEET AS5.2 INDICATES TO SEE THE STRUCTURAL
 SHEETS FOR MORE DETAIL,
 THERE ARE NO STRUCTURAL DETAILS FOR THIS AREAA OF THE
 BUILDING. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 FASTENING OF THIS CORNICE AND HOW IT WILL ACT IN A HIGH
 WIND EVENT.
  
 16) COMPLIED.
  
 17) 2ND REQUEST,AS5.3 DETAIL 3 METAL AWNING PLEASE
 PROVIDE TO WHICH IS THIS AWNING WILL BE DESIGNED TO?
 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED
 ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS
 OF CHAPTER 16 AS SHOWN BELOW:
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90
 MPH
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR OR C AS DEFINED IN
 CHAPTER 16 .
 3105.4.2.2
 THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE
 COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1.MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16
 .
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER
 16 .
 3105.4.2
 THE FABRIC PORTIONS OF AWNINGS FABRIC COVERED FRAMES
 SHALL BE SECURELY LACED, TIED OR OTHERWISE FASTENED TO
 THE FRAME; NO RAFTER OR FRONT BAR WILL BE PERMITTED IN
 POCKETS; AND IN NO CASE SHALL A ROLLING CURTAIN BE
 CAUSED TO OPERATE OVER A CANOPY FRAME.
 3105.4.3
 THE HORIZONTAL PROJECTION OF CANTILEVERED PORTIONS
 SHALL NOT BE GREATER THAN TWO TIMES THE HEIGHT, EXCEPT
 WHERE THE BUILDING CONSTRUCTION DOES NOT PERMIT A
 PROPER INSTALLATION; IN WHICH CASE, VARIANCE MAY BE
 PERMITTED BY THE BUILDING OFFICIAL, BASED ON SPECIAL
 DESIGN AND CONSTRUCTION.
 AWNINGS
 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS.
 3105.5.1 LOADS.
 RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO
 RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE
 EXCEPT THAT STRUCTURES OR PARTS THEREOF WHICH ARE
 INTENDED TO BE REMOVED OR REPOSITIONED DURING PERIODS
 OF HIGH WIND VELOCITY SHALL BE DESIGNED IN THEIR OPEN
 OR EXTENDED POSITION TO DESIGN PRESSURES BASED ON A
 BASIC WIND SPEED OF MINIMUM 90 MPH, 3-SECOND WIND GUST
 WITH APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS
 THAN 10 PSF (478 PA) ROOF LIVE LOAD.
 3105.5.2
 WHERE SUCH STRUCTURE IS INTENDED TO BE FOLDED OR
 OTHERWISE REPOSITIONED TO CLOSE AN OPENING WHEN THE
 BUILDING IS UNATTENDED OR ACT AS A STORM SHUTTER THE
 DESIGN IN THE CLOSED POSITION SHALL ALSO COMPLY WITH
 CHAPTER 16 AND SHALL BE IMPACT RESISTANT IN ACCORDANCE
 WITH SECTION1609.1.4.
 3105.5.3
 STRUCTURES DESIGNED TO BE READILY REMOVED OR
 REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL
 BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR
 PAINTED INSTRUCTIONS TO THE OWNER OR TENANT TO REMOVE
 OR REPOSITION THE STRUCTURE OR PART THEREOF DURING SUCH
 PERIODS OF TIME AS ARE DESIGNATED BY THE U.S. WEATHER
 BUREAU AS BEING A HURRICANE WARNING OR ALERT.
  
 18)2ND REQUEST,AS5.3 CURVED CANOPY SECTION, THESE
 DETAILS DO NOT INDICATE THE WHAT TYPE OF ROOF
 SHEATHING, NOR THICKNESS WILL BE PLACED ON THE CURVED
 ROOF SECTION. THE STRUCTURAL SHEETS3.1 DETAILS SAY TO
 SEE PLAN?
  
 19) 2ND REQUEST, SHEET A2.0 INDICATES THAT WALL TYPE# 1
 IS AN EXISTING WALL? ISN'T THIS A NEW BUILDING?
  
 20-23) COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.