| 2007-06-05 10:56:51 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | MUNICIPAL CODE WPB |
| | |
| | 1. TWO SETS OF DESIGN PLANS WERE SUBMITTED. ONE SET FOR |
| | THE ARCHITECTURAL AND ONE SET FOR THE MEP'S. IS IT THE |
| | INTENT OF THE OWNER TO APPLY SEPARATELY FOR THE SHELL |
| | AND THE BUILD-OUT? PLEASE CLARIFY. |
| | |
| | 2. SHT AS5.1 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE TOTAL SQUARE FOOT AREA BEING |
| | DRAINED BY EACH ROOF DRAIN AND INDICATE 1/2 AREA OF ALL |
| | VERTICAL WALLS ADDED TO THE SQUARE FOOTAGE IN THE |
| | CALCULATIONS. |
| | |
| | 3. SHT AS5.4 SHOW A DRAIN IN THE DUMPSTER ENCLOSURE. |
| | THIS DRAIN IS NOT APPROVED, AS IT WOULD HAVE TO CONNECT |
| | TO THE GREASE INTERCEPTOR WHICH CAN NOT DRAIN STORM |
| | WATER, NOR CAN IT CONNECT TO THE SANITARY FOR THE SAME |
| | REASON. PLEASE INDICATE IF THE ENCLOSURE WILL BE |
| | PROTECTED FROM THE STORM WATER. IF NOT DELETE THE |
| | DRAIN. |
| | |
| | 4. SHTS PS1.0 & PS2.0 THE GREASE INTERCEPTOR SHALL BE |
| | SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT |
| | RODNEY COMPO, (561)822-2272 OR CALVIN WILLIAMS, |
| | (561)822-2284. THEIR FAX NUMBER IS (561) 2287 & |
| | E-MAIL'S ARE [email protected] OR [email protected]. |
| | |
| | 5. SHT PS1.0 & PS2.0 AN RPZV BACKFLOW IS REQUIRED ON |
| | THE WATER SERVICE TO THE BUILDING. SECTION 608.13.2. |
| | SHEETS STATE "SEE CIVIL FOR CONT., BUT NO CIVIL SHEETS |
| | WERE SUBMITTED. PLEASE INDICATE ON THE PLUMBING SHEETS |
| | THAT THERE WILL BE A BACKFLOW INSTALLED ON THE WATER |
| | SERVICE. |
| | |
| | 6. SHT A5.0 NOTE #6STATES "FOR WALL TILE SCHED. SEE |
| | SHEET A4.0" NO WALL TILE SCHEDLUE IS LOCATED ON SHEET |
| | A4.0. PLEASE CLARIFY. WALLS WITHIN 2FT OF THE W/C'S |
| | SHALL COMPLY WITH SECTION 1210.2. |
| | |
| | 7. SHT P1.0 THE SIZING FORMULA FOR THE GREASE |
| | INTERCEPTOR INDICATES AN "EXISTING GREASE INTERCEPTOR. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 8. SHT P4.0 EQUIPMENT AND FIXTURES UTILIZED FOR THE |
| | STORAGE, PREPARATION AND HANDLING OF FOOD SHALL |
| | DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN |
| | AIR GAP, NOT AN AIR BREAK AS SHOWN IN DETAILS 2,6 & 8. |
| | SECTION 802.1.1. THE AIR GAP BETWEEN THE INDIRECT WASTE |
| | PIPE AND THE FLOOD LEVEL RIM OF THE WASTE RECEPTOR |
| | SHALL BE A MINIMUM OF TWICE THE EFFECTIVE OPENING OF |
| | THE INDIRECT WASTE PIPE. SECTION 802.2.1. |
| | |
| | 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 7. THE REVERSE OSMOSIS DRINKING WATER TREATMENTS SHALL |
| | MEET THE REQUIREMENTS OF NSF-58, REVERSE OSMOSIS |
| | DRINKING WATER TREATMENT UNITS, OR WATER QUALITY |
| | ASSOCIATION STANDARD S-300, POINT-OF-USE LOW PRESSURE |
| | REVERSE OSMOSIS DRINKING WATER SYSTEMS. SECTION 611.2. |
| | PLEASE SUBMIT MANUF SPECIFICATION SHEETS INDICATING |
| | COMPLIANCE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |