| Plan Review Notes For Permit 07040695 |
| Permit Number |
07040695 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-11 15:23:34 | --------------DENIED----------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS. | | | FBC CH. 1 AS AMENEDED BY THE CITY OF WEST PALM BEACH | | | | | | | | | 1. TWO DIFFERENT MECHANICAL SECTIONS WERE INCLUDED IN | | | PLANS. PLEASE INCLUDE ONLY ONE MECHANICAL DESIGN IN | | | EACH SET OF PLANS. PGS MS-1,MS-2 SHOW A DIFFERENT | | | DESIGN THAN M1.0-M3.0. PLEASE CLARIFY. FBC 106.1.1. | | | | | | 2. PLEASE SHOW SIZE, LOCATION AND POINT OF DISCHARGE | | | FOR WARMING OVEN DUCT. ALSO, PLEASE SHOW ROOF LAYOUT | | | WITH LOCATION OF EXHAUSTS, VENTS AND OA INTAKES TO SHOW | | | COMPLIANCE WITH FBC,M 401.5 THROUGH 401.5.2. | | | | | | 3. M3.0: HVAC CURB DETAIL STATES "FOR REFERENCE ONLY." | | | NO VERIFICATION OF CODE COMPLIANCE BY STRUCTURAL | | | ENGINEER COULD BE FOUND IN PLANS. PLEASE SHOW WIND LOAD | | | CALCULATIONS FOR BUILDING PLAN REVIEW SHOWING | | | COMPLIANCE WITH FBC CH 16. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|