2007-05-11 15:23:34--------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS.
 FBC CH. 1 AS AMENEDED BY THE CITY OF WEST PALM BEACH
  
  
 1. TWO DIFFERENT MECHANICAL SECTIONS WERE INCLUDED IN
 PLANS. PLEASE INCLUDE ONLY ONE MECHANICAL DESIGN IN
 EACH SET OF PLANS. PGS MS-1,MS-2 SHOW A DIFFERENT
 DESIGN THAN M1.0-M3.0. PLEASE CLARIFY. FBC 106.1.1.
  
 2. PLEASE SHOW SIZE, LOCATION AND POINT OF DISCHARGE
 FOR WARMING OVEN DUCT. ALSO, PLEASE SHOW ROOF LAYOUT
 WITH LOCATION OF EXHAUSTS, VENTS AND OA INTAKES TO SHOW
 COMPLIANCE WITH FBC,M 401.5 THROUGH 401.5.2.
  
 3. M3.0: HVAC CURB DETAIL STATES "FOR REFERENCE ONLY."
 NO VERIFICATION OF CODE COMPLIANCE BY STRUCTURAL
 ENGINEER COULD BE FOUND IN PLANS. PLEASE SHOW WIND LOAD
 CALCULATIONS FOR BUILDING PLAN REVIEW SHOWING
 COMPLIANCE WITH FBC CH 16.
  