| 2007-06-14 15:32:31 | 1. CONSTRUCTION, RENOVATION, AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. BUILDING ADDRESS SHALL BE PROVIDED ON THE PROPER | | | ELEVATION. THE NUMBERS SHALL BE AT LEAST SIX INCH AND | | | ONE INCH WIDE. | | | | | | 3. SITE PLAN DOES NOT ILLUSTRATE ANY EXISTING OR NEW | | | FIRE HYDRANTS. | | | | | | 4. FLOOR PLAN ONLY ILLUSTRATE ONLY ONE EMERGENCY LIGHT | | | FIXTURE. ADDITIONAL FIXTURES WILL BE REQUIRED. PAGE | | | E3.0 DISPLAYS MORE. PLEASE CORRELATE. | | | | | | 5. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE | | | AIR HANDLING UNIT TO SHUT DOWN. | | | | | | 6. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS. INFORMATION FOR CEILINGS ARE | | | LOCATED ON PAGE A3.0. | | | | | | 7. PLEASE ILLUSTRATE THE LOCATIONS OF PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | | | | 8. ALL ELECTRICAL WORK TO COMPLY WITH THE NATIONAL | | | ELECTRICAL CODE. | | | | | | 9. ALL WORK IS SUBJECT TO FIELD INSPECTION AND | | | APPROVAL. | | | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|