| Date |
Text |
| 2007-04-25 16:56:10 | |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR *PLAN |
| | REVIEW ONLY* AND HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | PLEASE KNOW ONCE PLANS ARE CODE COMPLIANT, IF THE |
| | PROJECT HAS NOT BEEN SUBMITTED FOR PERMIT IT WILL STILL |
| | REMAIN IN A FAILED STATUS UNTIL REVIEW OF APPLICATION |
| | FOR PERMIT ETC IS DONE. |
| | |
| | 2) NOTE: PLEASE SEE THAT TWO DIFFERENT SETS OF PLANS |
| | WERE SUBMITTED FOR ALL TRADES INCLUDING ARCHITECTURAL |
| | AND MEP PLANS. |
| | A REVIEW WAS COMMENCED ON THE FIRST SET OF PLANS FROM |
| | KAMM CONSULTING WHICH WAS ISSUED FROM THE POINTE VERDA |
| | BEACH OFFICE WHEN PLANS WERE ALSO DISCOVERED FROM KAMM |
| | CONSULTING WHICH WERE FROM THE DEERFIELD BEACH OFFICE. |
| | TWO SETS OF ELECTRICAL AND DESIGNS. DIFFERENT RISERS |
| | ETC. |
| | PLEASE SUBMIT ONLY TWO SETS OF PLANS FOR ONE DESIGN ON |
| | THE ONE ADDRESS FOR CODE COMPLIANCE REVIEW. |
| | PLEASE BE SURE TITLE BLOCKS ARE COMPLETE WITH ADDRESS. |
| | (ONLY ONE SUBMITTED HAS THE COMPLETE CORRECT ADDRESS). |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. REVIEW COMMENTS |
| | WILL BE BASED ON ONE DESIGN. |
| | FBC 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE INDICATE THE FOLLOWING CODES ON |
| | ELECTRICAL PLANS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | ** PLEASE KNOW THAT ANY OTHER CODES FOR OTHER TRADES |
| | MAY BE REQUIRED. |
| | |
| | 4) NOTE: PLEASE BE SURE TO SEE FBC 2004W/ 2006 |
| | REVISIONS TO CHAPTER 13. PLEASE BE SURE THE ENERGY |
| | CALCULATIONS COORDINATE WITH THE PLANS SUBMITTED FOR |
| | FIXTURES, WATTAGES, AND TYPES. |
| | PLEASE SEE 13-415.ABC.1.2 FOR TRACK LIGHTING. PLEASE |
| | SEE 13-415.AB.1.1, 13-415.1.A, ETC. 13-415.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT THE WIND LOADING INFORMATION FOR |
| | SITE LIGHTING POLES INCLUDING INFORMATION FOR EFFECTIVE |
| | PROJECTED AREAS FOR FIXTURES ON POLES. THESE MUST MEET |
| | THE FBC 140 MPH AND WILL BE REVIEWED BY THE |
| | BUILDING/STRUCTURAL REVIEWER. |
| | |
| | 6) NOTE: PLEASE SEE ANY LOCATION OF THE SERVICE ON THE |
| | SIDE OF THE BUILDING WHICH CONTAINSA DRIVEWAY/PARKING |
| | LOT AREA WHICH IS SUBJECT TO TRUCK AND VEHICLE TRAFFIC. |
| | PLEASE INDICATE THE HEIGHT OF THE RISER AS REQUIRED PER |
| | 230.24B4. |
| | PLEASE ALSO PLACE A NOTE ON PLANS FOR REQUIRED BOLLARDS |
| | FOR PROTECTION OF THE SERVICE EQUIPMENT PER 110.26(F)2 |
| | 7) NOTE: PLEASE SUBMIT AIC RATING FOR ALL SERVICE |
| | EQUIPMENT INCLUDING MAIN. |
| | 110.9, |
| | FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE 422.13 FOR WATER HEATER LOADS |
| | REQUIRED AT 125%. |
| | |
| | 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215.3, 230.42 ETC. |
| | PLEASE COMPLETE LOAD CALCULATIONS. ONE SET CONTAINS |
| | MORE INFORMATION THAN THE OTHER. |
| | |
| | 10) NOTE: PLEASE CLARIFY LOADS FOR TRACK LIGHTING AND |
| | SHOW WINDOWS PER 220.43 A AND B. |
| | |
| | 11) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES |
| | ABOVE WEST WINDOW. MOST WINDOWS ARE SHOWN BUT NOT ALL. |
| | |
| | |
| | 12) NOTE: ** PLEASE KNOW THAT THE BASE PLANS MAY BE |
| | USED AS REFERENCE FOR LOW VOLTAGE WORK AS SHOWN HOWEVER |
| | THE LV SECURITY AND OTHER LV SYSTEMS WILL BE REQUIRED |
| | TO BE UNDER SEPARATE PERMITS AND FEES. |
| | |
| | ** PLEASE KNOW THAT AS THE EXACT PLANS WHICH NEED TO BE |
| | REVIEWED ARE UNKNOWN, THERE MAY BE COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH ARE NOT PRESENT ON THIS REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |