| 2007-06-12 17:57:29 | BUILDING PLAN REVIEW |
| | PERMIT: 07040695 |
| | ADD: 2633 OKEECHOBEE BLVD |
| | CONT: "PLAN REVIEW" |
| | TEL: (561)744-3399 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)FBC 1802.2.1 QUESTIONABLE SOILS, 1802.2.1 |
| | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF |
| | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY |
| | WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 |
| | . |
| | |
| | |
| | 4 ) 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | |
| | 5) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS.ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. IN ADDITION TO THE ABOVE, A |
| | LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 6) SHEET AS0.1 |
| | 6A) PLEASE UPDATE THE APPLICABLE CODE, 2004 FBC WITH |
| | 2006 AMENDMENTS. |
| | |
| | 6B) TABLE 503 HEIGTH AND AREA PLEASE CORRECT ALLOWED |
| | STORIES TO (1). |
| | |
| | 6C) BOTTOM CENTER OF PLAN IS ILLEGABLE, PLEASE |
| | CORRECT. |
| | |
| | 6D) PRESSURES FOR OPENINGS ARE ALL LOW PLEASE SEE 2006 |
| | FBC TABLE 1609.6.2.1(2). |
| | |
| | 7) SHEET AS0.4 SECTION 7720/ 102 (1) CORRECT TO THE FBC |
| | 2004/W2006 AMENDMENTS |
| | |
| | (2) CORRECT ASCE 7-98 TO ASCE 7-02 |
| | |
| | |
| | 8) SHEET S1.0 : |
| | 8A) CORRECT DESIGNED TO THE 2001 FBC |
| | |
| | 8B) CORRECT WIND SPEED ZONE SEE FIGURE1609. |
| | |
| | 8C) CORRECT ASCE 7-98 TO ASCE 7-02 |
| | |
| | 8D) WIND PRESSURES FORFLAT ROOF ZONES 1, 2 & 3 ARE |
| | LOW SEE TABLE 1609.6.2.1(2) |
| | |
| | 8E) WIND PRESSURE ZONES FOR WALL ZONES 4 & 5 ARE BOTH |
| | LOW 10 SQ FT- 100 SQ FT. |
| | |
| | 9)1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS ,MISSING REPORTS ARE AS FOLLOWS:A) |
| | STOREFRONT SYSTEMS - THE REPORT SUBMITTED NO IMPACT |
| | TESTING |
| | B) READY ACCESS ALUMINIUM DRIVE THROUGH, MAY BE ISSUES |
| | WITH MULLIONS AND TRNSOM ABOVE |
| | C) YKK AP 35H OUTSWING DOORHIGHLIGHT TYPE OF GLAZING |
| | TO BE INSTALLED. |
| | D) INGERSOLL- RAND H16-4 GOOD FOR +/- 70 OK |
| | E) SOPREMA NODIFIED ROOFING - NO SUBSYSTEM INDICATED |
| | F) EFIS SYSTEMS- NO REPORT SUBMITTED |
| | G) METAL ROOFING- NO REPORT SUBMITTED |
| | H) TRUSS ANCHORS AND CLIPS ( CURVED CANOPY) |
| | |
| | 10)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 11) READY ACCESS ALUMINIUM DRIVE THROUGH WINDOW SHOWN |
| | ON SHEET AS2.1 INDICATES A SECTION 3 AS7.1 IS MISSING, |
| | PLEASE PROVIDE. |
| | 11A) SHEET S2.1 SAME WINDOW INDICATES A 4X4 STEEL |
| | COLUMN BETWEEN TWO WINDOWS BUT NONE IN THE CORENER, IS |
| | THIS CORNER TO BE BUTT GLAZING? |
| | |
| | 12)SHEET S2.1 & S2.2 BOTH NEED TO CORRECT THE WIND |
| | SPEEDZONE, SEE FIGURE 1609. |
| | |
| | 13) THERE APPEARS TO BE A DESCREPANCY BETWEEN AS6.3 |
| | FOUNDATION DETAILS AND S3.1 DETAIL# 1.IN ALL CASES |
| | SEE 2114.2 REQUIREMENTS FOR TERMITE INSPECTION. 2114.2 |
| | CONCRETE BEARING LEDGE. |
| | BRICK , STONE OR OTHER VENEER SHALL BE SUPPORTED BY A |
| | CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL |
| | THICKNESS OF THE BRICK , STONE OR OTHER VENEER, WHICH |
| | IS POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO |
| | SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL |
| | CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT |
| | SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE |
| | IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL |
| | BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL |
| | SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED |
| | IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW |
| | GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED |
| | TO THE CAVITY CREATED BETWEEN THE VENEER AND THE |
| | FOUNDATION, IN LIEU OF A PHYSICAL BARRIER. EXCEPTION: |
| | VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL SECURED TO |
| | THE FOUNDATION SIDEWALL IN ACCORDANCE WITH ACI 530/ASCE |
| | 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152 MM) CLEAR |
| | INSPECTION SPACE OF THE FOUNDATION SIDEWALL EXTERIOR |
| | EXIST BETWEEN THE VENEER AND THE TOP OF ANY SOIL, SOD, |
| | MULCH OR OTHER ORGANIC LANDSCAPING COMPONENT, DECK, |
| | APRON, PORCH, WALK OR ANY OTHER WORK IMMEDIATELY |
| | ADJACENT TO OR ADJOINING THE STRUCTURE. |
| | |
| | 14)AS6.3 AND AS8.1 BOTH INDICATE VARIOUS BRICK |
| | APPLICATIONS NO MENTION OFWALL TIES OR JOINT |
| | REINFORCEMENT. 2103.11.2 JOINT REINFORCEMENT. JOINT |
| | REINFORCEMENT SHALL COMPLY WITH ASTM A 951. THE MAXIMUM |
| | SPACING OF CROSSWIRES IN LADDER-TYPE JOINT |
| | REINFORCEMENT AND OF POINT OF CONNECTION OF CROSS WIRES |
| | TO LONGITUDINAL WIRES OF TRUSS-TYPE REINFORCEMENT SHALL |
| | BE 16 INCHES (400 MM). |
| | 2103.11.5 ANCHORS, TIES AND ACCESSORIES. |
| | ANCHORS, TIES AND ACCESSORIES SHALL CONFORM TO THE |
| | FOLLOWING STANDARDS: ASTM A 36 FOR STRUCTURAL STEEL; |
| | ASTM A 82 FOR PLAIN STEEL WIRE FOR CONCRETE |
| | REINFORCEMENT; ASTM A 185 FOR PLAIN STEEL-WELDED WIRE |
| | FABRIC FOR CONCRETE REINFORCEMENT; ASTM A 167, TYPE |
| | 304, FOR STAINLESS AND HEAT-RESISTING CHROMIUM-NICKEL |
| | STEEL PLATE, SHEET AND STRIP AND ASTM A 366 FOR |
| | COLD-ROLLED CARBON STEEL SHEET, COMMERCIAL QUALITY. |
| | |
| | 15) AS5.2 AND AS6.3 BOTH INDICATE A METAL CORNICE |
| | SECTION AROUND THE PERIMETER OF THE ROOF. THE DETSIL 8 |
| | SHEET AS5.2 INDICATES TO SEE THE STRUCTURAL SHEETS FOR |
| | MORE DETAIL, |
| | THERE ARE NO STRUCTURAL DETAILS FOR THIS AREAA OF THE |
| | BUILDING. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE |
| | FASTENING OF THIS CORNICE AND HOW IT WILL ACT IN A HIGH |
| | WIND EVENT. |
| | |
| | 16) AS5.2 DETAIL# 1 INDICATES A ROOF DRAIN AND THE |
| | SECONDARY OVER FLOW, THE OVERFLOW IS NOT TO BE AT THE |
| | SAME LEVEL AS THE MAIN DRAIN. OVERFLOW |
| | 1514.4.2 OVERFLOW DRAINS AND SCUPPERS. |
| | WHERE ROOF DRAINS ARE REQUIRED, OVERFLOW DRAINS OR |
| | OVERFLOW SCUPPERS SIZED IN ACCORDANCE WITH FLORIDA |
| | BUILDING CODE, PLUMBING SHALL BE INSTALLED WITH THE |
| | INLET FLOW LINE LOCATED NOT LESS THAN 2 INCHES (51 MM) |
| | OR MORE THAN 4 INCHES (102 MM) ABOVE THE LOW POINT OF |
| | THE FINISHED ROOFING SURFACE, EXCLUDING SUMPS. OVERFLOW |
| | SCUPPERS SHALL BE A MINIMUM OF 4 INCHES (102 MM) IN ANY |
| | DIMENSION AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO |
| | REQUIRED VERTICAL LEADERS, CONDUCTORS OR DOWNSPOUTS. |
| | OVERFLOW DRAINS AND SCUPPERS SHALL ALSO COMPLY WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING , AND SECTION 1617 OF |
| | THIS CODE. |
| | |
| | 17) AS5.3 DETAIL 3 METAL AWNING PLEASE PROVIDE TO WHICH |
| | IS THIS AWNING TO BE DESIGNED T? DESIGN OF THE |
| | STRUCTURAL FRAMING MEMBERS SHALL BE BASED ON RATIONAL |
| | ANALYSIS, USING THE APPLICABLE WIND LOADS OF CHAPTER 16 |
| | AS SHOWN BELOW: |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1.MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 |
| | MPH |
| | 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN |
| | LIFE OF 0.77. |
| | 3.EXPOSURE CATEGORY B FOR OR C AS DEFINED IN |
| | CHAPTER 16 . |
| | 3105.4.2.2 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE |
| | COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| | NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1.MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16 |
| | . |
| | 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN |
| | LIFE OF 0.77. |
| | 3.EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER |
| | 16 . |
| | 3105.4.2 |
| | THE FABRIC PORTIONS OF AWNINGS FABRIC COVERED FRAMES |
| | SHALL BE SECURELY LACED, TIED OR OTHERWISE FASTENED TO |
| | THE FRAME; NO RAFTER OR FRONT BAR WILL BE PERMITTED IN |
| | POCKETS; AND IN NO CASE SHALL A ROLLING CURTAIN BE |
| | CAUSED TO OPERATE OVER A CANOPY FRAME. |
| | 3105.4.3 |
| | THE HORIZONTAL PROJECTION OF CANTILEVERED PORTIONS |
| | SHALL NOT BE GREATER THAN TWO TIMES THE HEIGHT, EXCEPT |
| | WHERE THE BUILDING CONSTRUCTION DOES NOT PERMIT A |
| | PROPER INSTALLATION; IN WHICH CASE, VARIANCE MAY BE |
| | PERMITTED BY THE BUILDING OFFICIAL, BASED ON SPECIAL |
| | DESIGN AND CONSTRUCTION. |
| | AWNINGS |
| | 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. |
| | 3105.5.1 LOADS. |
| | RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO |
| | RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE |
| | EXCEPT THAT STRUCTURES OR PARTS THEREOF WHICH ARE |
| | INTENDED TO BE REMOVED OR REPOSITIONED DURING PERIODS |
| | OF HIGH WIND VELOCITY SHALL BE DESIGNED IN THEIR OPEN |
| | OR EXTENDED POSITION TO DESIGN PRESSURES BASED ON A |
| | BASIC WIND SPEED OF MINIMUM 90 MPH, 3-SECOND WIND GUST |
| | WITH APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS |
| | THAN 10 PSF (478 PA) ROOF LIVE LOAD. |
| | 3105.5.2 |
| | WHERE SUCH STRUCTURE IS INTENDED TO BE FOLDED OR |
| | OTHERWISE REPOSITIONED TO CLOSE AN OPENING WHEN THE |
| | BUILDING IS UNATTENDED OR ACT AS A STORM SHUTTER THE |
| | DESIGN IN THE CLOSED POSITION SHALL ALSO COMPLY WITH |
| | CHAPTER 16 AND SHALL BE IMPACT RESISTANT IN ACCORDANCE |
| | WITH SECTION1609.1.4. |
| | 3105.5.3 |
| | STRUCTURES DESIGNED TO BE READILY REMOVED OR |
| | REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL |
| | BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR |
| | PAINTED INSTRUCTIONS TO THE OWNER OR TENANT TO REMOVE |
| | OR REPOSITION THE STRUCTURE OR PART THEREOF DURING SUCH |
| | PERIODS OF TIME AS ARE DESIGNATED BY THE U.S. WEATHER |
| | BUREAU AS BEING A HURRICANE WARNING OR ALERT. |
| | |
| | 18) AS5.3 CURVED CANOPY SECTION, THESE DETAILS DO NOT |
| | INDICATE WHAT TYPE OF ROOF SHEATHING WILL BE PLACED ON |
| | THE CURVED ROOF SECTION. THE STRUCTURAL SHEETS3.1 |
| | DETAILS SAY TO SEE PLAN? |
| | |
| | 19)SHEET A2.0 INDICATES THAT WALL TYPE# 1 IS AN |
| | EXISTING WALL? ISN'T THIS A NEW BUILDING/ |
| | |
| | 20) AS0.1 INDICATES IN THE OCCUPANCY LOAD A LOAD OF 39 |
| | WHEREAS G1.0 THE PLANS SHOW A OCCUPANT LOAD OF 41 + AN |
| | ADDITIONAL 17 ON AN EXTERIOR PATIO ? |
| | |
| | 21) SITE INFO ESTIMATES THE COST OF $150,000.00, LOW. |
| | |
| | 22) SHEET G2.0 INDICATES THERE TO BE AN EXISTING PATIO, |
| | EXISTING RAILING? |
| | |
| | 23)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |