| Plan Review Notes For Permit 07040689 |
| Permit Number |
07040689 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-11 13:54:26 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 4-30-07 NOTE #2.ARCHITECT | | | BUSINESS LICENSE NUMBER AAC001630 MUST APPEAR IN THE | | | TITLE BLOCK, SEE FAC 61G1-16.003 (2). | | | | | | 2) WOMEN EMPLOYEES RESTROOM REQUIRES THE EXHAUST FAN TO | | | BE 100 CFM'S, THE MEN'S ROOM TO BE 150 CFM'S, AND THE | | | WOMEN CUSTOMERS TO BE 100 CFM'S. SEE 2004 FBC/M TABLE | | | 403.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|