| 2007-04-27 09:24:18 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING CIRCUITING FOR NEW |
| | ELECTRICAL WHICH IS TO BE SHOWN. PLEASE CORRELATE WITH |
| | A PANEL SCHEDULE TO BE SUBMITTED. |
| | PLEASE INCLUDE CONDUCTOR SIZES ALONG WITH OVER CURRENT |
| | PROTECTION DEVICES. |
| | FBC 106.3.5.1.2 |
| | 408.4, 310.16, 240.4 |
| | |
| | 2) NOTE: PLEASE SEE THE LOCATION OF THE NEW ELECTRICAL |
| | PANEL DOES NOT MEET 110.26, 408.7, 240.24 OF THE NEC |
| | FOR MINIMUM CLEARANCES, VICINITY OF EASILY IGNITABLE |
| | MATERIALS ETC. |
| | PLEASE RELOCATE. |
| | |
| | 3) NOTE: PLEASE KNOW DEPENDING ON THE LOCATION OF THE |
| | NEW PANEL, A DISCONNECT MAY BE REQUIRED FOR THE WATER |
| | HEATER. |
| | 422.31 |
| | |
| | 4) NOTE: PLEASE PROVIDE LIGHTING ON PLANS AND |
| | CONTROLS. |
| | PLEASE SEE LS 101 7.8, AND 7.9 AS AN EMERGENCY BATTERY |
| | BACK UP LIGHT OF SOME KIND WILL BE REQUIRED. |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2,OF THE |
| | 2004 FBC W/2006 REVISIONS. |
| | |
| | |
| | 6) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |